SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3 <br />DATE: 6/20/2024LE\HYDRAULIC CALCULATIONS\HASS FILES\NC24103 STANDPIPE.SDF <br />JOB TITLE: STANDPIPE <br />(3) Total pressure at each node is used in balancing the system. <br />Maximum water velocity is 16.6 ft/sec at pipe 38. <br />(4) Items listed in bold print on the cover sheet <br />are automatically transferred from the calculation report. <br />(5) Available pressure at source node F2 under full flow conditions is <br />150.00 psi with a flow of 749.99 gpm. <br />(6) PIPE FITTINGS TABLE <br />User Pipe Table Name: SMITH <br />PAGE: Y MATERIAL: SCH7 HWC: 120 <br />Diameter Equivalent Fitting Lengths in Feet <br />(in) E T F C B G A D x <br />Ell Tee 45 ChkVly BfyVly GatVly AlmChk DPVly flex <br />4.298 9.30 31.90 4.70 24.70 7.80 3.00 28.90 28.90 0.00 <br />