i <br /> 6" LAT - SE1S IC BRACE C LCULATIO S <br /> Seismic Project 4" Lateral Brace Name 6" Lat <br /> Standard NFPA 13-2016 Drawing Reference Lat <br /> Brace Type Lateral Approval Agency UL Listed <br /> STRUCTURE INFORMATION SEISMIC BRACE ATTACHMENTS <br /> Structure Cracked Concrete Model Size Load Rating <br /> Substrate Normal Weight Cracked Concrete-4000 psi Swivel Att. AF075 1 NPS x 1/2" 1,425 lbf. <br /> BRACE INFORMATION Pipe Att. AF035 6 NPS x 1 NPS 1,955 lbf. <br /> Brace Member 1 NPS Sch 40 See Appendix A for alternate seismic brace attachments. <br /> Brace Length Max 7 ft 0 in All seismic brace attachments manufactured by ASC Engineered Solutions. <br /> Brace Angle 45° - 59° I <br /> Least Radius of Gyration 0.421 in. <br /> Ur Ratio Max 200 Wedge Anchor Structure: <br /> Max Horizontal Load 1,310 lbf. Concrete(By Others) <br /> Fig.AF075 <br /> FASTENER INFORMATION <br /> Fastener Name Wedge Anchor per NFPA = <br /> 13-2016 • <br /> Schedule 40 Service <br /> Brace Pipe Pipe <br /> Fastener Orientation B <br /> Fig.AF035 <br /> Fastener Diameter 1/2 in. <br /> Nominal Embedment 3 5/8 in. <br /> Max Horizontal Load 607 lbf. Net Vertical Reaction Forces do not need to be addressed per NFPA 13-2016. <br /> SPRINKLER SYSTEM LOAD CALCULATION (FPw = CP*Wr) <br /> Cp = 0.618 <br /> Qty Line Description Pipe Diameter/Type Length Weight per ft Weight <br /> 1 Main Braced Pipe 6 NPS Steel Sch 10 35.00 ft. 23.03 lb/ft. 806.05 lb. <br /> Weakest Main Size Spacing Max Fpw Total System Weight 806.05 lb. <br /> 6 NPS Steel Sch 10 35 ft. 2,269 lbf. System Design Weight (Wp) 927 lb. <br /> Horizontal Seismic Load (Fpw) 573 lbf. <br /> 3 <br />