INITIATING WIRING RECORD DRAWINGS
<br /> AS-BUILT/RECORD DRAWING REQUIREMENTS: Conve rg j nt
<br /> SIGNATURE LOOP WIRING LIMITATIONS: Z
<br /> THE FOLLOWING INFORMATION SHOULD BE RECORDED ON A SEPARATE SET OF O
<br /> SIGNATURE DUAL DRIVER CONTROLLER MODULES SUPPORTS UP TO 250 DRAWINGS FOR EACH PROJECT:
<br /> INTELLIGENT SIGNATURE DETECTORS AND 250 INTELLIGENT SIGNATURE W 450 Shattuck Avenue South,Renton,Washington 98057
<br /> MODULES 1. ANY CHANGES IN THE LOCATION OF ANY ASSOCIATED FIRE ALARM OR o Phone:425-272-2250 Fax:425-251-0949
<br /> WIRE LENGTH LIMITATIONS: INTERFACE EQUIPMENT.CONTROL PANELS,ANNUNCIATORS,DETECTORS, w
<br /> CONTROL RELAYS,INPUT AND OUTPUT MODULES,TERMINAL CABINETS, zYO ¢ w
<br /> NON-TWISTED,NON-SHIELDED WIRE ETC. F w p This dowmentand the inro�mation/aepiaions conrainea/shown
<br /> 16AWG-20pf/FT&4.02 OHMS/1000 FEET 2. ANY CHANGES TO CIRCUIT WIRING.THIS INCLUDES DELETION OR W o O is Me exclusive property of Convergint Technologies LLC and shall
<br /> 18AWG-20pfIFT 8 6.38 DHMS/1000 FEET ADDITIONAL WIRING RUNS.ANY RE-ROUTING OF CIRCUIT WIRING.ANY SEQUENCE O F OPERATIONS �i w m w ~ be hantllea as proprietary antl wnftlential information aria must be
<br /> DETECTORS ONLY 1
<br /> 6AWG-125 DETECTORS-9,275' ADDITIONS OR DELETIONS TO THE NUMBER,LOCATION,AND ORDER OF ¢ o Yo o O m w w —ned upon request.This document pnnot be rep.duc.d by any
<br /> MODULES ONLY 16AWG-125 MODULES DEVICE WIRING ON A CIRCUIT. z 0 < w mO ¢ w m ns without the wdnen eutnorizelion of convergent Technologies LLC.
<br /> DETECTORS AND MODULES 16AWG-125 OF EACH-3,608' 3. ADDRESSES AND/OR LABELS FOR ALL ADDRESSABLE DEVICES. ¢ 2 _ G
<br /> DETECTORS ONLY 16AWG
<br /> -125 DETECTORS-5,839' 4. CANDELA SETTINGS OF ALL VISUAL NOTIFICATION DEVICES. F
<br /> MODULES ONLY 18AWG-125 MODULES-4,986' 5. WATTAGE TAP SETTINGS OF ALL SPEAKER NOTIFICATION DEVICES. p O
<br /> DETECTORS AND MODULES 18AWG-125 OF EACH-2,271'
<br /> ANY CHANGES SHALL BE DISCUSSED WITH CONVERGINT PROJECT MANAGER Z
<br /> TWISTED PAIR.NON-SHIELDED WIRE TO ENSURE SYSTEM AND CODE PARAMETERS ARE MET.CONVERGINT SHALL a
<br /> i6AWG-36pf/FT&4.02 OHMS/1000 FEET NOT BE HELD ACCOUNTABLE FOR CHANGES MADE WITHOUT APPROVAL.
