SHEET NOTES: FLAG NOTES®: 1NpA <br /> A. AREAS ABOVE CEILINGS IN PROJECT ARE BEING USED AS RETURN AIR 1. COORDINATE LOW VOLTAGE SYSTEMS REQUIREMENTS AT FLOORBOXES 7. AT ALL WALL-MOUNTED LOW VOLTAGE SYSTEMS OUTLETS,ELECTRICAL 12. PROVIDE TWO-WAY CALL SYSTEM CALL BOX AT ELEVATOR LOBBIES. ¢orl <br /> PLENUMS.CONTRACTOR TO USE PLENUM RATED CABLE/INSTALLATION WITH OWNER AND ELECTRICAL CONTRACTOR.FOR BID PURPOSES, CONTRACTOR TO PROVIDE A 0.5-INCH CONDUIT FOR THE LOW VOLTAGE COORDINATE EXACT LOCATIONS WITH ARCHITECT AND FIRE MARSHAL. 2vo a y <br /> TO MEET CODE REQUIREMENTS. ASSUME TWO CATS DROPS AND ONE HDMI CONNECTION AT EACH SYSTEMS CABLING FROM THE WALL-MOUNTED OUTLET UP INTO THE <br /> FLOORBOX UNLESS NOTED OTHERWISE. ACCESSIBLE CEILING SPACE.PROVIDE BUSHING ON END OF CONDUIT IN 13. ALL DEVICE COVER PLATES IN AREAS ACCESSIBLE TO PATIENTS ON <br /> CEILING SPACE.CONFIRM CONDUIT SIZE REQUIREMENTS WITH LEVELS 3 AND 4 ARE TO BE HIGH-ABUSE.COVER PLATES ARE TO BE HIGH �o aJ7 <br /> 2. MAGNETIC HOLD OPENS FOR ELEVATOR SMOKE DOORS/CURTAINS TO BE DESIGN-BUILD LOW VOLTAGE CONTRACTOR. STRENGTH POLYCARBONATE OR POLYCARBONATFI NYLON BLEND WITH Au <br /> CONNECTED TO THE FIRE ALARM SYSTEM PER CODE AND AHJ TAMPERPROOF SCREWS IN EACH CORNER OF THE COVER PLATE. <br /> REQUIREMENTS. 8. AT ALL FLOORBOXES WITH LOW VOLTAGE SYSTEMS OUTLETS, PROVIDE CORTECH USA TIGER PLATES OR PRE-APPROVED EQUAL <br /> FrVEN <br /> LARM SYSTEM IS TO BE DESIGN-BUILD BY THE FIRE ALARM THE DESIGN-BUILD CONTRACTORS ARE TO COORDINATE WITH THE ELECTRICAL CONTRACTOR TO PROVIDE A 1-INCH CONDUIT FOR THE LOW COMPATIBLE WITH DEVICES TO BE INSTALLED IN THESE AREAS. <br /> RACTOR. ARCHITECT,OWNER AND FIRE MARSHAL FOR FIRE ALARM SYSTEMS 3. WAPS FOR WIRELESS NETWORK PROVIDED BY OWNER.CONTRACTOR TO VOLTAGE SYSTEMS CABLING FROM THE FLOORBOX IN THE SLAB INTO THE <br /> ( ) PROVIDE ONE CAT6 CABLE TO EACH WAP LOCATION FROM TELECOM NEAREST WALL THEN ROUTE UP INSIDE THE WALL UP INTO THE 14. ADD ALTERNATE:OVER/UNDER DOOR ALARMS AT PATIENT ROOMS.SEE <br /> TO CONFIRM FINAL SYSTEM REQUIREMENTS AND EQUIPMENT AND CLOSET ON THAT LEVEL.CONFIRM FINAL QUANTITIES AND LOCATIONS ACCESSIBLE CEILING SPACE,PROVIDE BUSHING ON END OF CONDUIT AT SPECIFICATION SECTION 27 00 00 FOR REQUIREMENTS AND INFORMATION. <br /> ANIC SYSTEM WILL BE PROVIDED AND INSTALLED BY THE DEVICE QUANTITIES,LOCATIONS AND FUNCTIONALITY. WITH OWNER. CEILING SPACE.CONFIRM CONDUIT SIZE REQUIREMENTS WITH Alk T M <br /> OR.THE ELECTRICAL CONTRACTOR SHALL PROVIDE REQUIRED THE OWNER WILL PROVIDE WIRELESS NETWORK WARS,CCTV SYSTEM DESIGN-BUILD LOW VOLTAGE CONTRACTOR. 