Technical Data TD450157EN Eluxa horns, horn strobes & strobes
<br /> Effective August 2022
<br /> Table 5. Specifications
<br /> Physical
<br /> Material Red or white textured UV stabilized,colored impregnated engineered plastic.Exceeds 94V-0 UL flammability rating
<br /> Weight Wall: 0.35 Ibs;Ceiling:0.55 Ibs
<br /> Lens Light Emitting Diode(LED)in a rugged Lexan lens
<br /> Dimensions Wall:4.79"H x 2.76"W x 1.18"D, Trimplate:5.25"H x 4.58"W x 0.32"D;Ceiling:6.27"Diameter x 1.69"D
<br /> Operating Temperature Indoor:32°F to 122°F WC to 50°C)and maximum humidity of 93%
<br /> Mounting&Wire Connections
<br /> Mounting(indoor only) Mounting plate included with all models. ELHS and ELST are for wall-mount applications only.ELHN can be used for
<br /> wall and ceiling-mount applications.Wall mounting:Single-gang,ELSBB backboxes or to 4"square with adapter kit.
<br /> ELHN can be used for wall and ceiling-mount applications. ELHSC and ELSTC are for ceiling mount applications only.
<br /> The ELHNC can also be used for wall-mount applications.Ceiling mounting: LSPKBB-C backboxes or to 4"square,1
<br /> 1/2"or 2 1/8"
<br /> Wire Connections #12 through#18 AWG
<br /> Power&General
<br /> Operating voltage 12 VDCNFWR:8-17.5 VDCNFWR;24 VDCNFWR:16-33 VDCNFWR(12 VDC ELHN/ELHNC models only)
<br /> Strobe Output Rating UL 1971,UL 1638,ULC S526:Selectable 15,30,75,110,135,185 candela output for wall models;Selectable 15,30,75,
<br /> 110,150,177 candela output for ceiling models
<br /> Synchronization Models Strobes can be synchronized with Wheelock's DSM Sync Modules,PS Power Supplies or SAFEPATH products,using
<br /> Wheelock patented sync protocol
<br /> Architects and Engineers Specifications output): Continuous,T3, and T3/T4 for fire (T3) and CO (T4) signaling.
<br /> The LED notification appliances shall be Wheelock@ ELHS audible The ELHS audible strobe, ELST strobe, and ELHN audible shall
<br /> visual strobe appliances, ELST visual strobe appliances and ELHN include a hinged mounting plate. Mounting options shall include
<br /> audible appliances for wall and ceiling-mount applications with a low- LED backboxes, single-gang backbox and to 4" square with adapter
<br /> kit for wall mount models and LED Ceiling backboxes and 4" square,
<br /> profile design or approved equals. Special lettering, including AGENT,
<br /> ALERT, EVACUATE, and no lettering, shall be available.The ELHS 1 1/2" or 2 1/8"deep for ceiling models. Two wire appliance wiring
<br /> and ELST strobes shall be listed for UL Standard 1971 (Emergency shall be capable of directly connecting to the mounting base.
<br /> Devices for the Hearing-Impaired)for Indoor Fire Protection Service Removal of an appliance shall result in a supervision fault condition
<br /> and UL 1638(Visible Signaling Devices. The ELHS and ELHN by the Fire Alarm Control Panel (FACP). All notification appliances
<br /> Audibles shall be UL Listed under Standard 464(Fire Protective shall be backwards compatible.
<br /> Signaling). All models shall meet the requirements of FCC Part 15 The ELHS, ELHN and ELST wall models shall have a low profile
<br /> and ICES-003.All inputs shall be compatible with standard reverse measuring 4.79"H x 2.76"W x 1.18"D. The ELHSC, ELHNC and
<br /> polarity supervision of circuit wiring by a Fire Alarm Control Panel ELSTC ceiling models shall have a low profile measuring 6.27"
<br /> (FACP)with the ability to operate from 16 to 33 VDCNFWR. Diameter with 1.69"D.
<br /> The ELHS audible strobe and ELST strobe appliances shall produce When synchronization is required,the appliance shall be compatible
<br /> a flash rate of one (1)flash per second over the Regulated Voltage with Wheelock®'s DSM Sync Modules, PS Power Supplies,
<br /> Range and shall incorporate a Light Emitting Diode (LED)as the SAFEPATH products or other manufacturer's panels with built-in
<br /> light source with a rugged Lexan(D lens.The appliances shall be of Wheelock®Patented Sync Protocol.The strobes shall not drift out
<br /> low current design. The LED strobe flash duration shall be 20 ms. of synchronization at any time during operation. If the sync protocol
<br /> Where Multi-Candela appliances are specified,the strobe intensity fails to operate,the strobe shall revert to a non-synchronized flash-
<br /> shall have 6 field selectable settings at 15, 30, 75, 110, 135 and 185 rate and still maintain (1)flash per second over its Regulated Voltage
<br /> candela for wall mount applications and 15, 30, 75, 110, 150 and 177 Range.The appliance shall also be designed so that the audible
<br /> for ceiling applications.The selector switch for selecting the candela signal may be silenced while maintaining strobe activation when
<br /> shall be tamper resistant. Appliances with candela settings shall used with Wheelock@ patented sync protocol.
<br /> show the candela selection in a visible location at all times when
<br /> installed.
<br /> NFPA 72 2016, UL 1971, UL, 1638, UL 464 ULC-S525-16, ULC-S526-
<br /> The audible shall have a choice of three(3) horn patterns (high &low 16, CSFM, FM, FCC, RoHS, ICES
<br /> rr
<br /> WE ENCOURAGE AND SUPPORT NICET CERTIFICATION
<br /> 3 YEAR WARRANTY
<br /> Eaton
<br /> 1000 Eaton Boulevard ©2022 Eaton
<br /> Cleveland,OH 44122 All Rights Reserved
<br /> United States Printed in USA
<br /> Eaton.com Publication No.TD450157EN
<br /> August 2022
<br /> Life safety&mass notification solutions Eaton is a registered trademark.
<br /> 273 Branchport Ave.
<br /> Long Branch,NJ 07740 All other trademarks are property
<br /> Powering Business Worldwide Eaton.com/Lifesafetynotification of their respective owners.
<br />
|