E>40-023-F1 G5-CP1 RL5-5: INPUT/OUTPUT POINTS SUMMARY a>40-023-F1 G5-CP1 RL5-6: INPUT/OUTPUT POINTS SUMMARY
<br /> ADDRESS: CONTROLLER #RL5-5 PANEL LOCATION: BLDG 40-023, FIRST FLOOR, COL: X/X.XX ADDRESS: CONTROLLER #RL5-6 PANEL LOCATION: BLDG 40-023, FIRST FLOOR, COL: X/X.XX
<br /> RL5-5 rr-__) BACNET MSTP FROM RL5-4 RL5-6 rr 84CNET MSTP FROM RL5-5
<br /> CPO-RL5 BACNIET GND 64 -j I- CPO-RL5 BACNEr GNP 64 I I
<br /> MSTP C-63 -=Z=-_ -J
<br /> BUS C+62 - --}� BACNET MSTP TO RL5-6 MSTP C-63 -_-_-
<br /> BUS C+62 - -}� BACNET MSTP TO RL5-7
<br /> DEVICE INSTANCE : -Q1 DEVICE INSTANCE : -Qi
<br /> SYLK WMl 30 SYLK WM1 30
<br /> BUS WM2 31 BUS WN2 31
<br /> GNP 61 GNP 61
<br /> UI10 60 UI Ill 60
<br /> 11I959 023Ahu6L CD11 Enable Push Button U1959 023Ahu6LCD1 1 EnbPshBtn
<br /> GNP 58 GNP 58
<br /> 023Ahu6L CD9 Enable Push Button UI857 023Ahu6LCD9EnbPshBtn 023Ahu6L CD10 Enable Push Button U1857 023Ahu6LCD1OEnbPshBtn
<br /> 023Ahu6L CDS Enable Push Button UI756 023Ahu6LCDBEnbPshBtn 023Ahu6L CD22 Cross flow Damper Feedback UI756 023Ahu6LCD22CrsFloDmprFdbk
<br /> U GNP 55 U GNP 55
<br /> 023Ahu6L CD9 Dam er Feedback I UI654 023Ahu6LCD9DmprFdbk 1023Ahu6L CD11 Damper Feedback I U1654 023Ahu6LCD11DmprFdbk
<br /> 023Ahu6L C09 Discharge Air Temperature U1553 023Ahu6LCD9DaTemp 023Ahu6L CD11 Discharge Air Temperature U1553 023Ahu6LCD1 1 DaTemp
<br /> GNP 52 GNP 52
<br /> 023Ahu6L CD9 Air Flow U1451 023Ahu6LCD9XrFIo 023Ahu6L CD11 Air Flow (TR I 023Ahu6LCD11AirFlo
<br /> 023Ahu6L COS Damper Feedback UI356 023Ahu6LCD8DmprFdbk 023Ahu6L CD10 Dumper Feedback UI350 023Ahu6LCD10DmprFdbk
<br /> GNP 49 GNP 49
<br /> 023Ahu6L CD8 Dischar a Air Temperature 111248 023Ahu6LCD8DaTemp 1023Ahu6L CD10 Discharge Air Temperature U1248 023Ahu6LCD1ODaTemp
<br /> 023Ahu6L CD8 Air Flow 9 UI147 023Ahu6LCD8XrFIo 0 023Ahu6L CD10 Air Flow UI147 023Ahu6LCD1OAirFlo
<br /> UI7-UI6=10k,20k,0-10v,Dry Contact GNP 46 UI1-UI6=10k 20k,0-10v,Dry Contact m GNP 46
<br /> UI7-Ul10=PT1000,0-10v,Dry Contact UI7-UI10=PTIODO,0-10v,Dry Contact
<br /> 24V-43 24V-43
<br /> A06 42 A06 42
<br /> CNT 41 75-F 41
<br /> A05 40 A05 40
<br /> 24V-39 247-39
<br /> A 004 38 A 004 38
<br /> D UNT 37 D 15F 37
<br /> A0336 023Ahu6L CD22 Cross Flow Damper Control A0336 023Ahu6LCD22CrsFloDmprCtrl
<br /> 24V-35 X GENERAL NOTES
<br /> 023Ahu6L CD9 Dam er Control A0234 023Ahu6LCD9DmprCtrl 023Ahu6L CD11 Damper Control 023Ahu6LCD11DmprCtrlGND 33 `R023Ahu6L CD8 Dam er Control A0132 023Ahu6LCD8DmprCtrl 023Ahu6L CD10 Dam er Control 023Ahu6LCD1ODmprCtrl 1. REFER TO WIRING GUIDELINE REFERENCE ON SHEET 40-023-E901-5A
<br /> 0-11vdc,A01-A02=lOn A,AO3-AO6=1mA 24V„ 3 4 GND 0-11vdc,AO1-AO2=10mA,A03-A06=lrrkA 24V- FOR WIRING DETAILS.
