<br /> C MICROMATIC° STANDARD
<br /> � � RESPONSE PENDENT
<br /> SPRINKLER VK102 (K5.6)
<br /> -NlKjw4j
<br /> The Viking Corporation,210 N Industrial Park Drive, Hastings MI 49058
<br /> Telephone:269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email:techsvcs@vikingcorp.com
<br /> Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
<br /> Approval Chart 1 (UL) Temperature KEY
<br /> Micromatic®Standard Response Pendent Sprinkler VK102 qFinish
<br /> Escutcheon(:fapplicable)
<br /> Maximum 175 PSI(12 bar)WWP
<br /> Sprinkler Thread Size Nominal Overall Length Listings and Approvals;
<br /> Base Part SIN K-Factor (Refer also to UL Design Criteria.)
<br /> Number' NPT BSP U.S. metric2 Inches mm cULus° I VdS LPCB C E e '
<br /> Standard Orifice
<br /> 12987 VK102 1/2" 15 mm 5.6 80.6 2-1/4" 57 1 Al,B4,B1Y,C5,D3,E6,G6Z A2 A2,B4,B2Y F2,G2Y F2X9
<br /> 12989 VK102 15 mm 5.6 80.6 2-1/4" 57 A1,B4,B1Y,C5,133,E6,G6Z A2 A2,B4,B2Y F2,G2Y F2X9
<br /> 19776 VK102 1/2" 5.6 80.6 2-1/4" 57 - E7
<br /> 20229 VK102 15 mm 5.6 80.6 2-1/4" 57 - E7
<br /> NOTICEOffice)
<br /> 10139 VK102 1/2" 15 mm 5.6 80.6 2-1/4" 57 Al,B4,B1Y,C5,D3,E6,G6Z
<br /> 10173 VK102 15 mm 5.6 80.6 2-1/4" 57 Al,B4,B1Y,C5,D3,E6,G6Z A2 A2,B4,62Y F2W9
<br /> 18020 VK102 1/2" 15 mm 5.6 80.6 2-1/4" 57 Al,B4,B1Y,C5,D3,E6,G6Z A2 A2,B4,B2Y F2,G2X F2W9
<br /> Approved Temperature Ratings
<br /> A- 135 OF (57 °C), 155 OF (68 °C), 175 OF(79
<br /> °C), 200 OF (93 °C), 286 OF (141 °C), and 360 Approved Finishes
<br /> OF(182°C) 1 - Brass, Chrome, White Polyester56, and Black
<br /> B- 135 OF(57°C), 155 OF(68 °C), 175 OF (79 Polyester5,6 Approved Escutcheons
<br /> °C),and 200 OF(93°C) 2-Brass,Chrome,White Polyesters,and Black Polyesters X - Recessed with the Viking Micromatic° Model
<br /> C-286 OF(141 °C) 3-Brass and Chrome E-1, E-2,or E-3 Recessed Escutcheon
<br /> D-500 OF(260°C)7 4-Wax-Coated Brass and Wax Over Polyester' Y - Standard surface-mounted escutcheon or re-
<br /> cessed with the Viking Micromatic Model E-1, E-2,
<br /> E- 155 OF(68°C), 175 OF(79 °C),200 OF (93 5-High Temperature 200 OF(93°C)Wax Coating(corro- or E-3 Recessed Escutcheon
<br /> °C), 286 OF(141 °C), 360 OF(182°C),and 500 sion resistant);maximum ambient temperature allowed at Z - Standard surface-mounted escutcheon or re-
<br /> OF(260°C)7 ceiling=150 OF(65°C) cessed with the Viking Micromatic®Model E-1
<br /> F- 155 OF(68°C), 175 OF (79°C), 200 OF (93 6-ENT5
<br /> °C),286 OF(141 °C), and 360 OF(182°C) 7-Chrome
<br /> G-155 OF(68°C), 175 OF(79°C), and 200 OF
<br /> (93°C)
<br /> Footnotes
<br /> Base part number is shown.For complete part number,refer to Viking's current price schedule.
<br /> z Metric K-factor shown is for use when pressure is measured in bar.When pressure is measured in kPa,divide the metric K-factor shown by 10.0.
<br /> 'This table shows the listings and approvals available at the time of printing.Check with the manufacturer for any additional approvals.
<br /> 4 Listed by Underwriters Laboratories Inc.for use in the U.S.and Canada.
<br /> 5 cULus Listed as corrosion resistant.
<br /> 6 Other colors are available on request with the same Listings and Approvals as the standard colors.
<br /> 'Sprinklers of Ultra-High temperature rating are intended for use inside ovens,dryers,or similar enclosures with normal operating temperatures above 300°F(149°C).Where the ambient temperature around
<br /> the Ultra-High temperature rated sprinkler is significantly reduced below 300 OF(149°C),the response time of the Ultra-High temperature rated sprinkler may be severely retarded.
<br /> 9 CE Certified,Standard EN 12259-1,EC-certificate of constancy of performance 0832-CPR-S0021.
<br /> 'MED Certified,Standard EN 12259-1:EC-certificate 0832-MED-1003.
<br /> DESIGN CRITERIA- UL
<br /> (Also refer to Approval Chart 1.
<br /> 7thelatest
<br /> Reguirements:
<br /> omatic®Standard Response Pendent Sprinkler VK102 is cULus Listed as indicated in Approval Chart 1 for installation in accordance
<br /> dition of NFPA 13 for standard spray sprinklers.
<br /> • Designed for use in Light,Ordinary,and Extra Hazard occupancies.
<br /> • The sprinkler installation rules contained in NFPA 13 for standard spray pendent sprinklers must be followed.
<br /> IMPORTANT.Always refer to Bulletin Form No. F 091699-Care and Handling of Sprinklers.Also refer to Form No. F 080614
<br /> for general care, installation,and maintenance information.Viking sprinklers are to be installed in accordance with the latest
<br /> edition of Viking technical data, the appropriate standards of NFPA, LPCB,APSAD, VdS or other similar organizations, and
<br /> also with the provisions of governmental codes, ordinances, and standards,whenever applicable.
<br /> Form No. F_031414 19.02.21 Rev 19.1