<br /> Everett Fire Dept Permit FA2310-021
<br /> .Notes: A a w m
<br /> i(NFPA 72) I Site Address: 2701 Wetmore Ave W
<br /> EVERETT Applicant: Home Run Electric LLC s yWl 0)
<br /> -See Attached Fire Alarm System r I Application Date: 10/26/2023 Lim"y H N 3
<br /> Acceptance Test Checklist. Description: Fire Alarm System N Q o
<br /> m�
<br /> •24 hour Battery Test-At the time of the I = W LCinspection/test provide proof verifying that the Review Status: 1st Review by City&Peer Reviewers Review Date: 11/02/2023 <I—
<br /> panel has been operating on secondary power I c o
<br /> (battery)for 24 hours.No other problems a H m
<br /> shall be indicated on the panel. I 0 ro F
<br /> IL701 W T M 0 R E N r
<br /> 'I Ev E i Y Q
<br /> I-Record of Completion-For all new EVERETT
<br /> systems,a Record of Completion is required Everett Fire Dept.Permit Review o 0 0 to be entered into The Compliance Engine I Status:Approved 0 Z„
<br /> poor to permit final. Reviewed By:BPearson N a a
<br /> F I R E ALARM SYSTEM I�(wwW'.thecomplianceengine. 11/02/2 3 39 54
<br /> —__________— P______J PM INSTALLING CONTRACTOR:
<br /> PROJECT INFORMATION DEVICE LEGEND II t
<br /> SYMBOL MANUFACTURER PARTNO DESCRIPTION OTY I
<br /> O SILENT KNIGHT SK-520B FIRE ALARM CONTROL PANEL,CONVENTIONAL,10-30 ZONE 1 �O I yl E,`U N
<br /> NAME: 2701 WETMORE "s - ""' E L E C T R I C
<br /> ADDRESS: 2701 WETMORE NAc SILENT KNIGHT 5496 54966A INTELLIGENT REMOTE POWER SUPPLY 1 _.,nev ="""�® zn3s4a�AwwL3�..00a vu seou
<br /> EVERETT,WA 98201 °^^• .„. r(4zq sar-aryl J II—) s
<br /> ❑
<br /> /,i RONvryY,w�nneNCN°bsom F SILENT KNIGHT SK-PULLSA ADDRESSABLE MANUAL PULL STATION,SINGLE-ACTION 1
<br /> SCOPE OF WORK JB GENERIC GENERIC WIREPATH JBOX 01 HARDWARE,JUNCTION BOX 3 - :.,°,Q ^ � , - 21118 66 TH AVE- W
<br /> LYone:(425)489-0791
<br /> NNWOOD,WA 98036
<br /> RECONFIGURING EXISTING SK-5808 ADRESSABLE FIRE ALARM CONTROL PANEL INTO NEW 0 SILENT KNIGHT SK-MONITOR-2 ADDRESSABLE DUAL MONITOR MODULE 6 �� —� „ —0- 2x® �. Ph
<br /> D g § Fax: (425)489-7996
<br /> RESIDENTIAL OCCUPANCIES AND REVISED BUILDING CONFIGURATION. h
