Laserfiche WebLink
Wiring & Configuration Alarm,trouble,and supervisory relay1T133) <br /> Notification appliance circuits(TB2) The trouble relay is normally-open,held closed,and opens on any <br /> trouble event or when the panel is de-energized.The supervisory <br /> The i064 comes equipped with two notification appliance circuits. relay is normally-open,and closes on any supervisory event.The <br /> Each circuit can be individually configured for continuous,temporal, alarm relay changes over on any alarm event. <br /> synchronized,and coded output. <br /> Relay specifications <br /> Circuit Specifications Alarm Trouble Supervisory <br /> Circuit Type 2 Class B,Class A optional when Class A card is installed. Type Form C Form A <br /> Each circuit is 2.5 amps. Voltage 24 VDC at 1 A resistive 24 VDC at 1 A resistive <br /> Voltage 24 VFWR <br /> Current 3.75A total(115/230 60hz) Relay circuits can only be connected to power-limited sources. <br /> 3.0A total(230v 50hz) <br /> 2.5 A max per circuit <br /> Impedance 26 Q total,0.35 NF max Auxiliary&Smoke power outputs(TB3) <br /> EOLR 15 K Q.1/2 W The control panel provides two auxiliary power outputs which can <br /> be used for powering ancillary equipment such as remote an- <br /> nunciators and two wire smoke detectors. Aux 2 can be software <br /> Class B wiring selected to operate continuous.The circuit is supervised for shorts <br /> NAC1 + + and grounds. <br /> 5 NAC1+ _ Note:For a complete list of devices that can be connected to this <br /> 0 NAC2- + + EorR circuit,refer to the i0 Series compatibility list(p/n 3101064). <br /> NAC2+ _ _ <br /> Circuit specifications <br /> TB <br /> Marking indicates output signal polarity when the circuit is active. Circuit voltage range 21.9 to 28.3 V <br /> Polarity reverses when the circuit is not active.Wire notification Resettable circuit 24 VDC nominal at 500 mA <br /> appliances accordingly.Notification appliance polarity shown in (Aux power 2) <br /> active state. Continuous circuit 24 VDC nominal at 500 mA.Use this circuit for <br /> (Aux power 1) powering two-wire smoke detectors. <br /> Note:Any current above 0.5 amp connected to both Aux 1 and 2 will reduce the total <br /> Signature Device loop available NAC power by that amount. <br /> The system provides one device loop circuit that can be used with <br /> any mix of Signature Series detectors and modules.The loop circuit <br /> is supervised for opens,shorts,and grounds. Annunciator loop(T64) <br /> Circuit Specifications The control panel provides a connection for up to eight serially <br /> Device loops 1 loop Class B,Class A optional when Class A card is driven and supervised remote annunciators. <br /> installed.Supporting up to 64 device addresses. <br /> Communication Maximum 20 V peek-to-peek Circuit specifications <br /> line voltage Device loops Class B(Style Y)or Class A(Style Z) <br /> Circuit current 0.5 A max Circuit voltage 2.55 V <br /> Circuit impedance 660 total,0.5 NF,max Circuit current 30 mA max <br /> Isolators 64 maximum Circuit impedance Up to 8 annunciators or 4000 feet <br /> Class B wiring Class B Class A <br /> Channel Channel Channel1 Channe12 <br /> Loop 1 SEC + Data Line (D (D IS IS TB4 TB4 <br /> Loop 1 PRI _ + + Annunciator Annunciator <br /> + Q CH1(+)IN CH1(+)IN <br /> Loop Loop CH1(—)IN CH1(—)IN <br /> Loop card device device <br /> CH2(+)IN CH2(+)IN <br /> Class A wiring (S)CH2(—)IN CH2(—)IN <br /> Loop 1 SEC <br /> + <br /> + + <br /> Loop 1 PRI <br /> Pj�Loop Loop <br /> Loop card Data Line device device <br /> Data Sheet 85005-0131 Issue 3 <br /> Not to be used for installation purposes.Page 4 of 8 <br />