Laserfiche WebLink
Product Overview — (continued) <br /> Model ZIC-4A contains a microprocessor which Leased Line—Each of the four(4)circuits on Model ZIC-4A <br /> allows notification-circuit outputs to function in a can be configured for connection to a leased line.The <br /> degrade mode —even if the main FireFinder XLS circuits can be programmed to transmit Alarm, <br /> processor or the local-network communication link Supervisory, or Trouble signals. A leased-line module <br /> has failed. In a degrade mode, Model ZIC-4A will (Model LLM-1) is required for this feature. <br /> respond to an Alarm or Trouble from any <br /> intelligent-addressable initiating device or Bell Follower—Each of the four(4)circuits on Model <br /> conventional-zone initiating device connected in ZIC-4A can be configured as a NAC that can follow the input <br /> the same local enclosure. from another NAC in an external fire-alarm control <br /> Standard NAC zone—Each of the four(4)circuits on panel. Circuit 1 on a Model ZIC-4A card within a <br /> Model ZIC-4A can be configured for use as a FireFinder XLS system enclosure can be configured as the <br /> standard Notification Appliance Circuit. The NAC Bell Follower—Master and is connected to the external <br /> output can be used as a steady, strobe- NAC. <br /> synchronized, or zone-coded output. Available Any other ZIC-4A circuit in that enclosure can be <br /> coding includes ANSI Temporal, March Time 120- configured to follow the state of the Master. This feature <br /> pulse-per-minute (PPM), March Time 60 PPM, can be used to synchronize coded or ANSI Temporal patterns <br /> March Time 30 PPM, Canadian Two-stage 30 PPM, for audible sounds with another fire-alarm control panel. <br /> Canadian Two-stage 120 PPM and custom <br /> coding. Outputs may be programmed through logic <br /> to transmit up to three (3) different signal types, Controls and Indicators <br /> depending on event priority. For instance, the same RESET switch Re-initializes Model ZIC-4A card only <br /> circuit can be programmed to transmit the ANSI <br /> Temporal pattern for evacuation, March Time 120 POWER LED Indicates that power is applied to <br /> PPM for tornado notification, and a custom code for Model ZIC-4A <br /> recall. CARD-FAIL LED Illuminates when the card <br /> Standard speaker zone—Each of the four(4)circuits microprocessor has failed <br /> on Model ZIC-4A can be configured for use as a CAN-FAIL LED Illuminates when the CAN <br /> standard speaker circuit in single or dual-channel communication fails and Model ZIC- <br /> systems. Model ZIC-4A can be used with the Model 4A is in degrade mode <br /> ZAM-180 bulk amplifier, or Model ZAC-40 amplifier <br /> card. Each circuit on Model ZIC-4A is limited to 96 HNET-FAIL LED Illuminates when the HNET <br /> Watts per zone. communication fails and Model ZIC- <br /> Releasing zone— Each of the four (4) circuits on 4A is in degrade mode <br /> Model ZIC-4A can be configured for use as a releasing GND-FAULT LED Indicates the detection of a ground- <br /> circuit.This circuit can be used to release FM-200. fault condition (either negative or <br /> For proper supervision of a releasing circuit,the Model positive) on the field wiring of <br /> REL-EOL module must be used. Model REL-EOL can Model ZIC-4A <br /> use power directly from the FireFinder XLS system. ZONE-ACTIVE Illuminates to indicate that the zone <br /> No external, regulated power supply is required. LEDs has been activated either <br /> Municipal Tie—Each of the four(4)circuits on Model automatically or manually. There is <br /> ZIC-4A can be configured so that it can be connected one (1) LED for each zone. <br /> to and activate a municipal city tie box. The circuit TROUBLE LEDs Indicates the presence of a Trouble <br /> meets the requirement of some jurisdictions to allow condition (either an open circuit or <br /> the box to be reset before the fire-alarm control panel. a short circuit) on the zone. <br /> A leased-line module (Model LLM-1) is required for this There is one (1) LED for each <br /> feature. zone. <br /> SIEMENS Industry, Inc. <br /> Building Technologies Division <br />