Specifications <br /> Mechanical heat detector shall be a System Sensor 5600 series model number listed to Underwriters Laboratories UL 521 for <br /> Heat Detectors for Fire Protective Signaling Systems.The detector shall be either a single-circuit or a dual-circuit type,normally open.The <br /> detector shall be rated for activation at either 135°F(57°C)or 194°F(90oC),and shall activate by means of a fixed temperature thermal sensor, <br /> or a combination fixed temperature/rate-of-rise thermal sensor.The rate-of-rise element shall be activated by a rapid rise in temperature, <br /> approximately 15°F(8.3°C)per minute.The detector shall include a reversible mounting bracket for mounting to 31/2-inch and 4-inch <br /> octagonal,single gang,and 4-inch square back boxes with a square to round plaster ring.Wiring connections shall be made by means of <br /> SEMS screws that shall accommodate 14-22AWG wire.The detector shall contain alphanumeric markings on the exterior of the housing to <br /> identify its temperature rating and activation method.The rate-of-rise element of combination fixed temperature/rate-of-rise models shall be <br /> restorable,to allow for field-testing.The detectors shall include an external collector that shall drop upon activation to identify the unit in alarm. <br /> Physical/Operating <br /> Maximum Installation Temperature 5601 P,5603,5621,and 5623: 100°F(38°C) <br /> 5602,5604,5622,and 5624: 150OF(65.6°C) <br /> Operating Humidity Range 5 to 95%RH non-condensing <br /> Dimensions with mounting bracket Diameter:4.57 inches(11.6cm) <br /> Height: 1.69 inches(4.3cm) <br /> Alarm Temperature 5601 P,5603,5621,and 5623: 135°F(57°C) <br /> 5602,5604,5622,and 5624: 194OF(90°C) <br /> Weight 6 oz.(170 grams) <br /> Rate-of-Rise Threshold 150F(8.3°C)rise per minute(models 5601 P,5602,5621,and 5622 only) <br /> Mounting 31/2-inch octagonal back box <br /> 4-inch octagonal back box <br /> Single gang back box <br /> 4-inch square back box with a square to round plaster ring <br /> Electrical Specifications <br /> Operating Voltage/Contact 6-125VAC/3A <br /> Ratings 6-28VDC/1 A <br /> 125VDC/0.3A <br /> 250VDC/0.1A <br /> Input Terminals 14-22 AWG <br /> e "yd <br /> O O O O O <br /> a o o c o 0 0 0 <br /> 5601 P 5602,5622 5603,5623 5604,5624 5621 <br /> Ordering Information <br /> MethodIdentification <br /> .. <br /> Model Circuit on Exterior Rating Activation Ceiling* <br /> 5601 P Single None 135°F(57°C) Fixed Temperature/Rate-of-Rise 50 feet x 50 feet(15.24m x 15.2m) <br /> 5602 Single Lettering 194°F(90°C) Fixed Temperature/Rate-of-Rise 50 feet x 50 feet(15.24m x 15.2m) <br /> 5603 Single Lettering 135°F(57°C) Fixed Temperature 25 feet x 25 feet(7.62m x 7.62m) <br /> 5604 Single Lettering 194°F(90°C) Fixed Temperature 25 feet x 25 feet(7.62m x 7.62m) <br /> 5621 Dual Lettering 135°F(57°C) Fixed Temperature/Rate-of-Rise 50 feet x 50 feet(15.24m x 15.2m) <br /> 5622 Dual Lettering 194°F(90°C) Fixed Temperature/Rate-of-Rise 50 feet x 50 feet(15.24m x 15.2m) <br /> —► 5623 Dual Lettering 135°F(57°C) Fixed Temperature 25 feet x 25 feet(7.62m x 7.62m) <br /> 5624 Dual Lettering 194°F(90°C) Fixed Temperature 25 feet x 25 feet(7.62m x 7.62m) <br /> `NOTE:Refer to NFPA72 guidelines for spacing reductions when ceiling heights exceed 10 feet. <br /> SYSTEM 3825 Ohio Avenue•St.Charles, IL 60174 ©2013 System Sensor. <br /> Product specifications subject to change without notice.Visit systemsensorcom <br /> Phone:800 SENSOR2•Fax:630 377 6495 or current product information,including the latest version of this data sheet. <br /> SENSOR" <br /> www.systemsensor.com SPDS30001.7/13 <br />