Laserfiche WebLink
SHEET NOTES: FLAG NOTES 0: <br /> A <br /> A. AREAS ABOVE CEILINGS IN PROJECT ARE BEING USED AS RETURN AIR 1. PATIENT CARE GIVEN AT IN-PATIENT SLEEPING ROOMS.SYSTEM TO 8. PROVIDE CEILING-MOUNTED LOW VOLTAGE OCCUPANCY SENSORS WITH HIGH OFF CONTROL OF LUMINAIRES NOTED;FACEPLATE TO BE HIGH STRENGTH <br /> PLENUMS.CONTRACTOR TO USE PLENUM RATED CABLEI INSTALLATION AUTOMATICALLY SHUT OFF LIGHTING IN SLEEPING ROOMS NOT PROVIDED AS IMPACT,INJECTION MOLDED PLASTIC CONSTRUCTION FOR AUTOMATIC ON/OFF POLYCARBONATE OR POLYCARBONATEI.011 BLEND WITH TAMPERPROOF 18. OVERRIDE CONTROLS FOR EXTERIOR PATIENT AREA TO BE PROVIDED AT <br /> TO MEET CODE REQUIREMENTS.SEE MECHANICAL PLANS FOR PLENUM PER EXCEPTION#2 TO C405.2.5.1 IN THE WSEC.DAYLIGHT RESPONSIVE CONTROL.PROVIDE POWER/RELAY PACKS AS NEEDED.FIELD VERIFY SCREWS IN EACH CORNER OF THE PLATE(CORTECH USA TIGER PLATES OR LIGHTING CONTROL SYSTEM TOUCHSCREEN AT THE NURSES'STATION;SEE <br /> AREAS. CONTROLS NOT PROVIDED PER C405.2.4 EXCEPTION#1.TYPICAL FOR ALL LOCATIONS OF POWER]RELAY PACKS WITH ALL OTHER TRADES;IF POSSIBLE PRE-APPROVED EQUAL).PROVIDE POWER/RELAY PACKS AS NEEDED.FIELD FLAG NOTE#15,THIS DRAWING. <br /> IN-PATIENT ROOMS. PER MANUFACTURER'S LENGTH LIMITATIONS,INSTALL IN ACCESSIBLE CEILING VERIFY LOCATIONS OF POWER/RELAY PACKS WITH ALL OTHER TRADES;IF <br /> B. UNLESS NOTED OTHERWISE,OCCUPANCY SENSORS ARE TO CONTROL SPACES OF STAFF ONLY AREAS(MEDS,TECH WORK,ETC).PROVIDE POSSIBLE PER MANUFACTURER'S LENGTH LIMITATIONS,INSTALL IN ACCESSIBLE 19. PROVIDE CEILING-FAN RATED BLANKED OFF JUNCTION BOX AT CEILING FOR 7oxeu <br /> ALL LUMINAIRES IN ROOMS IN WHICH THEY ARE INSTALLED.WHERE 2. AUTOMATIC DAYLGHTING CONTROLS NOT REQUIRED IN SPACE;NOT MORE PERMANENT LABELING ON ALL POWER/RELAY PACKS IDENTIFYING AREA CEILING SPACES OF STAFF ONLY AREAS(MEDS,TECH WORK,ETC).PROVIDE FUTURE INSTALLATION OF CEILING FANS.PROVIDE AN ADDITIONAL BLANKED <br /> MULTIPLE OCCUPANCY SENSORS ARE SHOWN IN ONE ROOM, THAN TWO GENERAL LIGHTING FIXTURES WITHIN THE COMBINED PRIMARY AND SERVED,SWITCH LEG(AS APPLICABLE)AND CIRCUITING. PERMANENT LABELING ON ALL POWERI RELAY PACKS IDENTIFYING AREA OFF JUNCTION BOX IN THE WALL FOR FUTURE CONTROLS(FIELD VERIFY <br /> OCCUPANCY DETECTED BY ANY SENSOR IS TO KEEP ON ALL LUMINAIRES SECONDARY SIDELIT ZONES. SERVED,SWITCH LEG(AS APPLICABLE)AND CIRCUITING. LOCATION).PROVIDE SPARE CONDUCTORS FROM CEILING BOX TO WALL <br /> (AND CONTROLLED RECEPTACLES WHERE APPLICABLE)IN THE ROOM 9. COMMISSION AUTOMATIC DAYLIGHTING CONTROLS IN ELEVATOR LOBBY TO STATION FOR FUTURE SEPARATE WIRED CONTROL OF FAN AND INTEGRAL LIGHT <br /> UNLESS NOTED OTHERWISE. 