|
CONCRETE FOUNDATIONS AND REINFORCING AEI 16. ELECTRICAL METALLIC TUBING (EMT) OR METAL-CLAD CABLE (MC) SHALL BE USED FOR CONCEALED INDOOR LOCATIONS.
<br /> 1. ALL CONCRETE WORK SHALL BE IN ACCORDANCE WITH THE ACI 301, ACI 318, ACI 336, ASTM A184, ASTM A185 AND THE DESIGN 17. SCHEDULE 40 PVC UNDERGROUND ON STRAIGHTS AND SCHEDULE 80 PVC FOR ALL ELBOWS 90s AND ALL APPROVED ABOVE
<br /> AND CONSTRUCTION SPECIFICATION FOR CAST-IN-PLACE CONCRETE. GRADE PVC CONDUIT. / v
<br /> 2. UNLESS NOTED OTHERWISE SOIL BEARING PRESSURE USED FOR DESIGN OF SLABS AND FOUNDATIONS IS ASSUMED TO BE 1000 psf. 18. LIQUID-TIGHT FLEXIBLE METALLIC CONDUIT (LIQUID-TTTE FLEX) SHALL BE USED INDOORS AND OUTDOORS, WHERE VIBRATION
<br /> OCCURS OR FLEXIBILITY IS NEEDED. dwsh
<br /> 3. ALL CONCRETE SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH (f'c) OF 3000 psi AT 28 DAYS (THE CONCRETE HAS BEEN 19. CONDUIT AND TUBING FITTINGS SHALL BE THREADED OR COMPRESSION-TYPE AND APPROVED FOR THE LOCATION USED. SET
<br /> DESIGNED BASED ON 25W PSI), UNLESS NOTED OTHERWISE. NO MORE THAN 90 MINUTES SHALL ELAPSE FROM BATCH TIME TO TIME OF SCREW FITTINGS ARE NOT ACCEPTABLE.
<br /> PLACEMENT UNLESS APPROVED BY THE ENGINEER OF RECORD, TEMPERATURE OF CONCRETE SHALL NOT EXCEED 90'f AT TIME OF
<br /> PLACEMENT. 20. CABINETS, BOXES AND WIRE WAYS SHALL BE LABELED FOR ELECTRICAL USE IN ACCORDANCE WITH NEMA, UL, ANSI/IEEE AND THE 5701 SOUTH SANTA FE DRIVE
<br /> 4. CONCRETE EXPOSED TO FREEZE-THAW CYCLES SHALL CONTAIN AIR ENTRAINING ADMIXTURES. AMOUNT OF AIR ENTRAINMENT TO BE NEC. LITTLETON, CO 80120
<br /> BASED ON SIZE OF AGGREGATE AND F3 CLASS EXPOSURE (VERY SEVERE). CEMENT USED TO BE TYPE 11 PORTLAND CEMENT WITH A 21. WIREWAYS SHALL BE METAL WITH AN ENAMEL FINISH AND INCLUDE A HINGED COVER, DESIGNED TO SWING OPEN DOWNWARDS
<br /> MAXIMUM WATER-TO-CEMENT RATIO (W/C) OF 0.45. (WIREMOLD SPECMATE WIREWAY).
<br /> 5. ALL STEEL REINFORCING SHALL CONFORM TO ASTM A615. ALL WELDED WIRE FABRIC (WWF) SHALL CONFORM TO ASTM A185. ALL 22, SLOTTED WIRING DUCT SHALL BE PVC AND INCLUDE COVER (PANDUTT TYPE E OR EQUAL).
<br /> SPLICES SHALL BE CLASS 'B' TENSION SPLICES, UNLESS NOTED OTHERWISE. ALL HOOKS SHALL BE STANDARD 90 DEGREE HOOKS, 23. CONDUITS SHALL BE FASTENED SECURELY IN PLACE WITH APPROVED NON-PERFORATED STRAPS AND HANGERS. EXPLOSIVE
<br /> UNLESS NOTED OTHERWISE YIELD STRENGTH (Fy) OF STANDARD DEFORMED BARS ARE AS FOLLOWS: DEVICES (i.e. POWDER-ACTUATED) FOR ATTACHING HANGERS TO STRUCTURE WILL NOT BE PERMITTED. CLOSELY FOLLOW THE LINES OF 0
<br /> #4 BARS AND SMALLER 40 kbi THE STRUCTURE, MAINTAIN CLOSE PROXIMITY TO THE STRUCTURE AND KEEP CONDUITS IN TIGHT ENVELOPES. CHANGES IN DIRECTION TO O
<br /> ROUTE AROUND OBSTACLES SHALL BE MADE WITH CONDUIT OUTLET BODIES. CONDUIT SHALL BE INSTALLED IN A NEAT AND WORKMANLIKE
<br /> 15 BARS AND LARGER 60 ksi MANNER. PARALLEL AND PERPENDICULAR TO STRUCTURE WALL AND CEILING LINES. ALL CONDUIT SHALL BE FISHED TO CLEAR
<br /> OBSTRUCTIONS. ENDS OF CONDUITS SHALL BE TEMPORARILY CAPPED FLUSH TO FINISH GRADE TO PREVENT CONCRETE, PLASTER OR DIRT
<br /> 6. THE FOLLOWING MINIMUM CONCRETE COVER SHALL BE PROVIDED FOR REINFORCING STEEL UNLESS SHOWN OTHERWISE ON FROM ENTERING. CONDUITS SHALL BE RIGIDLY CLAMPED TO BOXES BY GALVANIZED MALLEABLE IRON BUSHING ON INSIDE AND GALVANIZED 1000 HOLCOMB WOODS PKWY,
<br /> DRAWINGS: MALLEABLE IRON LOCKNUT ON OUTSIDE AND INSIDE. SUITE 270
<br /> ROSWELL, GA 30076
<br /> • CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH 3' 24. EQUIPMENT CABINETS, TERMINAL BOXES, JUNCTION BOXES AND PULL BOXES SHALL BE GALVANIZED OR EPDXY-COATED SHEET 678-280-2325
<br /> • CONCRETE EXPOSED TO EARTH OR WEATHER: STEEL SHALL MEET OR EXCEED UL 50 AND BE RATED NEMA 1 (OR BETTER) FOR INTERIOR LOCATIONS AND NEMA 3 (OR BETTER) FOR
<br /> • #6 BARS AND LARGER 2• EXTERIOR LOCATIONS.
