Laserfiche WebLink
ILI-S-E3 ILI-MB-E3/ILI-S-E3 <br /> The Intelligent Loop Interface-Expansion Board(ILI- For instructions on the installation of the ILI-MB-E3 or <br /> S-E3)provides the E3 Series control panel with two ILI-S-E3,refer to the following documents: <br /> additional electrically isolated signaling line circuits. . E3 Series°Expandable Emergency Evacuation <br /> The layout is similarto the ILI-MB-E3 except a number Manual,Part Number:LS10080-051GF-E <br /> of components are omitted.The ILI-S-E3 occupies one <br /> node on the Broadband network.The ILI-S-E3 provides • ILI-MB-E3 Installation Instructions,Part Number: <br /> two signaling line circuits and terminals for the 9000-0579 <br /> connections to up to 159 detectors,159 modules and <br /> 159 addressable sounder bases per SLC in Velociti ILI-S-E3 Installation Instructions,Part Number: <br /> mode.In CLIP mode,each SLC supports 99 detectors 9000-0569 <br /> and 99 modules. For information on the ILI95-MB-E3 and ILI95-S-E3, <br /> Installation refer to the ILI95-E3 Series Data Sheet,Part Number, <br /> 9021-60336. <br /> Typically,the ILI-MB-E3 or ILI-S-E3 can be mounted in For information on the ANX,refer to the ANX Data <br /> the following E3 Series cabinets: Sheet,Part Number,9021-60497. <br /> Cabinet B Backbox:B-Slim-E3 <br /> Cabinet C Backbox:E3-ILI-CPLATE Ordering Information <br /> E3-INCC-CPLATE ILI-MB-E3:Intelligent Loop Interface-Main Board <br /> E3-INX-CPLATE ILI-S-E3:Intelligent Loop Interface-Expansion Board <br /> Cabinet D Backbox:E3-INCC-DPlate <br /> E3-INX-DPLATE <br /> 2 <br />