Laserfiche WebLink
TLLBraceTM Seismic Calculation <br /> ECC Learning Resource Center Job# <br /> 1001 N Broadway <br /> i4rssiness Walrfdwi�es <br /> Brace Identification 3" Longitudinal Brace-C <br /> Brace Type (Per NFPA#13) NFPA Type B <br /> Braced Pipe(ft) 3" Sch.10 Steel Pipe <br /> Spacing of Brace 80' 0" (24.38 m) <br /> Orientation of Brace Longitudinal <br /> Bracing Material 1" Sch.40 <br /> Maximum Brace Length 7' 0" (2.13 m) <br /> Slenderness Ratio used for Load Calculation 200 <br /> True Angle of Brace for Calculation 45° <br /> Type of Fastener Wedge Anchor 1/2in, x 3 5/8in. (4,000 PSI Normal Weight Cracked Cot <br /> Length of Fastener 3 5/8in. <br /> Summary of Pipe within Zone of Influence <br /> 3"Sch.10 Steel Pipe(76.2 mm) 8o ft(24.4 m) <br /> G-Factor Used 0.5936 <br /> Allowance for Heads and Fittings 15% <br /> Conclusions <br /> Total Adjusted Load of Pipe in Zone of Influence 434 Ibs (197 kg) <br /> Material Capacity 1310 lbs(594 kg) <br /> Fastener Capacity 460 Ibs (209 kg) <br /> Fig.4L Clamp 1425 Ibs(646 kg) <br /> Fig.980 Universal Swivel 1425 Ibs(646 kg) <br /> Structural Member Mild Steel Concrete Slab <br /> Calculations prepared by Brett Hamilton <br /> `The description of the Structural Member is for informational purposes only. <br /> TOLBraceTM software calculates the brace assembly only,not the structure it is attached to. <br /> Calculated with TOLBrace-6 <br /> Visit us at www.talco.corn <br />