<br /> 25. METAL RECEPTACLE, SWITCH AND DEVICE BOXES SHALL BE GALVANIZED, EPDXY-COATED OR NON-CORRODING; SHALL MEET OR W0
<br /> • #5 BARS AND SMALLER 1-1/2• EXCEED UL 514A AND NEMA OS 1 AND BE RATED NEMA 1 (OR BETTER) FOR INTERIOR LOCATIONS AND WEATHER PROTECTED (WP OR
<br /> • CONCRETE NOT EXPOSED TO EARTH OR WEATHER: BETTER) FOR EXTERIOR LOCATIONS.
<br /> • SLAB AND WALLS 3/4" 26. NONMETALLIC RECEPTACLE, SWITCH AND DEVICE BOXES SHALL MEET OR EXCEED NEMA OS 2 (NEWEST REVISION) AND BE RATED
<br /> BEAMS AND COLUMNS 1-1/2• NEMA 1 (OR BETTER) FOR INTERIOR LOCATIONS AND WEATHER PROTECTED (WP OR BETTER) FOR EXTERIOR LOCATIONS.
<br /> •
<br /> 27. THE CONTRACTOR SHALL NOTIFY AND OBTAIN NECESSARY AUTHORIZATION FROM THE CARRIER AND/OR DISH Wireless L.L.C. AND
<br /> 7. A TOOLED EDGE OR A 3/4• CHAMFER SHALL BE PROVIDED AT ALL EXPOSED EDGES OF CONCRETE, UNLESS NOTED OTHERWISE, TOWER OWNER BEFORE COMMENCING WORK ON THE AC POWER DISTRIBUTION PANELS. M! „9
<br /> IN ACCORDANCE WITH AG 301 SECTION 4.2.4. 28. THE CONTRACTOR SHALL PROVIDE NECESSARY TAGGING ON THE BREAKERS, CABLES AND DISTRIBUTION PANELS IN ACCORDANCE �A��„
<br /> WITH THE APPLICABLE CODES AND STANDARDS TO SAFEGUARD LIFE AND PROPERTY. IpHAy�
<br /> ELECTRICAL INSTALLATION NOTES: 29. INSTALL LAMICOID LABEL ON THE METER CENTER TO SHOW 'DISH Wireless LLC.•.
<br /> 1. 07l1U2D22
<br /> ALL ELECTRICAL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS, NEC AND ALL APPLICABLE 30. ALL EMPTY/SPARE CONDUITS THAT ARE INSTALLED ARE TO HAVE A METERED MULE TAPE PULL CORD INSTALLED. BI NUMBER: 604-106-18
<br /> _ FEDERAL, STATE, AND LOCAL CODES/ORDINANCES.
<br /> 2. IT IS A VIOLATION OF LAW FOR ANY PERSON,
<br /> CONDUIT ROUTINGS ARE SCHEMATIC. CONTRACTOR SHALL INSTALL CONDUITS S0 THAT ACCESS TO EQUIPMENT IS NOT BLOCKED UNLESS THEY ARE ACTING UNDER THE DIRECTION
<br /> - AND TRIP HAZARDS ARE ELIMINATED. OF A LICENSED PROFESSIONAL ENGINEER,
<br /> TO ALTER THIS DOCUMENT.
<br /> 3. WIRING, RACEWAY AND SUPPORT METHODS AND MATERIALS SHALL COMPLY WITH THE REQUIREMENTS OF THE NEC.
<br /> DRAWN BY: CHECKED BY: PPROVED BY
<br /> 4. ALL CIRCUITS SHALL BE SEGREGATED AND MAINTAIN MINIMUM CABLE SEPARATION AS REQUIRED BY THE NEC.