<br /> Q SILENT KNIGHT SK-RELAY ADDRESSABLE RELAY MODULE 3 sew°e.«vQ m�a�� eel ouo9
<br /> IM SILENT KNIGHT SK-ISO FAULT ISOLATOR MODULE 4 pnIX& „•,.ma etl •• \,u.,.aaaaO"
<br /> FIRE ALARM CONTRACTOR �F] SYSTEM SENSOR HW-LF SOUNDER,LOW FREQUENCY,WALL,WHITE 78 mn".w A°c"-0©oPotl"°M use=maeErsv ee Q�Po
<br /> 0
<br /> NAME: HOME RUN ELECTRIC ® SILENT KNIGHT SK-PHOTO ADDRESSABLE PHOTOELECTRIC SMOKE DETECTOR 24 q °" "°'9
<br /> ADDRESS: 21118 66TH AVE W
<br /> LYNNWOOD,WA 98038 ® SILENT KNIGHT 3K-PHOTO-T ADDRESSABLE PHOTOELECTRIC 3MOKEIHEATDETECTOR 7 � ���"_�- �,',�® °°°"`"' _ l
<br /> PHONE: (425)489-7996 SYSTEM SENSOR P2RK 2-WIRE HORN STROBE,STANDARD CD,OUTDOOR 7 ,
<br /> FAX (125)489-7996 �P .-• ° 0
<br /> SYSTEM SENSOR P21RL 2-WIRE,HORN STROBE,RED 1 S
<br /> APPLICABLE CODES AND STANDARDS SYSTEM SENSOR P2WL 2-WIRE,HORN STROBE,WHITE 28 fi a r C
<br /> NFPA 72 NATIONAL FIRE ALARM CODE 2019 EDITION SYSTEM SENSOR PC2WL 2-WIRE,HORN STROBE,WHITE 1
<br /> INTERNATIONAL BUILDING CODE 2015 EDITION C
<br /> INTERNATIONAL FIRE CODE 2015 EDITION SYSTEM SENSOR SWL STROBE,WHITE B
<br /> NFPA 70 NATIONAL ELECTRICAL CODE 2020 EDITION a V
<br /> CABLE AND WIRE LEGEND
<br /> LABEL LINETYPE AWG RESISTANCE DESCRIPTION N
<br /> CIRCUIT LABELING LEGEND A 16 7.77 2 COND.SOLID COPPER FPLR
<br /> DEVICE IDENTIFIER
<br /> B ---------------- 14 3.07 2 COND.SOLID COPPER FPLR ANALOG UNSHIELDED VICINITY MAP
<br /> SLC1• m
<br /> SLC=SIGNALING LINE CIRCUIT C ----------------------- 18 6.7000 4COND.SOLID COPPER FPLR ANALOG UNSHIELDED
<br /> NAC=NOTIFICATION APPLIANCE CIRCUIT
<br /> CIRCUIT IDENTIFIER ADRIAN M.STEIK
<br /> it Engir f Tu w.Levrl4
<br /> NICET[ehirulien lAmbw:0937(16
<br /> NuxFoeixiy SigmNre �lw=r�3'U
<br /> ABBREVIATIONS
<br /> INPUTS
<br /> A AMPERE J-BOX JUNCTION BOX GENERAL SYSTEM OPERATION
<br /> AFF ABOVE FINISHED FLOOR kV KILOVOLT I^L
<br /> AHU AIR HANDLING UNIT WA KILOVOLTAMPERE ACTIVATION OF ANY SMOKE DETECTOR,HEAT DETECTOR OR MANUAL PULL STATION SHALL: v�
<br /> Uj
<br /> AL ALUMINIUM kW KILOWATT - VISUALLY INDICATE THE APPROPRIATE ZONE ON THE FACP: O SHEET INDEX
<br /> AMP AMPERE kWh KILOWATT HOUR -- WHAT TYPE OF DEVICE WAS ACTIVATED.
