Laserfiche WebLink
Form 6.2 <br /> Assessment of Sources of Ignition and Adjacent Combustible Materials <br /> A B C I D E <br /> Sources of Ignition and Requirements Is the Facility NFPA 58com liant? Section <br /> # Pertaining to Adjacent Combustible Reference <br /> Materials Yes No NA (2020 Edition) <br /> Are combustible materials not closer than <br /> 1 10 ft. from each container? 0 El ❑ 6.5.3.3 <br /> Is a distance at least 20 ft.provided between <br /> containers and tanks containing flammable ZI 2 liquids with flash point less than 200 OF El ❑ 6.5.3.6 <br /> (e.g.,gasoline,diesel)? <br /> 3 Are electrical equipment and wiring installed per ❑ ❑ ❑ 6.25.2 <br /> Code requirements? <br /> 4 <br /> Is open flame equipment located and used ❑ ❑ ❑ 6.25.3.1 <br /> accordingto Code? <br /> Are ignition control procedures and requirements <br /> 5 duringliquid transfer operations complied with? 0 ❑ El 7.2.3.2 <br /> Is an approved,portable,dry chemical fire <br /> 6 extinguisher of minimum capacity 18 lbs.and ✓❑ ❑ ❑ 6.29.4.2 <br /> having a B:C rating provided in the facility? <br /> Is an approved,portable,dry chemical fire <br /> 7 extinguisher of minimum capacity 18 lbs.and ❑ ❑ El9.3.5 and <br /> having a B:C rating provided on each truck or 9.4.7 <br /> trailer used to transport portable containers? <br /> 8 Is the prohibition on smoking within the facility ❑ El El 7.2.3.2(B)and <br /> premises strictly enforced? 9.4.10 <br /> Note: Check"NA"in the row of any items that are not applicable. <br /> A - 12 <br />