ARCHITECTS AND ENGINEERS SPECIFICATIONS <br /> General <br /> Weatherproof notification appliances shall be UL listed for outdoor use.Weatherproof Strobe appliances shall be listed under UL Standard <br /> 1638(Standard for Visual Signaling Appliances)for Indoor/Outdoor use and UL Standard 1971 (Standard for Safety Signaling Devices <br /> for Hearing Impaired).The appliances shall be available for optional wall mounting or ceiling mounting to weatherproof backboxes using <br /> either exposed conduit or concealed conduit, or semi-flush mounting to a recessed electrical box in walls or ceilings using Wheelock <br /> mounting accessories. <br /> Weatherproof Strobes <br /> Weatherproof Strobe appliances shall produce a minimum flash rate of 60 flashes per minute over the UL Regulated Voltage Range <br /> of 16 to 33 VDC and shall incorporate a Xenon flashtube. The weatherproof strobes shall be available with UL 1971 candela ratings <br /> up to 185 cd for wall mounting and 177 cd for ceiling mounting. UL 1638 candela ratings up to 180 cd at 77°F shall be available. The <br /> strobes shall operate over an extended temperature range of—40°F to 150°F (-40°C to 66°C) and be listed for maximum humidity of <br /> 95% RH. Strobe inputs shall be polarized for compatibility with standard reverse polarity supervision of circuit wiring by a Fire Alarm <br /> Control Panel (FACP). <br /> Weatherproof Audibles and Audible/Strobe Combinations Weatherproof horns and multitone audibles shall be listed for Indoor/Outdoor <br /> use under UL Standard 464.The horns shall be able to produce a continuous output or a temporal code-3 output that can be synchronized. <br /> The horns shall have at least 3 sound level settings. Horn/Strobe combinations shall be able to be synchronized on a single NAC. <br /> Multitone audibles shall be able to produce 8 distinct tones selectable by dip switch and shall have at least 2 sound level settings.Multitone <br /> Audible/Strobe combinations shall have independent inputs for the audible and strobe. The strobes shall be able to be synchronized. <br /> The audibles shall be able to be coded when operated on a separate NAC. <br /> Weatherproof Speakers and Speaker/Strobes <br /> Weatherproof speakers and speaker/strobes shall be listed for Indoor/Outdoor use under UL Standard 1480.All speakers shall provide <br /> field selectable taps for 1/8W to 8W operation for either 25 VRMS or 70 VRMS audio systems and shall incorporate a sealed back <br /> construction for extra protection and improved audibility. Speakers without strobes shall be Wheelock Series ET-1010. They shall be <br /> listed to produce up to 94 dBA and shall incorporate a vandal resistant grille design. Speaker with strobes shall be Wheelock Series <br /> ET70WP.They shall be available for surface or semi-flush mounting to walls or ceilings and shall be listed to produce up to 93 dBA. <br /> Synchronization Modules <br /> When synchronization of strobes or temporal code-3 audibles is required,the appliances shall be compatible with the Wheelock Series <br /> DSM Sync Modules, Wheelock Power Supplies or other manufacturers panels with built-in Wheelock Patented Sync Protocol. The <br /> strobes and audibles shall not drift out of synchronization at any time during operation. <br /> Series ASWP audibles and strobes shall be able to be synchronized on a 2-wire circuit with the ability to silence the audible if required. <br /> The strobes on Series MT multitone audible/strobe appliances shall be able to be synchronized and shall be able to be operated on a <br /> separate circuit from the audibles while the audible circuit is connected to a coded or continuous NAC. <br /> Weatherproof Mounting Accessories <br /> Weatherproof mounting options shall include surface mounting or semi-flush mounting to walls or ceilings.Surface mounted appliances <br /> shall mount to Wheelock 1013, WBB, WPBB or WPSBB weatherproof backboxes using either exposed conduit or concealed conduit. <br /> For concealed conduit the weatherproof backbox shall be mounted to a recessed electrical box with Wheelock's WP-KIT to provide a <br /> weatherproof seal for the electrical box. Semi-flush mounted appliances shall mount to a recessed electrical box using Wheelock WFP <br /> or WFPA flush plates to provide a weatherproof seal between the electrical box and the appliance. <br /> WE ENCOURAGE AND SUPPORT NICET CERTIFICATION <br /> 3 YEAR WARRANTY <br /> S9004 WP 11/12 <br /> NJ Location <br /> 273 Branchport Ave. <br /> Long Branch, NJ 07740 <br /> 800-631-2148 <br /> Cooper Notification is Wheelock® MEDC SAFEPATH® WAVE ii COOPER Notification <br />