<br /> AWG AMERICAN WIRE GAUGE MFR MANUFACTURER -- FROM WHICH AREATHEALARM WASGENERATED. U K W
<br /> BLDG BUILDING MECH MECHANICAL - ACTUATEEXTERIORSTROBE. J O W
<br /> C CONDUIT MIN MINIMUM - TRANSMIT THE APPROPRIATE ZONE ALARM SIGNAL TO THE APPROVED CENTRAL m m U SHEET NO. SHEET DESCRIPTION O 0
<br /> CB CIRCUIT BREAKER (A) NEW STATION FOR COMMUNICATION TO THE FIRE DEPARTMENT. z0 } =O = o y w A/
<br /> CCTV CLOSED CIRCUIT TELEVISION NAC NOTIFICATION APPLIANCE CIRCUIT F w w .�U. Y FAD. TITLE SHEET L Al
<br /> CKT CIRCUIT NEC NATIONAL ELECTRIC CODE THESYSTEMSHALLBEELECTRICALLYSUPERVISEDSOTHATTHEOCCURRENCEOFA z ¢ c = 3 N w N W
<br /> CLG CEILING NEUT NEUTRAL SINGLE OPEN,OR GROUND FAULT ON ANY FIELD WIRING,OR FAILURE OF PRIMARY POWER O2 > > Q U 0
<br /> r m oq = t ^ m p FA1.1 LEVEL 1 FLOOR PLAN-FIRE ALARM SYSTEM
<br /> CO CONDUIT ONLY NFPA NATIONAL FIRE PROTECTION ASSOCIATION SUPPLY,WILL CAUSE A VISUAL'TROUBLE'AT THE FACP B REMOTE ANNUNCIATOR AND Q 4 w U 3 } m
<br /> COMM COMMUNICATION NC NORMALLY CLOSED 'TROUBLE"SIGNAL SHALL BE TRANSMITTED TO THE APPROVED CENTRAL STATION FOR > ¢ LL 3 z w m O f
<br /> z FA1.2 LEVEL 2 FLOOR PLAN-FIRE ALARM SYSTEM
<br /> CU COPPER NIC NOT IN CONTRACT APPROPRIATE ACTION. 6 0 w l7 2� w f O v,
<br /> DCV DOUBLE CHECK VALVE NO NUMBER;NORMALLY OPEN Q F 3 U, O
<br /> CIA DIAMETER NTS NOT TO SCALE a a g 0 J w FA1.3 LEVEL 3 FLOOR PLAN-FIRE ALARM SYSTEM
<br /> Dlsc DISCONNECT oD OVERHEAD DOOR;OVERALL DIAMETER G a N N -- _- 2 ¢ w j z FA2.1 RISER DIAGRAM-FIRE ALARM SYSTEM
<br /> ON DOWN PV POST INDICATOR VALVE w = ¢ ] w a > O = /
<br /> DO DOOR OPERATOR PINE PANEL Lri
<br /> o a ¢ w w O u-
<br /> (E) ¢ FA2.2 BATTERY AND CIRCUIT CALCULATIONS-FIRE ALARM SYSTEM
<br /> EA EXISTING PVC POLYVINYL CHLORIDE(PLASTIC) w ¢ < < < z U 3 X x IL. w f
<br /> EA EACH PWR POWER 0 = ¢ Q ¢ = z z z H C7
<br /> EF EXHAUST FAN QN QUANTITY O z w Ce w O w z ¢�¢
<br /> ELEC ELECTRIC READ REQUIRED u, 2 LL z W C07 O � vai mw iz CD w 1
<br /> ELEV ELEVATOR RH RANGE HOOD L
<br /> EMT ELECTRICAL METALLIC TUBING RMC RIGID METALLIC CONDUIT ACTUATE ALARM SIGNAL AT FACP 0 0 9 0 00 0 0 0 0 9 0 0 GENERAL NOTES L III
<br /> EOL END OF LINE RESISTOR SF SUPPLY FAN;SQUARE FEET ACTUATE ALARM SIGNAL AT ANNUNCIATOR 0 0 0 0 0 0 0 0 I— W
<br /> EOLR END OF LINE RESISTOR SLC SIGNALING LINE CIRCUIT
<br /> EXIST EXISTING SPEC SPECIFICATION TRANSMIT ALARM SIGNAL TO CENTRAL STATION
<br /> F FIXED ST SHUNT TRIP LU
<br /> FA FIRE ALARM STD STANDARD ACTIVATE ALL BUILDING NOTIFICATION APPLIANCES
<br /> FAA FIRE ALARM ANNUNCIATOR TEL TELEPHONE ACTUATE SUPERVISORY SIGNAL AT FACP • ALL FIRE ALARM SYSTEM WORK COMPLETED UNDER THE SCOPE OF THIS FIRE ALARM PLAN REVIEW SHALL BE FIELD
<br /> FACP FIRE ALARM CONTROL PANEL TELCOTELEPHONE COMPANY VERIFIED BY FIRE INSPECTION PERSONNEL AND THE FIRE CODE OFFICIAL.
