Laserfiche WebLink
CIRCUIT/CONDUCTOR SCHEDULE <br /> ID SETS CONDUCTORS (CU) CONDUIT FROM TO VIA VAULTS NOTES <br /> 4M1F 5 4#600 KCMIL 4- SNOPUD XFMR SWBD 4M1 SERVICE CONDUCTORS <br /> VM2P, VMlP. <br /> 4S1F 1 4#250 KCMIL, 1#2G 4" SWBD 4M1 PANEL 4S1 VS5P, V56P V51P, VS2P, VS3P, VS4P, <br /> SGSX 1 2#4, 1#8G 1' PANEL 4S1 XFMR XG1 <br /> SGSF 1 311/0, 1#6G 1-1/2' XFMR XG1 GUARD SHACK <br /> 2S1X 1 2#6, 1#10G 1 PANEL 4S1 XFMR XS1 <br /> 2S1F 1 4#1, 1#6G 1-1/2" XFMR XS1 PANEL 2S1 XFMR GROUND WIRE 1#8 CU <br /> 4W1F 3 41600 KCMIL, 1#4/OG 4' SWBD 4M1 PANEL 4W1 VM2P, VW1P, VW2P <br /> LSTS 1 3#1, 1#8G 1-1/2' PANEL 01 MANUAL TRANSFER SWITCH <br /> LSGR 1 3#1/0, 1#8G 1-1/2' GENERATOR SET MANUAL TRANSFER SWITCH CONTROL PANEL <br /> LSCP 1 311/0, 1#8G 4- GEN MTS LIFT STATION CTRL PANEL VW2P, VW3P CONTROL PANEL <br /> TRCP 1 4#250 KCMIL, 1#2G 4' PANEL 01 TREATMENT CTRL PANEL VW2P, VW3P, VW4P CONTROL PANEL <br /> 4P1F 2 4#250 KCMIL, 1#2G 4" SWBD 4M1 PANEL 4P1 VM2P, VM1P, VN1P, VN2P, VN3P, VN4P, <br /> VNSP <br /> LSBX 1 211/0, 1#6G 1-1/2' PANEL 4P1 XFMR XL1 <br /> LSBF 1 314/0, 1#4G 2' XFMR XL1 LONGSHOREMAN BREAK RM <br /> LSRX 1 2#1/0, 1#6G 1-1/2' PANEL 4P1 XFMR XI-2 <br /> LSRF 1 3#4/0, 1#4G 2' XFMR XI-2 LONGSHOREMAN REST RM <br /> 2P1X 1 3#6, 1#10G 1 PANEL 4P1 XFMR XP1 <br /> 2P1F 1 4#1, 1#6G 1-1/2" XFMR XP1 PANEL 2P1 <br /> LP01-04AF 1 3#4, 111 OG 4' PANEL 41-1 POLES LP01-LP04 VM2P, VW1 P, VW2P, VW3P, VW4P, VWSP, <br /> VW6P <br /> 4, 1 10G 4" PANEL 4L1 POLES LP05-LP10 VM2P, VM1P, VN1P, VN2P, VN3P, VN4P, <br /> LP05-10AF 1 3 <br /> # # VS1 P, VS2P, VS3P, VS4P <br /> LP11-14AF 1 3#4, 1#10G 4" PANEL 4L1 POLES LP11-14 �P VM1P, VE1P, VE2P, VE3P, VE4P, <br /> LP01-04SF 1 2#10, 1#10G 4' PANEL 41-1 POLES LP01-LP04 VW6P VW1P, VW2P, VW3P, VW4P, VW5P, LIGHTS E SAME 4" CONDUIT AS AREA <br /> 10, 1 10G 4" PANEL 4L7 POLES LP05-LP10 VM2P, VM1P, VN1P, VN2P, VN3P, VN4P, USE THE SAME 4' CONDUIT AS AREA <br /> LPOS-tOSF 1 2 <br /> # # VS1P, VS2P, VS3P, VS4P LIGHTS <br /> LP11-14SF 1 2#10, 1#10G 4' PANEL 41-1 POLES LP11-14 �P VM1P, VE1P, VE2P, VE3P, VE4P, USE LIGHTS E SAME 4" CONDUIT AS AREA <br /> MPZF1 1 2#4, 1#6G 4- SWBD 4M1 WEST VAULTS <br /> MPZF2 1 2#2, 1#4G 4 SWBD 4M1 SOUTH VAULTS <br /> E <br /> N MPZF3 1 2#2, 1#4G 4" SWBD 4M1 EAST VAULTS <br /> 0 <br /> MPZF 1 2#10, 1#10G 2' VAULT MPZ <br /> o IF SHEET IS LESS THAN 22x34 LV <br /> cn <br /> REDUCE SCALE ACCORDINGLY <br /> o PD. SI��� s� PORT OF EVERETT DWG. N0. c W <br /> ��OI \ g D. 0 ur. LIS NONE E6.2 <br /> 9 �, °�`N °"'� NORTON TERMINAL DEVELOPMENT CIP NO. <br /> Port O N D. SIATERLIS 05/07/2021 1-8-900-05 O <br /> a ASSOCIATESEVOCT ,INC. & MTCA 3RD INTERIM ACTION Z <br /> ENGINEERS-CONSULTANTS DOWN M CHECKED BY. <br /> c ,�,sN�,,,,,��,,,,,,, C. SMITH S. BARTKOSKE PRaEcr <br /> w� ��, /2,/zD� DKSm ,em CIRCUIT/CONDUCTOR <br /> No. MT-NT-2o21-oz.2 <br /> o P.O. BOX 538 Waal 3u«m rn twct 3cxasoo (206)2435022 www.elcon.am O <br /> N -fa NO-LID IS300 CHRISTENSEN ROAD,STE 330 TONAL �� <br /> v EVERETT, WA 98206 /07/202 D16 FOR LTIY REVIEW V <br /> SEATTLE,WA 9B1 B8 SCHEDULE SHEET N0. 127 OF 150 <br /> i (425) 259-3I64 No. DATE ar REVISION NO. DATE By REv�sia+ b/18/21 <br />