3. PROVIDE LEED COMPLIANT LIGHTING CONTROLS IN TREATMENT PLANNING ENSURE 10 FC MINIMUM IS MAINTAINED AT THE ELEVATOR THRESHOLD PER CONNECT BACK TO LIGHTING CONTROL SYSTEM TO ALLOW FOR OVERRIDE OF IN FAN.CAP OFF,MAKE SAFE AND LABEL SPARE CONDUCTORS.FIELD VERIFY <br /> ROOM;LIGHTING FOR ALL PRESENTATION WALLS TO BE SEPARATELY CODE REQUIREMENTS. LUMINAIRES VIA LIGHTING CONTROL SYSTEM TOUCHSCREEN AT THE NURSES' LOCATION OF ALL BOXES WITH ARCHITECT AND OWNER. <br /> CONTROLLABLE.PROVIDE THE FOLLOWING ENGRAVING ON THE WALL STATIOm <br /> STATION ON FLOOR.SEE LIGHTING CONTROLS SEQUENCE OF OPERATIONS FOR <br /> =TYPE X1 UNLESS NOTED OTHERWISE;FACES,ARROWS AND MOUNTING AS SHOWN. (RAISE/LOWER BUTTONS TO HAVE STANDARD SYMBOLS): DE CEILING-MOUNTED LOW VOLTAGE OCCUPANCY SENSORS WITH HIGH INTENDED OPERATION AT EACH ROOM TYPE. 20. ELECTRICAL CONTRACTOR TO PROVIDE FIRE RATED BOXES AT ALL RECESSED <br /> a) WALL STATION#1(ac,bd): ,INJECTION MOLDED PLASTIC CONSTRUCTION IN THE PATIENT TOILETS LUMINAIRE LOCATIONS IN FIRE RATED CEILINGS TO MAINTAIN FIRE RATING OF A • • <br /> II TYPE X4 UNLESS NOTED OTHERWISE;FACES,ARROWS AND MOUNTING AS SHOWN. BUTTON(CHANNEL)1:LINE 1:WEST WALL TIENT SHOWERS FOR AUTOMATIC ON/OFF CONTROL.FIELD VERIFY 15. LIGHTING CONTROLS SYSTEM TOUCH SCREEN FOR CONTROL OF NETWORKED CEILING ASSEMBLY.SEE ARCHITECTURAL RCP AND FIEL VERIFY EXACT <br /> LINE 2:OW OFF IONS OF OCCUPANCY SENSORS;LOCATE SO THEY ARE OUT OF REACH OF LIGHTING CONTROLS ON THIS LEVEL INCLUDING AREAS NOTED BELOW. LOCATIONS.COORDINATE LOCATIONS,LAYOUTS AND INSTALLATION 38 NORTHWEST DAVIS,SUITE 3D0 <br /> BUTTON(CHANNEL)2:LINE 1:EAST WALL ON STANDING ON THE TOILET OR SINK.PROVIDE POWER/RELAY PACKS CONTROLS NOTED BELOW ARE IN ADDITION TO LOCATION CONTROLS PROVIDED REQUIREMENTS WITH ALL OTHER TRADES.MAINTAIN ALL CODE AND PORTLAND,OR 97209 <br /> LINE 2:OW OFF DED.FIELD VERIFY LOCATIONS OF POWER/RELAY PACKS WITH ALL AT/NEAR THESE SPACES UNO.SEE LIGHTING CONTROLS SEQUENCE OF MANUFACTURER'S REQUIRED CLEARANCES.TYPICAL AT ALL FIRE RATED 503.245.7100 <br /> b) WALL STATION#2(ab,W): TRADES;IF POSSIBLE PER MANUFACTURER'S LENGTH LIMITATIONS, OPERATIONS FORADDITIONAL INFORMATION.EMERGENCY LUMINAIRES,WHERE CEILING LOCATIONS. <br /> LIGHTING CONTROL ZONE(LCZ)CIRCUITING BUTTON(CHANNEL)1:LINE1:SWALL IN ACCESSIBLE CEILING SPACES OF STAFF ONLY AREAS(MEDS,TECH PROVIDED,ARE TO BE CONTROLLED WITH THE NON-EMERGENCY LUMINAIRES IN 15055THAVE,SUITE300 <br /> LINE 2:OW OFF ,ETC).PROVIDE PERMANENT LABELING ON ALL POWER]RELAY PACKS THE SAME ROOMI AREAS UNLESS NOTED OTHERWISE. 