GENERAL CONSTRUCTION NOTES smartlink
<br /> 1. FOR THE PURPOSE CONTRACTOR
<br /> CONSTRUCTION DRAWINGS,ME FOLLOWING DEFINITIONS SHALL APPLY: 36. SUBCON TRACTORS SHALL BE RESPONSIBLE FOR OBTAINING ALL PERMITS AND INSPECTIONS R RMOUIREDEFOR CONSTRUCTION.IF
<br /> CONTRACTOR(CONSTRUCTION) SUBCONTRACTOR CANNOT OBTAIN A PERMIT THEY MUST NOTIFY THE GENERAL CONTRACT. IMMEDIATELY.
<br /> OWNERUSCONTRAAT&FICLOR 37. SUBCONTRACTOR SHALL REMOVE ALL TRASH AND DEBRIS FROM THE SITE ON A DAILY BASIS.
<br /> OEM-ORIGINAL EQUIPMENT MANUFACTURE 360 CIVIC DRIVE,SUITE C
<br /> 38. INFORMATION SHOW ON THESE DRAWINGS WAS OBTAINED FROM SITE VISITS AND/DR DRAWINGS PROVIDED BY THE SITE OWNER. PLEASANT HILL,CA 94523
<br /> 2. ALL SIZE WORK SHALL BE COMPLETED As INDICATED ON THE DRAWINGS AND AT&T PROJECT SPECIFICATIONS. CONTRACTORS SHALL NOTIFY TIE ENGINEER OF ANY DISCREPANCIES PRIOR TO ORDERING MATERIAL OR PROCEEDING WITH
<br /> CONSTRUCTION.
<br /> 3. GENERAL CONTRACTOR ANDED SUBCONTRACTOR SHALL PIRO THE SITE AND SHALL CONTRACTOR
<br /> HIMSELF SUBCO WITH ALL CONDITIONS
<br /> AFFECTING M PROPOSED WORK SHALL MAKE PROVISIONS GENERAL CONTRACTOR AND SUBCONTRACTOR SHALL BE 39. No WHITE STHOBIC uGHM ARE PERMITTED.LIGHTING IF REQUIRED,WILL MEET FM STANDARDS AND REOUIREMENTs.
<br /> THAT THE WORK MAY BE ACCOMPLISHED
<br /> THE ENGINEERSSW PRIOR TO PROCEEDING
<br /> WITH
<br /> OF WORK. ,ANY 0 N5.AND CONFIRMING ALL COAXIAL CABLE INSTALLATIONS TO FOLLOW MANUFACTURER'S INSTRUCTIONS AND RECOMMENDATIONS
<br /> RESPONSIBLE FOR FAMILIARIZING HIMSELF WITH ALL CONTRACT DOCUMENTS,FIELD CONDITIONS.DIMENSIONS.
<br /> MPLIE ED SHOWN LNG WTH CONSTRUCTION DISCREPANCIES SHALL BE 4a
<br /> BROUGHT TO THE ATTENTION 0TOR TO THE COMMENCEMENTAT&T
<br /> 4, DANCE WITH ALL APPLICABLE CODES,REGULATIONS,AND 41. 0 NOISE.SMOKE.OUST.ODOR.OR VIBRATIONS WILL RESULT FROM THIS FACILITY.
<br /> ORDINPNCES.GENERAL CONTRACTOR SHALL ISSUE BE
<br /> APPROPRIATE NOTICES AND COMPLY WITH ALL LAWS,ORDINANCES.RULES, (DELETE THIS NOTE IF THE SITE WILL HAVE A GENERATOR)
<br /> REGULATIONS.AND LAWFUL ORDERS OF ANY PUBLIC AUTHORITY REGANDING ME PERFORMANCE OF WORK, 42. NO ADDITIONAL PARKING TO BE PROPOSED.EXISTING ACCESS AND PARKING TO REMAIN. TobWy-p.
<br /> 5. ALL WORK CARRIED OUT SHALL COMPLY WITH ALL APPLICABLE MUNICIPAL AND UTILITY COMPANY SPECIFICATIONS AND LOGAL (REVISE THIS NOTE ACCORDING TO ME SITE CONFIGURATION)
<br /> JURISDICTIONAL CODES,ORDINANCES,AND APPLICABLE REGUL 43ATIONS. PI S PROPOSED AT THIS SITE. 2700 W. WATT AVE.