<br /> FAPS FIRE ALARM POWER SUPPLY TEMP TEMPORARY TRANSMIT SUPERVISORY SIGNAL TO CENTRAL STATION
<br /> • VISIBLE NOTIFICATION APPLIANCES SHALL REMAIN ACTIVE(FLASHING)WHEN THE AUTOMATIC AND MANUAL FIRE ALARM O `
<br /> LU
<br /> FARA FIRE ALARM REMOTE ANNUNCIATOR TS TAMPER SWITCH ACTUATE TROUBLE SIGNAL AT FACP
<br /> FBO FURNISHED BY OTHERS TYP TYPICAL a SYSTEM ISSILENCED.
<br /> FDC FIRE DEPARTMENT CONNECTION UGND UNDERGROUND TRANSMIT TROUBLE SIGNAL TO CENTRAL STATION • • • • FIRE ALARM SYSTEM SHALL TRANSMIT TROUBLE,SUPERVISORY AND FIRE SIGNALS DIRECTLY TO THE COMMUNICATIONS
<br /> FEC FIRE EXTINGUISHER CABINET ILL UNDERWRITERS 0 ELEVATOR CONTROL: CENTER REMOTE SUPERVISING STATION
<br /> FH FIRE HYDRANT UON UNLESS
<br /> STATION.
<br /> OTHERWISE NOTED (y
<br /> FPL FIRE POWER LIMITED V VOLT PRIMARY ELEVATOR RECALL MOUNT PULL STATIONS AT 42 AT ACTIVATOR WITHIN 5 OF LATCH SIDE OF EXIT DOORS
<br /> J
<br /> FPLR FIRE POWER LIMITED RISER VA VOLT AMPERE ELEVATOR CONTROL: • MOUNT AUDIO VISUAL DEVICES AT 80"ABOVE FLOOR LEVEL
<br /> FP LP FIRE POWER LIMITED PLENUM VAC VOLTAGE,ALTERNATING CURRENT I—
<br /> • A DEDICATED 120VAC,20A BRANCH CIRCUIT BREAKER SHALL BE PROVIDED,MARKED IN RED,LOCK-ON PROVISION AND w
<br /> FS WATER FLOW SWITCH VDC VOLTAGE,DIRECT CURRENT ALTERNATE ELEVATOR RECALL w
<br /> FSD FIRE/SMOKE DAMPER VR VANDAL RESISTANT IDENTIFIED AS"FIRE ALARM CIRCUIT CONTROL".THE LOCATION OF THE CIRCUIT BREAKER WILL BE PERMANENTLY N
<br /> G GROUND W WATT ELEVATOR CONTROL: IDENTIFIED AT THE FIRE ALARM CONTROL UNIT.
<br /> GEC GROUNDING ELECTRODE CONDUCTOR W/ WITH FIRE HAT
<br /> GEN GENERATOR W/O WITHOUT DRAWN BY RMV
<br /> HT HEATTRACE WP WEATHERPROOF
<br /> IDC INITIATING DEVICE CIRCUIT Z IMPEDANCE SEQUENCE OF OPERATIONS MATRIX CHECKED BY: Adrian M.Steik
<br /> PLOTOATE: 10/4/22
<br /> PROJECT NUMBER: 2 2-012
<br /> FAO , 1
<br /> DRAWING ONLY TO SCALE IF PLOTTED AT 24"X 36" SHEET N..BEa: