Laserfiche WebLink
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3 <br /> DATE: 12/17/202403\CALCULATIONS\HYDRAULIC CALC'S\TRAVELER HYD CALCSI2 .SDF <br /> JOB TITLE: Traveler <br /> NFPA WATER SUPPLY DATA <br /> SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D <br /> NODE PRESS. PRESS. @ PRESS. @ DEMAND PRESS. <br /> TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI) <br /> SOURCE 67 .0 57.0 3090.0 63. 6 1723. 9 53.8 <br /> AGGREGATE FLOW ANALYSIS: <br /> TOTAL FLOW AT SOURCE 1723. 9 GPM <br /> TOTAL HOSE STREAM ALLOWANCE AT SOURCE 0 .0 GPM <br /> OTHER HOSE STREAM ALLOWANCES 500.0 GPM <br /> TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 1223. 9 GPM <br /> NODE ANALYSIS DATA <br /> NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE <br /> (FT) (PSI) (GPM) <br /> 51 16.5 K=16.80 35.0 99.4 <br /> S2 16.5 K=16.80 35.3 99. 9 <br /> S3 16.5 K=16.80 36. 6 101. 6 <br /> S4 16.5 K=16.80 39.2 105.1 <br /> S5 16.5 K=16.80 35.2 99.7 <br /> S6 16.5 K=16.80 35.5 100.1 <br /> S7 16.5 K=16.80 36.8 101. 9 <br /> S8 16.5 K=16.80 39.4 105.4 <br /> S9 16.5 K=16.80 35. 9 100. 6 <br /> S10 16.5 K=16.80 36.2 101.1 <br /> S11 16.5 K=16.80 37.5 102 .8 <br /> S12 16.5 K=16.80 40 . 1 106.4 <br /> 1 14 .5 - - - - 36.8 - - - <br /> 2 14 .5 - - - - 37 .2 - - - <br /> 3 14 .5 - - - - 38.5 - - - <br /> 4 14 .5 - - - - 41 . 1 - - - <br /> 5 14 .5 - - - - 37.0 - - - <br /> 6 14 .5 - - - - 37 .4 - - - <br /> 7 14 .5 - - - - 38.7 - - - <br /> 8 14 .5 - - - - 41 .3 - - - <br /> 9 14 .5 - - - - 37.7 - - - <br /> 10 14 .5 - - - - 38 . 1 - - - <br /> 11 14 .5 - - - - 39.4 - - - <br /> 12 14 .5 - - - - 42 . 1 - - - <br /> A 14 .5 - - - - 62.7 - - - <br /> B 14 .5 - - - - 63. 1 - - - <br /> C 14 .5 - - - - 64.2 - - - <br /> D 13. 0 - - - - 107 .2 - - - <br /> E 16. 0 - - - - 114.4 - - - <br /> MF1 13. 0 - - - - 108 . 6 - - - <br /> MF2 13. 0 - - - - 110.8 - - - <br /> TOR 16. 0 - - - - 115.2 - - - <br />