<br /> 6. UNLESS NOTED OTHERWISE,THE WORK SHALL INCLUDE FURNISHING MATERIALS,EQUIPMENT,APPURTENANCES,AND LABOR (REVISE THIS NOTEACCORDNG TO ME SITE CONBGUIVTON) SACRAMENTO,CA 95821
<br /> NECESSARY TO COMPLETE ALL INSTALLATIONS AS INDICATED ON ME DRAWINGS,
<br /> 7. PLANS ARE NOT TO BE SCALED.THESE PLANS ARE INTENDED TO BE A DIAGRAMMATIC OUTLINE ONLY UNLESS OTHERWISE NOTED. l
<br /> DIMENSIONS SHOWN ARE TO FINISH SURFACES UNLESS OTHERWISE NOTED.SPACING BETWEEN EQUIPMENT S THE MINIMUM
<br /> GROUNDING NOTES. Fuller
<br /> MEUCOEN CAL DOCUMENTS.
<br /> THEREFORE,SUBCS CRITICAL S FIELD VERIFY DIMENSIONS,SHOULD MERE NI ANY NUESTIONS TIE ENGINEER
<br /> EER M Ci 'V��I\1L_
<br /> OR OR TO PROCEEDING WITHTHE WORK.DETAILS AREAIMERGED TO SHRESPONSOWNBLE DEFORSIGN TINTENT MODIFICATIONS MAY BE REQUIRED To
<br /> TO 1. ALL GROUND ELECTRODE SYSTEMS(INCLUDING TELECOMMUNICATION,RADIO,LIGHTNING PROTECTION,AND AC POWER DESIGN DEVELOP CONSTRUCT
<br /> SLAT JOB DIMENSIONS OR CONDITIONS AND SUCH MODIFICATIONS SHALL BE INCLUDED AS PART OF WORK AND PREPARED BY THE SHALL BE BONGED TOGETHER BELOW OR BY TWO OR MORE COPPER-DING CONDUCTORS IN ACCORDANCE
<br /> ENGINEER PRIOR TO PROCEEDING WITH WORK.
<br /> WITH THE 1100 E.WOODFIELD ROAD,SURE 5D0
<br /> 8, ME SUBCONTRACTOR SHALL INSTALL ALL EQUIPMENT AND MATERIALS IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS SCHAUMBURG,IWNIOIS 60173
<br /> UNLESS SPECIFICALLY STATED OTHERWISE. TEL:847-908-R400
<br /> 2. ME SUBCONTRACTOR SHALL PERFORM IEEE FALL-OF-POIENIAL RESISTANCE TO EARTH TESTING(PER IEEE 1- COA#4143
<br /> 9. IF THE SPECIFIED EQUIPMENT CANNOT BE INSTALLED AS SHOWN ON THESE DRAWINGS,THE SUBCONTRACTOR SHALL PROPOSE AN
<br /> ALTERNATIVE INSTALLATION SPACE FOR APPROVAL BY THE ENGINEER PRIOR TO PROCEEDING. AND 81) SUB FOR GROUND ELECTRODE SYSTEMS.THE CONTRACTOR SHALL FURNISH AND INSTALL SUPPLEMENTAL www.fuRerton-us.mm
<br /> 10. GENERAL CONTACTOR SHALL BE RESPONSIBLE FOR THE SAFETY OF WORK AREA,ADJACENT AR EAR AND BUILDING OCCUPANTS GROUND ELECTRODES AS NEEDED TO CHIEVE A LEST RESULT OF 5 OHMS Oft LESS. REV DATE DESCRIPTION BY
<br /> MAT ARE LIKELY TO BE AFFECTED BY THE WORK UNDER THIS CONTRACT.WORK SHALL CONFIRM TO ALL OSHA REQUIREMENTS 3. ME SUBCONTRACTOR IS RESPONSIBLE FOR PROPERLY SEQUENCING GROUNDING AND UNDERGROUND CONDUIT
<br /> AND THE LOCAL JURISDICTION. INSTALLATION AS TO PREVENT ANY LOSS OF CONTINUITY IN THE GROUNDING SYSTEM OR DAMAGE TO THE CONDUIT A 4/19/24 90%REVIEW SJ
<br /> 11. GENERAL CONTRACTOR SHALL COORDINATE WORK AND SCHEDULE WORK ACTIVITIES WITH OTHER DISCIPLINES. &PROVIDE TESTING RESULTS. Y 4 30 29 REVISION SJ
<br /> 12. ERECTION SHALL BE GONE IN A WORKMANLIKE MANNER BY COMPETENT EXPERIENCED WORKMAN IN ACCORDANCE WITH APPLICABLE 4. METAL CONDUIT AND MAY SHALL BE GROUNDED AND MADE ELECTRICALLY CONTINUOUS WITH LISTED CODING C 5 16 24 SJ 95%REVIEW
<br /> CODES AND THE BEST ACCEPTED PRACTICE.ALL MEMBERS SHALL BE LAID PLUMB AND TRUE AS INDICATED ON ME DRAWINGS. FITTINGS OR BY BONDING ACROSS ME DISCONTINUITY WITH#6 AWG COPPER WIRE ILL APPROVED GROUNDING TYPE0 2 18 24 FINAL SJ
<br /> 13, SEAL PENETRATIONS THROUGH FIRE RATED AREAS WITH UL LISTED MATERIALS APPROVED BY LOCAL JURISDICTION.SUBCONTRACTOR CONDUIT CLAMPS.
