Laserfiche WebLink
Static city water pressure 40 psi <br /> Churn suction pressure 40 psi Churn discharge pressure 165 psi <br /> Was 300 GPM flow conducted? Yes ® No ❑ <br /> Hose size: 2 1/2 inch Tip size: 2 1/2 inch Hose length: 50 ft <br /> Pitot reading: 12/13/13/14 GPM: 2509 <br /> Was pump run for 10 minutes flowing? Yes ® No ❑ <br /> Were all fire pumps tested? Yes ® No ❑ <br /> Flow Chart <br /> NO.&SIZE PUMP PRESSURE PITOT FLOW RPM VOLTS AMPS <br /> OF NOZZELS PRESSURE <br /> DISCHG. SUCT. NET <br /> CHURN 165 40 125 0 0 1768 <br /> 4-21/Z"HM 127 28 99 12/13/13/14 2431 1767 <br /> 5-21/z"HM 90 20 70 14/16/14/13/18 3261 1767 <br /> Problems found: <br /> Corrections made: <br /> Date corrections made: By: <br /> THIS IS TO CERTIFY THAT THE FIRE PUMP SYSTEM HAS BEEN PROPERLY <br /> TESTED AND INSPECTED FOR RELIABILITY TO COVER THE ITEMS LISTED <br /> IN THIS REPORT; IS CONSISTANT WITH MANUFACTURER'S REQUIREMENTS; <br /> AND ALL CORRECTIONS ARE TO BE MADE BY OWNER. <br /> Signature of Tester: <br /> /Agency: Capitol PumpResources Phone: (360) 493-1830 <br />