<br /> R03 25 1 R03 25 2. REFER TO GENERAL WIRING DETAILS ON SHEET 40-023-E901-4A.
<br /> IN3 2a T.IN3 24 3. REFER TO BACNET WIRING DETAILS ON SHEET 40-023-E901-4C.
<br /> R02 23 R02 23
<br /> D IR0121 D 'Ro1L REFERENCE DRAWINGS
<br /> D 1INl 20 B 1 INI 20
<br /> RN 19 RN l9
<br /> RN 18 z, RN 18 REFER TO DWG. 40-023-E932-3F FOR PANEL LAYOUT.
<br /> I R04 16 0 1 R04.17 l6 REFER TO DWG. 40-023-E932-3G FOR PANEL LAYOUT.
<br /> 15-253voc,R01,R04=10A,R02-RD3=4A 15-253vac,R01,R04=10k R02-R03=4A
<br /> T11414 T0414 CONSTRUCTION NOTES
<br /> c� TN 13 om TN 13
<br /> D TD312 D TD312 FIELD TO DETERMINE DEVCE INSTANCE NUMBER ONSfTE.
<br /> 0 T0211 0 T02 It
<br /> TN 10 TN 10
<br /> T01 9 T01 9
<br /> Triac,24VAC,600mA T„ 8 Triac,24VAC,600mA T„ 8
<br /> o TN 7 TN 7
<br /> (GNID24V0 6 (GND)24Vo 5
<br /> 24V„ 5 24V„ 5
<br /> 24 VAC (GNDX24y0 a 24 VAC FROM PSH500-2(OUT-1) 24 VAC cGNn)2avo 4 24 VAC FROM PSH500-2(OUT-2)
<br /> zav- 3 REFER DRAWING NUMBER E932-3L FOR 24V„ 3 REFER DRAWING NUMBER E932-31L FOR
<br /> CONNECTION CONNECT ON
<br /> BILL OF MATERIAL BILL OF MATERIAL
<br /> PANEL DEVICES PANEL DEVICES
<br /> TAG TOT PART NUMBER MANUFACTURER DESCRIPTION TAG TOT PART NUMBER MANUFACTURER DESCRIPTION
<br /> NAME QTY NAME QTY
<br /> EA3 1 A-16N16ALP HOFFMAN 16xl6x6 NEMA 1 Medium Hinged-Cover Enclosure EA3 1 A-16N16ALP HOFFMAN 16xl6x6 NEMA 1 Medium Hinged-Cover Enclosure
<br /> with Perf with Perf
<br /> CPRL5 1 CPO-RL5 HONEYWELL CP OPEN, ROOM CONTROLLER, 24VAC, SYLK BUS, 10 UI, CPRL5 1 CPO-RL5 HONEYWELL CP OPEN, ROOM CONTROLLER, 24VAC, SYLK BUS, 10 UI,
<br /> 6 AO, 4 TRIAC, 4 RELAY 6 AO, 4 TRIAC, 4 RELAY
<br /> CVA 2 14500030-050 HONEYWELL 499 Ohm, 1/2W PRECISION RESISTOR CVA 2 14500030-050 HONEYWELL 499 Ohm, 1/2W PRECISION RESISTOR
<br /> FUSE I NOT KNOWN BUSS 24VAC, 4AMP FUSE 1 NOT KNOWN BUSS 24VAC, 4AMP
<br /> 1 NOT KNOWN BUSS 24VDC, 3AMP 1 NOT KNOWN BUSS 24VDC, 3AMP
<br /> 2 BAF111SDU IDEC FUSE HOLDER, W/LED 2 BAF111SDU IDEC FUSE HOLDER,W/LED
<br /> TBX 7 BA111TU2 IDEC SMALL TERMINAL BLOCK, 3 POLE TBX 8 BA111TU2 IDEC SMALL TERMINAL BLOCK, 3 POLE
<br /> TBS 4 BNL-6 IDEC TERMINAL DIN RAIL STOP TBS 4 BNL-6 IDEC TERMINAL DIN RAIL STOP
<br /> srw ROMM fff NTWVED DARE sw AWE ACCEPTABILITY a' IIm.24 ATE ""`PANEL EMCS-40-023- CPI-CPI RL5-5 and RL5-6 "" "`" '°" g"e0L "°` 11.25.24
<br /> 40-023 BUILDING-HBL EXPANSION-POS 4,5,6 USB-027992 HWL Vs 11.25.24 �( ."!'a TM 11.25.24 CONTROLLER LAYOUT 1/0 SUMMARY ,
<br /> AppRpyEp BY pEpr. p�h EW SB „ r24 ""E 40-023 BUILDING E932-2 F
<br /> SP 11.=4 BUILDING 40-023
<br /> in no. aarr N0.
<br /> W0917-
<br /> ELECTRICAL MASTER EVEREFT,WA awa"0 40-023-E932-2F