Laserfiche WebLink
I <br /> Static city water pressure 69 psi <br /> Churn suction pressure 66 psi Churn discharge pressure 149 psi <br /> Was 300 GPM flow conducted? Yes ® No ❑ <br /> Hose size: 2.5 inch Tip size: 2.5 inch Hose length: 25 ft <br /> Pitot reading: 9/9/9 GPM: 1524 <br /> Was pump run for 10 minutes flowing? Yes ® No ❑ <br /> Were all fire pumps tested? Yes ® No ❑ <br /> I <br /> Flow Chart <br /> NO.&SIZE OF PUMP PRESSURE PITOT FLOW RPM VOLTS AMPS COMMENTS <br /> NOZZELS PRESSURE <br /> DISCHG. SUCT. NET <br /> Churn 149 66 83 - 0 1770 <br /> 3—2 '/2"HM 137 64 73 9/9/9 1524 1769 <br /> 4—2 I/Z"HM 111 59 52 12/12/11/11 2246 1770 <br /> F <br /> Problems found: <br /> Collections made: <br /> Date corrections made: By: <br /> THIS IS TO CERTIFY THAT THE FIRE PUMP SYSTEM HAS BEEN PROPERLY <br /> TESTED AND INSPECTED FOR RELIABILITY TO COVER THE ITEMS LISTED <br /> IN THIS REPORT; IS CONSISTANT WITH MANUFACTURER'S REQUIREMENTS; <br /> AND ALL CORRECTIONS ARE TO BE MADE BY OWNER. <br /> Signature of Tester: <br /> Agency: Capitol Pump Resources Phone: (360) 493-1830 <br /> Witnessed By: <br /> HC;kw templates <br /> Es <br /> r <br /> i <br />