LUMINAIRE SCHEDULE GENERAL NOTES
<br /> LUMINAIRE LUM TYPE LAMP VOLTS LOAD LUMINAIRE DESCRIPTION LAMPS TYPE & COLOR FINISH MOUNTING MANUFACTURER/SE 1. SEE DRAWING E7.3 THRU E7.6 FOR LUMINAIRE COORDINATION WITH
<br /> SYMBOL TYPE (WATTS) TEMP RIES # LIGHTING CONTROLS.
<br /> F4 LED 480V 530 HIGH STRENGTH AL5052 ALUMINUM BODY, WEATHER RESISTANT (1) LED BOARD, FACTORY POLE PHOENIX #HL 2. PROVIDE CONTROL WIRING AS SPECIFIED BY LIGHTING CONTROL
<br /> POWDER COAT, UV-RESISTANT POLYCARBONATE LENS, IP66 3000'K STANDARD (HIGHLAND SERIES) MANUFACTURER'S RECOMMENDATIONS.
<br /> RATED, PIPE MOUNT, GLARE GUARD, 0-10V DIMMING DRIVER, POWDERCOAT OR APPROVED
<br /> NEMA 7-PIN RECEPTACLE WITH SHORTING CAP. SEE LIGHT EQUAL 3. ALL EXTERIOR FIXTURES SHALL BE RATED FOR USE DOWN TO
<br /> POLE SCHEDULE FOR HEAD QUANTITIES PER POLE AND ARM 1O'F.
<br /> LENGTHS.
<br /> TYPE 4 DISTRIBUTION, NOMINAL 34,000 MAX CANDELA AT 4. VERIFY VOLTAGE FROM CIRCUITRY AS INDICATED ON DRAWINGS
<br /> 280'H, 70-V PRIOR TO LUMINAIRE PROCUREMENT.
<br /> 70,700 MINIMUM LUMINAIRE LUMENS
<br /> F4L LED 480V 250 SAME AS F4 BUT LOWER LUMEN PACKAGE. SEE F4 SEE F4 SEE F4 PHOENIX #HL 5. REFER TO THE LIGHT POLE SCHEDULE FOR FIXTURE QUANTITIES,
<br /> 14,900 MAX CANDELA AT 225'H, 63-V (HIGHLAND SERIES) POLE HEIGHTS AND OTHER INFORMATION AT EACH POLE LOCATION.
<br /> 33,700 MINIMUM LUMINAIRE LUMENS OR APPROVED
<br /> EQUAL 6. PROVIDE SALTWATER WEATHERPROOF GASKETING BETWEEN
<br /> DISSIMILAR METALS TO PREVENT ELECTROLYSIS AND CORROSION.
<br /> F5 LED 480V 530 SAME AS TYPE F4 EXCEPT WITH DIFFERENT BEAM SEE F4 SEE F4 SEE F4 PHOENIX #HL
<br /> DISTRIBUTION, SEE LIGHT POLE SCHEDULE FOR HEAD (HIGHLAND SERIES)
<br /> 3 QUANTITIES PER POLE AND ARM LENGTHS. OR APPROVED
<br /> TYPE 5 DISTRIBUTION, NOMINAL 22,900 MAX CANDELA AT EQUAL
<br /> 270'H, 675V
<br /> 72,400 MINIMUM LUMINAIRE LUMENS
<br /> LOWERING -- -- -- TOP LATCHING EXTERNAL DRIVE, 2 LIGHTING CIRCUITS, WINCH -- FACTORY -- STRATUS PRODUCTS
<br /> DEVICE LOCATED INSIDE POLE, STAINLESS STEEL, SEE LIGHT POLE STANDARD #1060, OR
<br /> SCHEDULE FOR NUMBER OF CIRCUITS PER POLE GALVANIZE APPROVED EQUAL
<br /> A123
<br /> POLE -- -- -- 29'-6" ROUND TAPERED PRESTRESSED STEEL AND -- FACTORY -- NOV
<br /> SPUN-CAST CONCRETE POLE, 8-5/8" BASE DIA, 5-1/8" TOP STANDARD AMERON