15. PROVIDE DATA CONNECTION FOR GENERATOR AND ATS REMOTE <br /> STRUCTURE FOR SYSTEM(CONDUITS WITH PULLSTRINGS AT NVR DEVICES,AND CCTV SYSTEM CAMERAS.THE LOW VOLTAGE 4. PROVIDE ALARM AT DOOR TO ALERT LOCALLY AND THROUGH THE ANNUNCIATORS.CONFIRM EXACT LOCATIONS WITH ELECTRICAL • • <br /> isan <br /> CEILING AREAS SUCH AS PARKING GARAGE,SLEEVES/ CONTRACTOR IS TO PROVIDE ALL OTHER EQUIPMENT,DEVICES, ACCESS CONTROL SYSTEM IF DOOR IS PROPPED OPEN. 9. LOW VOLTAGE CONTRACTOR TO PROVIDE SOUND MASKING SYSTEM IN CONTRACTOR. <br /> TOPPING,RACK SPACE FOR EQUIPMENT,ETC).THE LOW PARTS,PIECES,CABLING,TERMINATIONS,ETC REQUIRED FOR AREAS NOTED.WHERE SPEAKERS ARE INSTALLED AT HARDLID CEILINGS, 38INDKIFIN rDAl WE 300GE CONTRACTOR SHALL PROVIDE NETWORK CONNECTIONS ON COMPLETE AND FULLY OPERATIONAL SYSTEMS PER CODE,AHJ,AND5. INSTALL STACKED COMBINATION CAN/DATA/HDMI OUTLETS AT ELECTRICAL CONTRACTOR TO PROVIDE 314-INCH CONDUIT FROM SYSTEM 16. PROVIDE DATA CONNECTIONS AS NEEDED TO SUPPORT BUILDING DDC KnAND,DR 97209 <br /> WALL-MOUNTED MONITOR INDICATED.TOP OUTLET FOR WALL-MOUNTED AV RACK(S)TO SPEAKER LOCATIONS AS REQUIRED.CONFIRM SYSTEM/ENERGY METERING SYSTEM;SEE SINGLE LINE DIAGRAM. s03.z4s.71W <br /> FLOOR;CONFIRM EXACT LOCATIONS AND QUANTITIES WITH OWNER REQUIREMENTS. MONITORS TO BE INSTALLED AT ELEVATION INDICATED.LOWER OUTLET REQUIREMENTS WITH OWNER AND DESIGN-BUILD CONTRACTOR. COORDINATE REQUIREMENTS AND LOCATIONS FOR DDC SYSTEM WITH <br /> M VENDOR.FOR BID ASSUME TWO NETWORK DROPS PER AT EACH LOCATION TO BE MOUNTED WITHIN CABINETRY BELOW.TYPICAL MECHANICAL CONTRACTOR. 1505 5M AVE,WE SaoR TO BE LOCATED IN THE IDF/SERVER CLOSETS ON THOSE THE DESIGN-BUILD CONTRACTORS ARE RESPONSIBLE FOR START-UP, FOR ALL LOCATIONS UNLESS NOTED OTHERWISE. FORBIDDING 10. CCTV CAMERAS PROVIDED BY OWNER.LOW VOLTAGE CONTRACTOR TO SFATr EWA A101 <br /> RS.SEE VENDOR'S DRAWINGS FOR DEVICE LOCATIONS. TESTING,COMMISSIONING,AND TRAINING FOR ALL FIRE ALARM AND PURPOSES,ASSUME HDMI INPUT OUTLET LOCATIONS(FOR HDMI SOURCE PROVIDE ONE CAT6 CABLE TO EACH CCTV LOCATION FROM CCTVzos.s76.1600LOW VOLTAGE SYSTEMS IN THE BUILDING. -COMPUTER,ETC)AT LOWER WALL OUTLET IN STACK.CONFIRM EXACT SYSTEM.CONFIRM FINAL QUANTITIES AND LOCATIONS WITH OWNER. 1010MARD911M <br /> THER LOW VOLTAGE SYSTEMS(TELECOM,CAN,ACCESS LOCATION(S)OF HDMI INPUT OUTLETS WITH OWNER.ELECTRICAL ELECTRICAL CONTRACTOR TO PROVIDE JUNCTION BOX AND 314-INCH SAN FRMCM,a94103 <br /> ROL,ETC ARE TO BE DESIGN-BUILT BY THE LOW-VOLTAGE THE ELECTRICAL CONTRACTOR IS TO PROVIDE ALL LINE VOLTAGE CONTRACTOR TO PROVIDE 1-INCH CONDUITS BETWEEN OUTLETS FOR CONDUIT WITH PULLSTRING TO NEAREST ACCESSIBLE CEILING FOR ALL als.zsz.70F3 <br /> TELECOM CABLING. CCTV CAMERA LOCATIONS AT BUILDING EXTERIOR,ON INTERIOR WALLS, p ANIDmM MDI3AN ARWIECTB,we <br /> CONTRACTOR. POWER AND INFRASTRUCTURE REQUIREMENTS(CONDUITS,BACK AND ON HARD-LID CEILINGS.PROVIDE BUSHING AT CONDUITS ENDS. <br /> BOXES,HANGERS,SUPPORTS,ETC)AS REQUIRED FOR ALL LOW 6. INSTALL STACKED COMBINATION CATVI DATA/HDMI OUTLETS AT SIDER+BYERS ASSOCIATES,INC. <br /> DEVICES AND EQUIPMENT SHOWN ON THESE DRAWINGS ARE FOR VOLTAGE SYSTEMS. WALL-MOUNTED MONITOR INDICATED.TOP OUTLET FOR WALL-MOUNTED 11. LOW VOLTAGE DESIGN-BUILD CONTRACTOR TO PROVIDE CARD READERS, E(�, <br /> MONITORS TO BE INSTALLED AT ELEVATION INDICATED.LOWER OUTLET REQUEST FOR EXIT SENSORS,DOOR POSITION SENSORS,AND ERE ME04WIEFS0ND UrrEELE 3. , <br /> BIDDING PURPOSES ONLY. � 192 NIIXERSON,SUITE 300 <br /> SEE DIVISION 27 AND 28 PERFORMANCE SPECIFICATIONS FOR AT EACH LOCATION TO BE MOUNTED WITHIN CABINETRY BELOW.TYPICAL REQUIRED)POWER SUPPLIES.COORDINATE INSTALLATIONS WITH THE SEAl WA98ro9 <br /> ADDITIONAL INFORMATION AND REQUIREMENTS. FOR ALL LOCATIONS UNLESS NOTED OTHERWISE. FORBIDDING DOOR HARDWARE PROVIDER/INSTALLER.SEE DOOR HARDWARE 205Z5.2955 <br /> PURPOSES,ASSUME HDMI INPUT OUTLET LOCATIONS(FOR HDMI SOURCE SPECIFICATION SECTION AND DOOR SCHEDULE IN ARCHITECTURAL <br /> -COMPUTER,ETC)AT LOWER WALL OUTLET IN STACK AND AT FLOOR BOX DRAWINGS FOR ADDITIONAL INFORMATION. <br /> 0 IN ROOM.CONFIRM EXACT LOCATION(S)OF HDMI INPUT OUTLETS WITH <br /> OWNER.ELECTRICAL CONTRACTOR TO PROVIDE 1-INCH CONDUITS <br /> BETWEEN OUTLETS FOR TELECOM CABLING <br /> 7 8\I 9\� 10 „ 12 73 14 15 C MPASS <br /> Y Health <br /> I ' LOTUS <br /> 0_ - ___ _ _ _ _ _ _ _ _ _ _ _ _ � development partners <br /> n I EMI <br /> = s a <br /> 2 3 A 'I -- __ __ I• <br /> ___- <br /> - 5 <br /> E5.01 <br /> _ I <br /> , <br /> 12 <br /> 2 Q 2 <br /> - O ... • C� <br /> 1 12 <br /> N <br /> oN <br /> J Y < <br /> -' <br /> ^ <br /> U <br /> I H <br /> - OJLLI <br /> U — _ — — _ — — — — — — — 360�— — — — — — — — — — — _ — — ___ — —� m ; <br /> ,.. .,..,,.-.� v"`� -. <br /> Lu <br /> 2 <br /> I I I I I I 0 Q In <br /> O m a <br /> m � ° <br /> I 4 I I I I �I -� I I <br /> � — — — — — — — — — — — —�— — — — — ——�' — — — — — —� RENS�ON� DA,E RFASOx WR 65UE <br /> ox" i <br /> 14 14 I j uR I -.. D - <br /> - --;_i I soOARRRovusraMR <br /> TYPICAL <br /> 14 14 1 14 14 1 14 14 14 1 14 14 14 1 <br /> i <br /> 1 <br /> , r L <br /> _ I Er� <br /> - LEVEL 3 FLOOR PLAN- <br /> - - - - - - - - - - - - - - 15 - - - - - - - - PRELIMINARY SYSTEMS <br /> PLAN <br /> 7 8 <br /> TYPICAL I TYPICAL I GMP SET <br /> I <br /> LEVEL 3 FLOOR PLAN - PRELIMINARY SYSTEMS PLAN B <br /> N SCALE:1/8'=1'-0' <br /> D c DATE PRDIER NUMBER <br /> E9® 09.20.2022 21016 <br /> SHEEP NUMBER _ <br /> NEY PLW <br /> E4.03 <br /> D 4 8 16 32 <br />