21. CEILING AT ELEVATOR CONTROL ROOM IS FIRE RATED ASSEMBLY.PROVIDE FIRE SEAMS,WA 98101 <br /> LCZ# AREA CIRCUIT BUTTON(CHANNEL)2:LINE 1:NWALL FYING AREA SERVED,SWITCHLEG(AS APPLICABLE)AND CIRCUITING. RATED BOXESI ACCESS PANELS AS REQUIRED.FIELD VERIFY REQUIREMENTS AND 206.576.1600 <br /> LINE 2:OW OFF AS PARTOF LIGHTING CONTROL SUBMITTAL,ELECTRICAL CONTRACTOR SHALL LOCATIONS WITH ALL OTHER TRADES. <br /> LCZ-0.19 CIRC C406 WAITING 488 OL3L-8 SAN IRAN STREET <br /> LCZ-0.20 CORRIDOR C402 OL3L-10 11. PROVIDE FOLLOWING FUNCTIONALITY AT THE WALL STATIONS INDICATED,SWITCHLEG a PROVIDE GRAPHIC SAMPLES(SCREEN CAPTURES)OF TOUCH SCREEN CONTROL � SAN FRANCISCO,CA 94103 <br /> 4. PATIENT CARE IS DIRECTLY PROVIDED IN ROOM.DAYLIGHT RESPONSIVE IS AN EMERGENCY LIGHTING CIRCUIT TO BE CONNECTED VIA UL924 BYPASS WITH SCREENS AND ORGANIZATION TREE FOR REVIEW BY OWNER AND DESIGN TEAM. 415,252.7063 <br /> LCZ4.21 HALLWAY C403 WEST OL3L-8 CONTROLS NOT REQUIRED PER C405.2.4 EXCEPTION#1. DIMMING OVERRIDE PER CODE REQUIREMENTS. a) PATIENT SLEEPING ROOMS:MANUAL COLOR TUNING,OW OFF AND RAISE LOWER 0ANKROM MOISAN ARCHITECTS,INC. <br /> LCZ4.22 ELEV VEST C405 OL3L-8 a) BUTTON#1:SWITCHLEGS abc(ALL LIGHTS IN ROOM)ON TO 100% CONTROL SHALL BE PROVIDED FOR THE R6 LUMINAIRES IN THESE ROOMS.THE S3 <br /> LCZ-0.23 CIRC C404,SOBERING BAYS OL3L-10 5. LIGHTING CONTROLS FOR ROOM PROVIDED AT NURSES'STATION DUE TO b) BUTTON#2:SWITCHLEGS a AND b(PRESENTATION WALL)ON TO 30%,SWITCHLEG WALL LUMINAIRES ARE TO HAVE TOUCH-ACTNATED LOCAL DIMMING CONTROLS SIDER+BYERS ASSOCIATES,INC. <br /> c ON TO 80% SEPARATE LOCAL SWITCH NOT REQUIRED)AND SHALL ALSO HAVE OW OFF T <br /> SAFETY CONCERNS AS ALLOWED BY ENERGY CODE SECTION C405.2.3 ( (�\ <br /> LCZ-0.24 HALLWAY C403 EAST OL3L-10 c) BUTTON#3:SWITCHLEGS a AND b OFF,UEGS S AND <br /> c ON TO 30% ROOM O BE SEPARATELY <br /> NURSES'STATION ABLE.SCREEN.EACH SWITCHLEG IN EACH MECMANICALAND SITE 3DO \` <br /> EXCEPTION#1.LIGHTING CONTROL SYSTEM TO PROVIDE COLOR TUNING d) BUTTON i]4:SWITCHLEGc OFF,SWITCHLEGS aANDb ON T030% 192 NICKERSON,SUITE 300 <br /> CONTROLS FOR RES LUMINAIRE AND