10 .03 <br /> FLOW DATA <br /> Frictional Resistance <br /> Fitting Size Equivalent Feet/meters of Straight Pipe <br /> Actual Straight Tee <br /> Nominal Outside No.002 <br /> Diameter Diameter 90'Elbow 45'Elbow <br /> Inches/mm Inches/mm No.001 No.003 Branch Run <br /> 2 2.375 3.5 1.8 8.5 3.5 <br /> 50 60,3 1,1 0,5 2,6 1,1 <br /> 21/2 2.875 4.3 2.2 10.8 4.3 <br /> 65 73,0 1,3 0,7 3,3 1,3 <br /> 76,1 mm 3.000 4.5 2.3 11.0 4.5 <br /> 76,1 1,4 0,7 3,4 1,4 <br /> 3 3.500 5.0 2.6 13.0 5.0 <br /> 80 88,9 1,5 0,8 4,0 1,5 <br /> 4 4.500 6.8 3.4 16.0 6.8 <br /> 100 114,3 2,1 1,0 4,9 2,1 <br /> 5 5.563 8.5 4.2 21.0 8.5 <br /> 125 141,3 2,6 1,3 6,4 2,6 <br /> 6 6.625 10.0 5.0 25.0 10.0 <br /> 150 168,3 3,0 1,5 7,6 3,0 <br /> 8 8.625 13.0 5.0 33.0 13.0 <br /> 200 219,1 4,0 1,5 10,1 4,0 <br /> t The flow data listed is based upon the pressure drop of Schedule 40 pipe. <br /> MATERIAL SPECIFICATIONS <br /> Fitting: Ductile iron conforming to ASTM A-536,grade 65-45-12 <br /> Fitting Coating:Orange enamel <br /> • Optional: Hot dipped galvanized <br /> This product sha0 be manufactured by Victauhc Company.All products to be installed in accordance with current Victaulic insta0ation/assembly instructions. <br /> Victaulic reserves the right to change product specifications,designs and standard equipment without notice and without incurring obligations. <br /> 2 Fire Lock®Fittings <br />