<br /> DIA, 11" SQUARE BASEPLATE PRESTRESSED TO POLE, LOWER FINISH CENTRECON
<br /> INTERIOR 1'-0" AND LOWER EXTERIOR 0'-B' FINISH: #MBR OR
<br /> ELLIS PAINT COMPANY #690 VINYL WASH PRIMER, ENGARD APPROVED EQUAL
<br /> #463 COAL TAR EPDXY FINISH
<br /> POLE -- -- -- 47' FACETED TAPERED STEEL POLE, MINIMUM 17" BASE DIA, -- FACTORY -- STRUCTURAL AND {,
<br /> 10.42" TOP DIA, 16 SIDES, HOT-DIPPED GALVANIZED AFTER STANDARD STEEL PRODUCTS Lighting standards must comply with
<br /> INSIDE AND OUTSIDE, POLE TOP PROVISION: GALVANIZE INC
<br /> PLATE, SHAFT QTY: 1 EACH, DESIGN WIND: 90MPH, DESIGN A123 #Q-41924 SERIES
<br /> CRITERIA: AASHTO LTS-6 OR APPROVED the provision of meeting Dark Sky
<br /> EQUAL
<br /> POLE -- -- -- 71' FACETED TAPERED STEEL POLE, MINIMUM 17" BASE DIA, -- FACTORY -- STRUCTURAL AND Standards and shall be demonstrated
<br /> 7.435" TOP DIA, 16 SIDES, HOT-DIPPED GALVANIZED AFTER STANDARD STEEL PRODUCTS
<br /> FABRICATION INSIDE AND OUTSIDE, POLE TOP PROVISION: GALVANIZE INC on the plans showing lighting ranges
<br /> PLATE, SHAFT QTY: 2 EACH, DESIGN WIND: 9OMPH, DESIGN A123 #Q-41924 SERIES
<br /> CRITERIA: AASHTO LTS-6. OR APPROVED and lumens. In addition, a note shall
<br /> PROVIDE HANDHOLE COMPATIBLE WITH LOWERING DEVICE EQUAL
<br /> SYSTEM. be placed upon the plans certifying
<br /> compliance with dark sky standards.
<br /> E
<br /> o
<br /> N
<br /> � , e
<br /> N W
<br /> Know what'sbelOW. IF SHEET IS LESS THAN 22x34
<br /> call before you dig. REDUCE SCALE ACCORDINGLY
<br /> PROJECT ENGINEER: SCALE,
<br /> ELcO N SIATERLIS NONE
<br /> PORT OF EVERETT °W E7.1
<br /> t d DESESIGNm BY: DATE:
<br /> DATE.-
<br /> Port o 1q:y f ASSOCIATES,INC. e `'� D. SIATERLIS 05/07/2021 N O RT O N TERMINAL DEVELOPMENT CIP NO.1-$-9o°-os O
<br /> DRAWN IY: CHECKED�: & M T CA 3 R D INTERIM ACTION LL
<br /> a' nso=sa.n��awrm vw ENGINEERS—CONSULTANTS
<br /> aw. ��se=a= C. SMITH S. BARTKOSKE PROJECT
<br /> EVDMTof P.O. BOX 538 v��1 v..c=�I �00 (206)2435022 WWW.elcon.com , ,p1,202 DKS �m FOR aD g,, _� LUMINAIRE SCHEDULE Z
<br /> No. MT-NT-2021-02.2
<br /> n Evno.=swssa 16300 CHRISTENSEN ROAD,STE 330 /07/202 DKS FOR CRY RENEW S�ONAL MPROVET7 DY. O
<br /> EVERETT, WA 98206 SEATTLE,WA 98188 V
<br /> / 425 259-3164 SHEET NO. 133 OF 150
<br /> N0. DATE BY RENSION N0. DATE BY RENSION 6/b/21
<br />
|