<br /> SHALL KEEP AREA CLEAN,HAZARD FREE,AND DISPOSE OF ALL DEBRIS, 5. METAL RACEWAY SHALL NOT BE USED AS THE NEC REQUIRED EQUIPMENT GROUND CONDUCTOR.STRANDED COPPER
<br /> 14 WORK PREVIOUSLY COMPLETED IS REPRESENTED BY LIGHT SHADED LINES AND NOTES.ME SCOPE OF WORK FOR THIS PROJECT IS CONDUCTORS WITH ACCORDANCE WITH ME NEC,SHALL BE FURNISHED AND INSTALLED I HEREBY CERTIFY THAT THESE DRAWINGS WERE
<br /> DARK LINESANN NOTES.SUBCONTRACTORS GENERAL CONTRACTOR OF ANY EXISTING S EQUIPMENT. PREPARED BY ME OR UNDER MY DIRECT
<br /> CONDRIONSETTIV.T_ATE FROMTHE DRAWINGS PRIOR TO BEGINNING CONSTRUCTIONTHE 6. EACH BTS CABINET FRAIME SHALL BE DIRECTLY CgJNECIED i0 THE MASTER GROUND BAR WITH GREEN INSULATED SUPERVISION AND CONTROL,AND TO THE BEST
<br /> OF MY KNOWLEDGE AND BELIEF COMPLY WITH
<br /> 15. SUBCONTRACTOR SHALL PROVIDE WRITTEN NOTICE TO THE CONSTRUCTION MANAGER 48 HOURS PRIOR TO COMMENCEMENT OF SUPPLEMENTAL EQUIPMENT GROUND WIRES,p6 AK STRANDED COPPER OR LARGER FOR INDOM BTS:q2 AWG THE REQUIREMENTS OF ALL APPLICABLE CODES,
<br /> WORK.
<br /> STRANDED COPPER FOR OUTDOOR BTS.
<br /> 18 SUBCONTFACTOR SHALLPROTECT IMPROVEMENTS,PAVEMENTS, LANDSCAPING AND STRUCTURES.ANY DAMAGED 7 CONNECTIONS TO ME GROUND BUS SHALL NOT BE DOUBLED UP OR STACKED.BACK TO BACK CON
<br /> PART SHALL BE REPAIRED AT-CONTRACTOR'S EXPENSE To
<br /> THE SATISFACBON OF THE OWNER. OPPOSITE SIDES OF THE GROUND BUS ARE PERMITTED. NECIONS ON DEL W S
<br /> 17. ME SUBCONTRACTOR SHALL CONTACT UTILITY LOCATING SERVICES PRIOR TO THE START OF CONSTRUCTION. B. ALL EXTERIOR GROUND CONDUCTORS BETWEEN EUIPMENT/GROUND BARS AND THE GROUND RING.SHALL BE p2 Q�OF WASHA O�T�
<br /> 18. GENERAL CONTRACTOR SHALL COORDINATE AND MAINTAIN ACCESS FOR ALL TRADES AND SUBCONTRACTORS TO ME SITE AND/OR AWG SOLID TINNED COPPER UNLESS OTHERWISE INDICATED. F,P TO
<br /> BUILDING. 9. ALUMINUM CONDUCTOR OR COPPER CLAD STEEL CONDUCTOR SHALL NOT BE USED FOR GROUNDING CONNECTIONS.
<br /> 19. ME GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR SECURTY OF THE SITE FOR THE DURATION OF CONSTRUCTION UNTIL JOB 10. USE OF 90'BENDS IN ME PROTECTION GROUNDING CONDUCTORS SHALL BE AVOIDED MEN 45"BENDS CAN BE R
<br /> COMPLETION,
<br /> ADEQUATELY SUPPORTED.
