i Permit Inspections <br /> V E R E T T City of Everett <br /> WASHINGTON <br /> 10/31/2017 10/31/2017 ElecRoughln STEVE BANKS Corr Reqd <br /> Notes: <br /> Suite 101 not ready,Suite 205 GFCI protect all receptacles within 6'of sinks or undergrounds.Have spece evaluated for classifications for fumes,gases, <br /> etc.Provide load calculation for sub panel.Space 203&204 not ready <br /> Space 201&202 no change from previous inspection. <br /> Exit and pathway lighting has to be on the same circuit as the area that they serve. <br /> 11/16/2017 11/16/2017 ELEC FINAL STEVE BANKS CORRECTION <br /> REQUIRED <br /> Notes: <br /> OK new show window,receptacles and circuits and GFCI receptacles to counter and reach in freezers. <br /> Cap wires and install box cover above door. <br /> Snax unit. <br /> No other inspection areas ready at this time. <br /> I <br /> Printed:Tuesday,05 August,2025 2 of 2 rk <br /> SUPERION <br />