<br /> 18AWG-25pf/FT&6.38 OHMS/1000 FEET
<br /> DETECTORS ONLY 16AWG-125 DETECTORS-9,275' THIS INFORMATION SHALL BE NEAT AND LEGIBLE WHEN PRESENTED TO THE
<br /> MODULES ONLY 16AWG-125 MODULES-7,921' TECHNICIAN AT THE CONCLUSION OF THE PROJECT.PLEASE NOTE CONTACT
<br /> DETECTORS AND MODULES 16AWG-1250F EACH-3,608' INFORMATION ON DRAWINGS FOR INDIVIDUALS WITH FAMILIARITY OF
<br /> DETECTORS ONLY i8AWG-125 DETECTORS-5,839' INSTALLATION IN THE EVENT QUESTIONS ARISE DURING THE CLOSEOUT
<br /> MODULES ONLY 1BAWG-125 MODULES-4,986' PROCESS. ACTIVATION OF LOCALALARM AT LIT&2120 HEADEND(LED DISP,ZON F LED&AUDIBLE IND.) X X X X X X X
<br /> DETECTORS AND MODULES 18AWG-125 OF EACH-2,271'
<br /> TWISTED PAIR,SHIELDED WIRE ACTIVATE ALL AUDIBLE&VISIBLE ALARMS x x x x x x
<br /> 1
<br /> 6AWG-82pf/FT&4.02 OHMS/1000 FEET
<br /> 18AWG-58pf/FT&6.38 OHMS/1000 FEET
<br /> DETECTORS ONLY i6AWG-125 DETECTORS-6,098' INDICATION OF ALARM ON ANNUNCIATOR
<br /> MODULES ONLY 16AWG-125 MODULES-6,098'
<br /> DETECTORS AND MODULES 16AWG-125 OF EACH-3,608' INITIATE PRIMARY ELEV.RECALL SEQUENCE TO MAIN FLOOR(IF APPLICABLE) x
<br /> DETECTORS ONLY i8AWG-125 DETECTORS-5,839'
<br /> MODULES ONLY 18AWG-125 MODULES-4,986'
<br /> DETECTORS AND MODULES 18AWG-125 OF EACH-2,271' INITIATE ALTERNATE FLEV.RECALLSEQUENCE TO FIRST FLOOR(IF APPLICABLE) x
<br /> SIG—RE—LOQP WRING,CLASS B ONLY RELEASE ALL DOOR HOLDERS&CLOSURES ON FLOOR IN ALARM(OR GEN.ALARM) x x x x x x
<br /> TRAMSMIT TROUBLES,SUPERVISORY X X X X X X
<br /> s 00 s 00 TRANSMITALARM SIGNALTO CENTRALSTATION MONITOR x X X X x x
<br /> SHUTDOWN RESPECTIVE HVAC FAN x
<br /> TROUBLE INDICATION ON FACP&ANNUNCIATOR x x
<br /> TRANSMITTROUBLE SIGNAL TO CENTRAL STATION MONITOR X X
<br /> 0
<br /> STAR-TAPPING.UNACCEPTABLE
<br /> NOTIFICATION WIRING
<br /> SPEAKER CIRCUIT WIRING LIMITATIONS:
<br /> WIRE LENGTH LIMITATIONS:
<br /> THE MAXIMUM ALLOWABLE WIRE LENGTH IS THE FARTHEST DISTANCE THAT A
<br /> SPEAKER CIRCUIT CAN EXTEND FROM THE AMPLIFIER TO THE LAST SPEAKER
<br /> WITHOUT LOSING 0.5 dB OF SIGNAL.THE FOLLOWING ARE MAXIMUM DISTANCE
<br /> BASED ON APPROXIMATE WATTAGE OF THE SPEAKER CIRCUIT.CIRCUIT LENGTHS
<br /> ARE FURTHER BASED ON ORIGINATION OF A CIRCUIT FROM EITHER THE
<br /> AMPLIFIER OR FROM THE CC1 MODULE.
<br /> ALLOWABLE LENGTH AT 25 V-S,WITH 0.5 dB LOSS
<br /> 16AWG-20 WATTS-231'
<br /> 16AWG-30 WATTS-154'
<br /> 16AWG-40 WATTS_1 16,
<br /> ALLOWABLE LENGTH AT 70 V-S,WITH 0.5 dB LOSS
<br /> 16AWG-20 WATTS-1815'
<br /> 16AWG-30 WATTS-1210'
<br /> 16AWG-40 WATTS-907'
<br /> NAC CIRCUIT(HORN,STROBE)WIRING LIMITATIONS:
<br /> FOR 24VDC SYSTEMS,MINIMUM DEVICE OPERATING VOLTAGE IS 16VDC.
<br /> VOLTAGE DROP CALCULATIONS ARE BASED ON 16VDC AND POWER SUPPLY
<br /> DE-RATED AND ON DEPLETED BATTERY BACKUP PER THE PRESCRIBED PERIOD
<br /> OF STANDBY AND ALARM RING TIME.THE VOLTAGE DROP WILL LIMIT THE
<br /> CIRCUITS CAPACITY IN ALMOST ALL CASES AND CURRENT CANNOT BE USED AS
<br /> THE ONLY CIRCUIT WIRING LIMITATION.ALTERATIONS TO CIRCUIT LENGTH
<br /> FROM THOSE CALCULATED MAY CAUSE CIRCUITS TO BE OUT OF THE
<br /> TOLERANCES GRANTED BY THE FIRE ALARM CODE.CHANGES TO DEVICE
<br /> LOCATION OR CIRCUIT LENGTH SHALL BE COMMUNICATED TO THE CONVERGINT
<br /> TEAM.