<br /> 20. M AL CONTRACTOR SHALL MAINTAIN IN GOOD CONDITION ONE COMPLETE SET OF PLANS WITH ALL REVISIONS,ADDENDA, 1. EXOTHERMIC WELDS SHALL BE USED FOR ALL GROUNDING CONNECTIONS BELOW GRADE. 52527
<br /> AND CHANGE ORDERS ON ME PREMISES AT ALL TIMES. 12. ALL GROUND CONNECTIONS ABOVE GRADE(INTERIOR&EXTERIOR)SHALL BE FORMED USING HIGH PRESS CRIMPS. r(i1J_L-E.•r•4"Y
<br /> 21. ME GENERAL CONTRACTOR R AND SUUBC SUBCOBE NTRACTOR
<br /> RIN SHALL
<br /> FEETROVID OF TRANRRTABILLE FIRE 7p-NGUISLL HERS
<br /> A RATING
<br /> HERE OF NOT
<br /> WORKLESS
<br /> 13. COMPRESSION GROUND CONNECTIONS MAY BE REPLACED BY EXOTHERMIC WELD CONNECTIONS. SS/ AL
<br /> BEING
<br /> MAN COMPLETED DURING CONSTRUCTION. 14, ICE BRIDGE BONDING CONDUCTORS SHALL BE EXOTHERMICALLY BONDED OR BOLTED TO ME BRIDGE AND THE
<br /> 22, ALL EXISTING ACTIVE SEWER,WATER,GAS,ELECTRIC,AND OTHER UTILITIES SHALL BE PROTECTED AT ALL TIMES,AND WHERE TOWER GROUND BAR.
<br /> REQUIRED FOR THE PROPER EXECUTION OF THE WORK.SHALL BE RELOCATED AS DIRECTED BY THE ENGINEER.EXTREME CAUTION 15, APPROVED ANTIOXIDANT COATINGS(I.E.CONDUCIVE GEL OR PASIE)SHALL BE USED ON ALL COMPRESSION AND
<br /> SHOULD BE USED BY THE SUBCONTRACTOR WHEN EXCAVATING OR DRILLING PIERS AROUND OR NEAR UTILITIES.SUBCONTRACTOR BOLTED GROUND CONNECTIONS. SITE NAME
<br /> SHALL PROVIDE SAFETY TRNNING FOR THE WORKING CREW.THIS SHALL INCLUDE BUT NOT BE LIMITED M A)FALL PROTECTION,B)
<br /> CONFINED SPACE,C)ELECTRICAL SAFETY,AND M TRENCHING&EXCAVATION. 16, ALL EXTERIOR GROUND CONNECTIONS SHALL BE COATED WITH A CORROSION RESISTANT MATERIAL.
<br /> ALL EX SHALL IBOCTIVE SEWERR,WATER,PLUGGED ORRO.HAND O DISCONNECTED HI POINTS WHICH WILL
<br /> THE EXECUTION OF THE 17. MISCELLANEOUS ELECTRICAL AND NON-ELECTRICAL METAL BOXES.FRAMES AND SJPPORTS SHALL BE BONDED TO EVERETT WALNUT
<br /> 23. OTHER DISCONNECTED
<br /> WHICH INTERFERE WIT ACCORDANCE W1M TH NEC.
<br /> NOT INTERFERE WITH THE ME GROUND RING,IN
<br /> EX
<br /> AXFOUTIO OF THE WORK,AS ND/OR FOCAL UTILITIES. DIRECTED BY ME RESPONSIBLE ENGINEER,AND SUBJECT TO THE APPROVAL OF THE OMER 18. BOND ALL METALLIC OBJECTS WITHIN 6 FT OF MAIN GROUND WRES WITH 1-#2 AWG TIN-PLATED COPPER GROUND
<br /> CONDUCTOR.