<br /> 4.1. ALL EQUIPMENT SHALL BEAR THE UNDERWRITERS LABORATORIES LABEL OF
<br /> MSB MSB OF APPROVAL, AND SHALL CONFORM TO REQUIREMENT OF REDS REV /j: -_-
<br /> THE NATIONAL ELECTRICAL CODE
<br /> 4.2. ALL OVERCURRENT DEVICES SHALL HAVE AN INTERRUPTING CURRENT RATING THAT SHALL BE GREATER THAN THE SHORT CIRCUIT CONSTRUCTION
<br /> CURRENT TO WHICH THEY ARE SUBJECTED, 22,000 AIC MINIMUM. VERIFY AVAILABLE SHORT CIRCUIT CURRENT DOES NOT EXCEED THE
<br /> RATING OF ELECTRICAL EQUIPMENT IN ACCORDANCE WITH ARTICLE 110.24 NEC OR THE MOST CURRENT ADOPTED CODE PRE THE DOCUMENTS
<br /> GOVERNING JURISDICTION.
<br /> 5. EACH END OF EVERY POWER PHASE CONDUCTOR, GROUNDING CONDUCTOR, AND TELCO CONDUCTOR OR CABLE SHALL BE SUBMfTTALS
<br /> LABELED WITH COLOR-CODED INSULATION OR ELECTRICAL TAPE (3M BRAND, 1/2• PLASTIC ELECTRICAL TAPE WITH UV PROTECTION, OR REV DATE DESCRIPTION
<br /> EQUAL). THE IDENTIFICATION METHOD SHALL CONFORM WITH NEC AND OSHA A "/a MS=FM mover
<br /> 6. ALL ELECTRICAL COMPONENTS SHALL BE CLEARLY LABELED WITH LAMICOID TAGS SHOWING THEIR RATED VOLTAGE, PHASE
<br /> o m/1It= WM wR noN
<br /> CONFIGURATION, WIRE CONFIGURATION, POWER OR AMPACITY RATING AND BRANCH CIRCUIT ID NUMBERS (i.e. PANEL BOARD AND CIRCUIT
<br /> ID'S).
<br /> 7. PANEL BOARDS (ID NUMBERS) SHALL BE CLEARLY LABELED WITH PLASTIC LABELS.
<br /> 8. TIE WRAPS ARE NOT ALLOWED.
<br /> 9. ALL POWER AND EQUIPMENT GROUND WIRING IN TUBING OR CONDUIT SHALL BE SINGLE COPPER CONDUCTOR (#14 OR LARGER) A&E PROJECT NUMBER
<br /> WITH TYPE THHW, THWN, THWN-2, XHHW, XHHW-2, THW, THW-2, RHW, OR RHW-2 INSULATION UNLESS OTHERWISE SPECIFIED. 22CCD05N-0041
<br /> 10. SUPPLEMENTAL EQUIPMENT GROUND WIRING LOCATED INDOORS SHALL BE SINGLE COPPER CONDUCTOR (#6 OR LARGER) WITH DISH Wireless L.L.C.
<br /> TYPE THHW, THWN, THWN-2, XHHW, XHHW-2, THW, THW-2, RHW, OR RHW-2 INSULATION UNLESS OTHERWISE SPECIFIED.
<br /> PROJECT INFORMATION
<br /> 11. POWER AND CONTROL WIRING IN FLEXIBLE CORD SHALL BE MULTI-CONDUCTOR, TYPE SOOW CORD (#14 OR LARGER) UNLESS SESEA00219B
<br /> OTHERWISE SPECIFIED. 9910 EVERGREEN WAY
<br /> 12. POWER AND CONTROL WIRING FOR USE IN CABLE TRAY SHALL BE MULTI-CONDUCTOR, TYPE TC CABLE (#14 OR LARGER), WITH
<br /> EVERETT, WA 98204
<br /> TYPE THHW, THWN, THWN-2, XHHW, XHHW-2, THW, THW-2, RHW, OR RHW-2 INSULATION UNLESS OTHERWISE SPECIFIED.
<br /> 13. ALL POWER AND GROUNDING CONNECTIONS SHALL BE CRIMP-STYLE, COMPRESSION WIRE LUGS AND WIRE NUTS B SHEET TITLEY THOMAS AND GENERAL NOTES
<br /> BETTS (OR EQUAL). LUGS AND WIRE NUTS SHALL BE RATED FOR OPERATION NOT LESS THAN 75' C (90' C IF AVAILABLE).
<br /> 14. RACEWAY AND CABLE TRAY SHALL BE LISTED OR LABELED FOR 0.ECTRK:AL USE IN ACCORDANCE WITH NEMA, UL, ANSI/IEEE AND
<br /> NEC.
<br /> SHEET NUMBER
<br /> 15. ELECTRICAL METALLIC TUBING (EMT), INTERMEDIATE METAL CONDUIT (!MC), OR RIGID METAL CONDUIT (RMC) SHALL BE USED FOR GN-4
<br /> EXPOSED INDOOR LOCATIONS.
<br />
|