<br /> NAC CIRCUIT WIRING AND ROUTING MUST NOT EXCEED WHAT IS SHOWN ON THE
<br /> DESIGN DRAWINGS AND CALCULATIONS.A VOLTAGE DROP TEST IS PART OF
<br /> MOST FIRE FINALS AND IS REQUIRED BY NFPA.A FAILED FIRE FINAL MAY
<br /> REQUIRE REWIRING OF THE FAILED CIRCUITS.
<br /> WIRE RESISTANCE RATINGS USED FOR CALCULATIONS:
<br /> 18AWG-13 OHMS PER 1000'
<br /> 16AWG-8 OHMS PER 1000'
<br /> 14AWG-5.2 OHMS PER 1000'
<br /> EXAMPLE: 1.0 AMP CIRCUIT LOAD USING#14 WIRE=409 FEET MAXIMUM.
<br /> CLASS A OR B NOTIFICATION WIRING
<br /> EOL
<br /> FACP
<br /> OR EOL RESISTOR ON
<br /> NAG NON ADDRESSABLE
<br /> CIRCUITS
<br /> DEVICE DEVICE
<br /> CLASS B,STYLE 4 WIRING
<br /> iosx-DescalPnox DATE
<br /> FACP
<br /> OR
<br /> NAC
<br /> DEVICE DEVICE
<br /> }
<br /> a
<br /> 0MIAH R.
<br /> Q PROJECT DESIGNER: xGBExTR
<br /> QW CLASS A POWER REQUIREMENTS
<br /> ,STYLE 6 WIRING
<br /> U
<br /> 1n EACH MAIN FIRE ALARM PANEL REQUIRES(1)120VAC,20AMP DEDICATED
<br /> Q SEPARATION OF CLASSACIRCUITS-INSTALLATIONEXCEPTION& CIRCUIT. PROVIDENCE PACIFIC CAMPUS
<br /> F CLASS AOUTGOING AND RETURN CONDUCTORS,EXITING AND RETURNING EACH NAC BOOSTER PANEL REQUIRES(1)120VAC,15AMP DEDICATED CIRCUIT. ELEVATOR T.I.
<br /> TO THE CONTROL PANEL,ARE TO BE ROUTED SEPARATELY.THE MINIMUM 916 PACIFIC AVE
<br /> v RECOMMENDED SEPARATION IS 1 FT.VERTICALLYAND 4 FT. IN BUILDINGS EMPLOYING EMERGENCY STANDBY POWER SYSTEMS,THE FIRE EVERETT,WA,98201
<br /> x HORIZONTALLY.THE FOLLOWING EXCEPTIONS STILL DO NOT ELIMINATE ALARM SHALL BE SUPPLIED WITH EMERGENCY POWER.THIS IS REQUIRED IN
<br /> THE 2ND PAIR OF WIRES.THEY ALLOW YOU TO USE A SINGLE RACEWAY HIGH-RISE AND SMOKE CONTROL APPLICATIONS.ALL OTHER APPLICATIONS
<br /> M AND ELIMINATE THE SEPARATION FOR THESE CONDITIONS. ARE SUBJECT TO LOCAL BUILDING AND ELECTRICAL CODES.
<br /> z 1. WHEN MAXIMUM CABLE,ENCLOSURE,OR RACEWAY IS LESS THAN 10 WHERE THE FIRE ALARM SYSTEM IS CONNECTED TO EMERGENCY NOTES
<br /> FEET.NO LIMIT TO NUMBER OF DEVICES. POWER,THE FIRE ALARM SYSTEM MONITORS THE GENERATOR FOR
<br /> 1n 2. UNLIMITED CONDUIT OR RACEWAY DROP TO AN INDIVIDUAL DEVICE. RUNNING,FUEL LOW AND TROUBLE STATES.
<br /> 0 3. UNLIMITED CONDUIT OR RACEWAY DROP TOA ROOM NOT FIRE ALARM SYSTEM
<br /> Z EXCEEDING 1000 SO,FT.NO LIMIT TO THE NUMBER OF DEVICES. FOR ADDITIONAL DETAILS,REFER TO NFPA 72,CHAPTER 10.
<br /> Q wgNc.
<br /> o FA-0-2
<br /> LL
<br />
|