DMX CONTROLS FOR S7 FIXTURES AS WELL ROOM TO BE SEPARATELY CONTROLLABLE. <br /> e) ROCKER SWITCH:RAISE]LOWER OF SELECTED SCENE LEVEL EAST O 100%O MANUAL OVERRIDE OF SCHEDULED DIMMING TO BRING SEATTLE,WA 9810E <br /> AS MANUAL ON/ AND RAISE]LOWER CONTROLS. LUMINAIRb) EES T0100%OUTPUT. zoe.za5zs66 <br /> NOTES: 12. PROVIDE FOLLOWING FUNCTIONALITY AT THE WALL STATIONS INDICATED,SWITCHLEGa c) LEVEL 4 LIVING/DINING ROOMS:MANUAL OVERRIDE OF SCHEDULED DIMMING TO <br /> A.SEE E3.09 FOR LIGHTING CONTROL ZONES ON LEVEL 4. 6. MANUAL LIGHTING CONTROLS PROVIDED WITH LIGHT REDUCTION PER IS AN EMERGENCY LIGHTING CIRCUIT TO BE CONNECTED VIAA UL924 BYPASS WITH BRING LUMINAIRES TO 100%OUTPUT,MANUAL OW OFF AND RAISE/LOWER <br /> B.ROUTE EMERGENCY LUMINAIRES THROUGH EMERGENCY LIGHTING INVERTER; C405.2.3.1.OCCUPANCY SENSOR/TIME SWITCH CONTROLS NOT REQUIRED FOR DIMMING OVERRIDE PER CODE REQUIREMENTS. CONTROLS.EACH LIVING ROOM AND THE DINING ROOM ARE TO BE SEPARATELY <br /> PROVIDE UL 924 BYPASS DEVICES AS REQUIRED BY CODE. SPACES WHERE PATIENT CARE IS PROVIDED OR SPACES WHERE AUTOMATIC a) BUTTON#1:SWITCHLEGS abc(ALL LIGHTS IN ROOM)ON TO 1DO% CONTROLLED. <br /> C.UNLESS OTHERWISE NOTED,CONNECT LUMINAIRES(NORMAL AND EMERGENCY)IN SHUTOFF WOULD ENDANGER OCCUPANT SAFETY OR SECURITY PER C405.2.2 b) BUTTON#2;SWITCHLEGS a AND b ON TO 100%,SWITCHLEG c OFF d) QUIET ROOM:MANUAL COLOR TUNING,ON/OFF AND RAISE LOWER CONTROL <br /> LIGHTING CONTROL ZONES TO CIRCUITS NOTED ABOVE.CIRCUITING FOR EXCEPTION. c) BUTTON#3:SWITCHLEGS a AND b OFF,SWITCHLEG c ON TO 100% SHALL BE PROVIDED FOR THE R8B LUMINAIRE IN EACH ROOM.DMX CONTROLS C MPASS <br /> LUMINAIRES NOT LOCATED IN LIGHTING CONTROL ZONES INDICATED IN PLANS d) BUTTON A:SWITCHLEGS a AND b ON TO 80%,SWITCHLEG c ON TO 30% SHALL BE PROVIDED FOR THE S7 LUMINAIRES IN THE ROOM. <br /> BELOW.CONNECT UNSWITCHED LEG OF CIRCUIT INDICATED TO EXIT SIGNS AND =STATIONTION FOR MANUAL ON/OFF AND RAISE LOWER CONTROLS OF II) ROCKER SWITCH:RAISEI LOWER OF SELECTED SCENE e) EXTERIOR PATIENT OUTDOOR SPACE:MANUAL ON/OFF CONTROL FROM DUSK TOBUG-EYES.CONNECT LUMINAIRES WITH INTEGRAL BATTERY PACKS PER S IN THE SOBERING BAYS;PROVIDE SEPARATE CONTROIS FOR EACH DAWN.MANUAL OVERRIDE OF CURFEW SWEEP-0FF. T T��l'- <br /> MANUFACTURERSINSTRUCTIONS. OTED.WALL STATION CONTROL OF LUMINAIRES AT CIRCULATION 13. NETWORKED OCCUPANCY SENSOR(S)TO PROVIDE AUTOMATIC AFTER HOURS 1~1 ulTCHLEGS a AND b)SHALL ONLY PROVIDE RAISE?LOWER