Laserfiche WebLink
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 11 <br /> DATE: 4/4/20255 KDC PHASE 1C\DESIGN\HYDRAULIC CALCS\SYSTEM 4\SYSTEM 4.SDF <br /> JOB TITLE: SYSTEM 4 3-6 <br /> WATER SUPPLY CURVE <br /> 108+ <br /> 99+ <br /> 90+ \\\ <br /> 81+ \\\ <br /> P 72+ X \\\ <br /> R \\\ <br /> E \\\\ <br /> S \\\ <br /> S 63+ \\\ <br /> U \\\ <br /> R \\\ <br /> E 56.0 psi @ 3771 gpm-> <br /> 54+ Flow Test Point <br /> P <br /> S <br /> 145+ <br /> 36+ <br /> 27+ <br /> ---------------------------- <br /> 18+ LEGEND " <br /> a <br /> X = Required Water Supply " <br /> 73.08 psi @ 1711.1 gpm " <br /> 9+ <br /> 0 = Available Water Supply " <br /> 87.50 psi @ 1711.1 gpm " <br /> 0++-+---+----+-----+------+--------+--------+---------+-----------+ <br /> 8001200 1600 2000 2400 2800 3200 3600 4000 <br /> FLOW (GPM) <br />