Laserfiche WebLink
TOLBraceTM Seismic Calculation <br /> CC Learning Resource Center Job# EW <br /> t <br /> 1001 N Broadway ate <br /> F§> ,:o�$ustess iR'arirdwxde <br /> Brace Identification 2'/z" Longitudinal Brace <br /> Brace Type (Per NFPA#13) NFPA Type B <br /> Braced Pipe(ft) 2.5" Sch.10 Steel Pipe <br /> Spacing of Brace 80' 0" (24.38 m) <br /> Orientation of Brace Longitudinal <br /> Bracing Material 1" Sch.40 <br /> Maximum Brace Length 7' 0" (2.13 m) <br /> Slenderness Ratio used for Load Calculation 200 <br /> True Angle of Brace for Calculation 45° <br /> Type of Fastener Fig.828 Across Beam <br /> Length of Fastener N/A <br /> Summary of Pipe within Zone of Influence <br /> 2.5"Sch.10 Steel Pipe(63.5 mm) 787724.4 m) <br /> G-Factor Used 0.5936 <br /> Allowance for Heads and Fittings 15% <br /> Conclusions <br /> Total Adjusted Load of Pipe in Zone of Influence 322 lbs (146 kg) <br /> Material Capacity 1310 lbs(594 kg) <br /> Fastener Capacity 1425 lbs(646 kg) <br /> Fig.4L Clamp 1425 lbs(646 kg) <br /> Fig.980 Universal Swivel 1425 lbs(646 kg) <br /> Structural Member Steel I-Beam <br /> Calculations prepared by Brett Hamilton <br /> The description of the Structural Member is for informational purposes only. <br /> TOLBraceT"software calculates the brace assembly only,not the structure it is attached to. <br /> Calculated with TOLBrace-8 <br /> Visit us at www.tolco.com <br />