Laserfiche WebLink
Form 9.5 <br /> Evaluation of Low Emission Transfer Equipment <br /> A B C D E F <br /> Proposed for NFPA 58 <br /> Item the facility? Section <br /> # Description Features Reference <br /> Yes No NA 2014 Edition <br /> Transfer into Delivery nozzle and <br /> permanently filler valve-Max. Fixed maximum <br /> 1 mounted ASME liquid release after liquid level gauge not E] E] (A) <br /> containers on transfer of 4 cm3 used during transfer (A)and(B) <br /> vehicles (0.24 in') operations <br /> During product Does not exceed 4 <br /> Transfer into Cm (0.24 in)from a <br /> stationary transfer or post hose of nominal size 1 ❑ ❑ 0 6.30.5.4(A) <br /> ASME containers transfer uncoupling inch or smaller <br /> 2 delivery valve and of the hose,liquid Does not exceed 15 <br /> product volume nozzle released to the cm3(0.91 in')from a ❑ ❑ 0 6.30.5.4(B) <br /> combination atmosphere hose of nominal size <br /> larger than 1 inch <br /> Transfer into Do containers less than 2,001 gal(w.c.)have <br /> stationary ASME an overfilling prevention device or another ❑ ❑ ✓❑ 6.30.5.4(F) <br /> 3 containers approved device? <br /> maximum filling Do containers greater than 2,000 gal(w.c.) <br /> limit have a float gauge or other non-venting ❑ ❑ ✓❑ 6.30.5.4(E) <br /> device? <br /> Transfer into <br /> stationary ASME Not used during routine transfer operations 6.30.5.4 <br /> 4 containers but may be used in calibrating other non- ❑ ❑ (C)and(D) <br /> fixed maximum venting liquid level gauges in the container <br /> liquid level gauge <br /> Note: If the facility does not have a particular feature described in items 2 or 3,check"NA"in column <br /> corresponding to its row. <br /> A - 28 <br />