<br /> 2 D BY ME TOWER,EQUIPMENT OR DRIVEWAY, 19. GROUND CONDUCTORS USED IN THE FACILITY GROUND AND LIGHTNING PROTECTION SYSTEMS SHALL NOT BE ROUTED SITE NUMBER:
<br /> 4 SHALL BE GRADED
<br /> EToWA UNIFORM SLOPE.AND STABILIZEDTO PREVENT T EROSION,ER THROUGH METALLIC OBJECTS THAT FORM A RING AROUND THE CONDUCTOR,SUCH AS METALLIC CONDUITS,METAL
<br /> 25. SUBCONTRACTOR SHALL MINIMIZE DISTURBANCE TO ME EXISTING SITE DURING CONSTRUCTION.EROSION CONTROL MEASURES,IF SUPPORT CLIPS OR SLEEVES THROUGH WALLS OR FLOORS.WHEN IT IS REWIRED TO BE HOUSED IN CONDUIT TO
<br /> RED RED SEDIMENT DURING CONTROL. MEET SHALL BE IN CONFORMANCE WITH THE FEDERAL AND LOCAL JURISOICIION FOR EROSION AND MEET CODE REQUIREMENTS OR LOCAL CONDITIONS,NONMETALLIC MATERIAL SUCH AS PVC PLASTIC CONDUIT SHALL
<br /> WA2821
<br /> 2 LL NR EMBANKMENT MATERIAL s BE PLACED ON FROZEN GROUNDING.FROZEN MATERIALS,SNOW OR ICE SHALL
<br /> BE USED.WHERE USE OF METAL CONDUIT IS UNAVGDABLE(E.G.NON-METALLIC CONDUIT PROHIBITED BY LOCAL
<br /> PLACED IN
<br /> ANY FILL OR EMBANKMENT. CODE)ME GROUND CONDUCTOR SHALL BE BONGED i0 EACH END OF ME METAL CONDUIT.
<br /> 27. ME SUBGRADE SHALL BE BROUGHT TO A SMOOTH UNIFORM GRADE AND COMPACTED TO 95 PERCENT STANDARD PROCTOR DENSITY SITE ADDRESS
<br /> UNDER PAVEMENT AND STRUCTURES AND 80 PERCENT STANDARD PROCTOR DENSITY IN OPEN SPACE. ALL TRENCHES IN PUBLIC
<br /> RIGHT OF WAY SHALL BE BACKFlLLED WITH FLOWABLE FILL OR OTHER MATERIAL PRE-APPROVED BY THE LOCAL JURISDICTION.
<br /> 3200 20TH STREET
<br /> 28. ALL NECESSARY RUBBISH,STUMPS.DEBRIS,STICKS,STONES,ADD OTHER REVISE SHALL BE REMOVED FROM THE SITE AND EVERVERETT,WA 98201
<br /> DISPOSED OF IN A LAWFUL MANNER.
<br /> 29. ALL BROCHURES,OPERATING AND MAINTENANCE MANUALS,CATALOGS,SHOP DRAWINGS,AND OTHER DOCUMENTS SHALL BE TURNED
<br /> OVER TO THE GENERAL CONTRACTOR AT COMPLETION OF CONSTRUCTION AND PRIOR i0 PAYMENT.
<br /> 30. SUBCONTRACTOR SHALL SUBMIT A COMPLETE SET OF AS-BUILT REDLINES TO THE GENERAL CONTRACTOR UPON COMPLETION OF SHEET NAME
<br /> PROJECT AND PRIOR TO FINAL PAYMENT.
<br /> 31. SUBCONTRACTOR SHALL LEAVE PREMISES IN A CLEAN CONDITION.
<br /> 32. ME PROPOSED FACIUTY WILL BE UNMANNED AND DOES NOT REQUIRE POTABLE WATER OR SEWER SERVICE.AND IS NOT FOR GENERAL NOTES
<br /> HUMAN HABITAT(NO HANDICAP ACCESS REQUIRED).
<br /> 33. OCCUPANCY IB LIMITED TO PERIODIC MAINTENANCE AND INSPECTION.APPROXIMATELY 2 TIMES PER MONTH,BY AT&T TECHNICIANS.
<br /> 34. NO OUTDOOR STORAGE OR SOLID WASTE CONTAINERS ARE PROPOSED. SHEET NUMBER
<br /> 35. ALL MATERIAL SHALL BE FURNISHED AND WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE LATEST REVISION AT&T MOBILITY
<br /> DNG EANDARD`TECHNICAL SPECIE ION OR C NSTRUOD N OF GRM/MRS WIRELESS TITER AND'TECHNICAL
<br /> DRAWINGS S-ALL GOVERN, G N-1
<br /> SPECIFICATION FOR FACILITY GROUNDING-.SPECIFICATION
<br /> OF A CONFLICT BETWEEN THE CONSTRUCION(SPECIFICATION AND THE
<br /> OFAPROJECT#2024.0005.0016