Laserfiche WebLink
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 9 <br /> DATE: 12/17/202403\CALCULATIONS\HYDRAULIC CALC'S\TRAVELER HYD CALCSI2 .SDF <br /> JOB TITLE: Traveler <br /> Pipe Tag K-fac Add F1 Add Fl To Fit: L C (Pt) <br /> Frm Node El (ft) PT (q) Node/ Nom ID Eq.Ln. F (Pe) <br /> To Node El (ft) PT Tot. (Q) Disch Act ID (ft. ) T Pf/ft. (Pf) <br /> Pipe: 142 Source 551.3 VG 5. 00 140 0.0 <br /> SOURCE -11. 6 53.8 1172 .7 VF2 16.000 ---- 0.00 -0.0 <br /> VG2 -11 . 6 53.8 1723. 9 16.410 5.00 0.001 0.0 <br /> NOTES (HASS) : <br /> (1) Calculations were performed by the HASS 2023 D computer program <br /> in accordance with NFPA (2020) <br /> under license no. 65689119 granted by <br /> HRS Systems, Inc. <br /> 208 Southside Square <br /> Petersburg, TN 37144 <br /> (931) 659-9760 <br /> (2) The system has been calculated to provide an average <br /> imbalance at each node of 0.001 gpm and a maximum <br /> imbalance at any node of 0.056 gpm. <br /> (3) Total pressure at each node is used in balancing the system. <br /> Maximum water velocity is 27 . 6 ft/sec at pipe 27 . <br /> (4) The Minimum pump suction pressure under maximum <br /> calculated demand is 53.40 (psi) at any pump <br /> (5) Items listed in bold print on the cover sheet <br /> are automatically transferred from the calculation report. <br /> (6) Available pressure at source node SOURCE under full flow conditions is <br /> 63.42 psi with a flow of 1774 .55 gpm. <br /> (7) PIPE FITTINGS TABLE <br /> User Pipe Table Name: VIC <br />