CONTROLS. CONTROL OF LUMINAIRES IN ROOM/AREA.WHERE MULTIPLE OCCUPANCY i6. <br /> ES AT CIRCULATION C404 ARE TO BE DIMMABLE ONLY DOWN TO 30% SENSORS ARE SHOWN IN ONE SPACE,OCCUPANCY DETECTED BY ANY SENSOR TO ALLOW FOR OVERRIDE OF TIMESWEEP FUNCTION(I.E.PUBLIC SHALL NOT BE ABLE <br /> SHALL NOT DIM TO OFF)FOR STAFF SAFETY.PROVIDE ENGRAVING AT IN SPACE SHALL HOLD ON?BRING ON TO FULL OUTPUT ALL LUMINAIRES IN TO MANUALLY TURN ON/OFF LIGHTING DURING BUSINESS HOURS)UNLESS OTHERWISE <br /> STATION BUTTONS IDENTIFYING AREAS SERVED. SPACE.DURING NORMAL BUSINESS HOURS,OCCUPANCY SENSORS SHALL BE NOTED.TYPICAL, <br /> DEACTIVATED. 17. CONNECTALL LUMINAIRES IN ROOM TO CIRCUIT INDICATED UNLESS NOTED <br /> ^ 9 14. PROVIDE VANDAL RESISTANT LOW VO GE WALL SWITCHES FOR MAN�ONI OTHERWISE. 1 15 I <br /> IJJ --------_ __ _«+ _ _ __ __ __ _ _ _ _ __ _-__-_ - - - - - - <br /> ON <br /> - R£-0 - DZ4.27P - - E]R3 ❑R3 '?31 3 _-- R3 R3.- P❑R3. R - i3�P C R3 ~R3 3 7 R3- ❑R3 QR3 R <br /> O❑ ❑ ! O L3L-2 L -L3L-0 L3L-0 17 17 3L-0 <br /> _ _ _ <br /> ima--1 <br /> - L - R a L3L-2 06 1 L O5 _.3❑ 105�R3- 17 ❑os- 1 02 R3 7 R R3 ❑R3O - P <br /> 3L-2 <br /> 17 R3 R3 I��-f-��'p�°�'�y R3 R <br /> _ - --- DZ4.1P� $Pox R-3 i IDZ.2P R3 ,DZ4R.3gP :� DZ44P R3 1Pp D2.6P� 3 �°.,OS <br /> DZ48P05 $"-" I Rg O(OS <br /> L 2. _.d 3 , d E 1� LJd Lld' -, EM _. ..LJd __._..Lid _ te a.- d_. cl� �f �-ze�sEeI�D=a�PC <br /> b <br /> - - -- --- - - S 3�2 _ <br /> 1 E b� Rg3L 8 3L-8 0�8 1 R5 R9 8 P-x 1 8 T $a.n <br /> - TL•'JI '`F pi OIL 12 R3 R3 <br /> - I d R-_fJlq C3L-0-L3L <br /> 3L-2 - L3L-2 L3L-0 EM OL3 f OL3L-10 +,Ci L3 �A 2 0 L L-0 L3L-0 <br /> v_ u os $D OS OL3L-8 OL�L-8 R9 3L 8 s 1-4 R5oa OL3L-10 ___ ��PR4") <br /> _ L3L-0R3 OL3-1 <br /> £M 13L- 08 R3 <br /> a_ a LJ <br /> 1 13E Y b - 3 i2 �� L L'8 F2 F2� Cd°Dz414d. L3L-4 <br /> EE I'D. 'd <br /> 19 07A23P L2 _,� Dx -- - F L3L OL3L-1 ) os <br /> D5 L2 y X3 13 ane P <br /> TYPICAL OF 'tI ' _ _ R9 EMIZJLos ❑R9 R9❑ os L EM eb 6 z R4' -1 17 u, F1 W <br /> 1� T5EM ffI IR-9-_I -L <br /> P Ia LJh LJ _ - )- U) <br /> �� _.FD 1 u a X®� J L3L-12 4 h h Q <br /> 16 - \ \ / L8",b13 ❑R9 c 44 <br /> -c. op.I s1 $ ._R1-6D ,EM d it <br /> TYPICAL .1D3L Doh b R5-4 R5-4 4 p __ d L L-0 17 L3L-0 17 Y � <br /> a X3; 5 S ._ O5_ OS Os .2S V 0 <br /> �D1A D1A .b\1. __' ! %� D4 EM 04 I c d l _ _ I- <br /> '-d-- d° EMS / \ 41,3E-8 - I3L-4 0 W <br /> ,02 'D4Aoc 9 D4Ad c _ I; r -mod 'i -- x nDx <br /> X3 P _ TR3 ___ _ J <br /> Nl�a _I_ d --EM d IRS <br /> - fig ___.