Laserfiche WebLink
IIISummary Of Outflowing Devices Job Number:22-3719 <br /> Report Description:Ordinary Group II(1 B1 L01) <br /> Actual Flow Minimum Flow K-Factor Pressure <br /> Device pm pm K psi <br /> Hydrant 10 64.00 64.00 0 71.515 <br /> Sprinkler 1248 28.47 25.85 5.6 25.853 <br /> Sprinkler 1250 27.95 25.85 5.6 24.915 <br /> Sprinkler 1260 28.15 25.85 5.6 25.261 <br /> Sprinkler 1261 28.04 25.85 5.6 25.064 <br /> Sprinkler 1264 33.50 25.85 5.6 35.780 <br /> Sprinkler 1268 33.74 25.85 5.6 36.299 <br /> Sprinkler 1269 25.93 25.85 5.6 21.446 <br /> y Sprinkler 1270 25.85 25.85 5.6 21.308 <br /> Sprinkler 1281 34.93 25.85 5.6 38.902 <br /> Sprinkler 1282 32.32 25.85 5.6 33.305 <br /> Sprinkler 1283 1 32.24 25.85 5.6 33.147 <br /> c> Most Demanding Sprinkler Data <br /> ©M.E.P.CAD AutoSPRINK 2023 08.1.33.0 4/4/2024 9:43:18AM Page 3 <br />