--JJ I m CC <br /> �g-g-_�ro R^g �-�a - w <br /> E b-.T R2-4B R2 ,..� �_ LJ _ O I� a R3 - <br /> I I I I, b h E EM OS 13 I EM 0 e� I OS EM I R3,EM � bLLI <br /> - - - BZ4.24P 1p C X3 13 _ _ M D a7P-: 8 EM 1 _ Q Q <br /> �- DZa13S _ _ EM - - - - O <br /> W6, IJ W6,E <br /> w_ <br /> _ ­q L31-4 L3L _ ❑ Q <br /> 01 <br /> TYPICAL Pc ao RTos I, I I O - O m 0. <br /> O <br /> oz322b \ <br /> 7 20 = <br /> b_os Da D4\` S\ I TYPICAL / 1 m M U <br /> ❑b pq <br /> P n <br /> s °P v i <br /> po <br /> _ 18 =_ _ _ _-__.-.._. <br /> D4A p _ DATE REASON FOR <br /> .._._. 6 n^ D4, ,,,-�D4!IDo D4 REVISION IssUE <br /> • ••_• •� •� i W LEM W6,EM _... GMPADRENDUM S <br /> r- �T\ 1 - 2 09 06 22 <br /> O1 ' 3 a92022 AMP ADDENDUM <br /> Os ° '' P Da a, ' 4 102022 A6401 <br /> �.� a•�Nf g ,.a,EM aEMi a�A321P P �� DZ4. - a.EM a 'nz.20.a Asl-04 <br /> - 2,E a. _ a a• •EM ,. Dz �� R4 _.R4 �, sbcl APPROVAL s Aslns <br /> TAMP <br /> 83 S <br /> R6 R6 OS 10.. S OS a I`10 IJII O _ 'h , OR7 c_1 5I b7 4 5 6 <br /> D4- <br /> $Oa. $:Oa b¢Q' Dp L - 2L2 Db- D4'b D4'b - DCb D4°b D4°b. � OD4 EM 0�X �*h` <br /> 4 _ d 8 _ Os Db � RBB D4 � I1ao e'EM �. + -h7 �a <br /> PC2 Y w'EM x°� EM x°� w x°TYPIC Ow M x w MU1 POF2 I DM °D %I�D4° D4 a- "t -_D4 20 .. h�DM <br /> I I I I I <br /> _ o� .I g• <br /> DZ3.195 ) oL-a_ oe ATYPICAL <br /> u <br /> r <br /> S 3 + 15 - - x I .--- r Dz3.165� - x Dz3.t5S - Dza 15 - <br /> / b b b b b b:' 11 Ica R5 B 5-0 R5-0 R5E6 EM- <br /> S1-16 <br /> - --a ac O D1A r - b __ a- a---_-_- <br /> J O - Rs yp6 Rs /g6 EMM �© os b I LEVEL 4 FLOOR <br /> L Oa Oa lla Oa Va- lJa L' - D1A�-,Q -_ '' os 11 os I, PLAN-LIGHTING <br /> a a 1, c <br /> I`I - �b b 3 a4' EM" OS OS I -, DlA - R5-68 I RSo4 R5o i RS-68 RS-fib I PLAN <br /> - _ <br /> T -.... - - _.... _ _ _ <br /> _ L Dz3,aP SI 05 SET <br /> ' A <br /> I <br /> UNLESS NOTED OTHERWISE, I TYPICAL FOR ALL PATIENT I (�"b UNLESS NOTED OTHERWISE, UNLESS NOTED OTHERWISE, <br /> h" 8 <br /> CONNECT ALL LUMINAIRES PRIVATE AND SEMI-PRIVATE RooQMS CONNECT ALL LUMINAIRES CONNECT ALL LUMINAIRES <br /> AND EXIT SIGNS IN THIS AND EXIT SIGNS IN THIS AND EXIT SIGNS IN THIS D C DATE PROJECTNUMSER <br /> Q AREA TO CIRCUIT OL3L-2 AREA TO CIRCUIT OL3L-4 AREA TO CIRCUIT 013E-6 P® 12.20.2023 21016 <br /> KEY PLAN y SHEET NUMBER.. ... <br /> 7�T LEVEL 4 FLOOR PLAN - LIGHTING PLAN -" E <br /> 1V SCALE:1/8'-1'-0' <br /> 0 4 8 16 32 <br />