Laserfiche WebLink
TFP316 <br /> Page 4of4 <br /> Installation Care and Limited <br /> TYCO Model ESFR-17 Early Suppres- Maintenance Warranty <br /> sion, Fast Response 16.8K Upright <br /> Sprinklers must be installed in accor- TYCO Model ESFR-17 Early Suppres- For warranty terms and conditions,visit <br /> dance with this section. sion, Fast Response 16.8K Upright www.tyco-fire.com. <br /> General Instructions Sprinklers must be maintained and ser- <br /> Avoid damage to the fusible Link viced in accordance with this section. Ordering <br /> Assembly during installation by using Before closing a fire protection system procedure <br /> the Frame arms only to handle the main control valve for maintenance <br /> sprinkler and by using the appropri- work on the fire protection system that <br /> ate sprinkler wrench. Do not apply it controls,permission to shut down the Contact your local distributor for avail- <br /> pressure to the fusible Link Assembly. affected fire protection system must be ability.When placing an order, indicate <br /> Failure to do so can lead to an unstable obtained from the proper authorities the full product name and part number <br /> link assembly and premature activation and notify all personnel who may be (P/N). <br /> of the sprinkler. Damaged sprinklers affected by this action. Sprinkler Assemblies <br /> must be replaced. Sprinklers which are found to be Specify: Model ESFR-17 Early Sup- <br /> A leak-tight 3/4 in. NPT sprinkler joint leaking or exhibiting visible signs of pression, Fast Response 16.8K Upright <br /> should be obtained by applying a min- corrosion must be replaced. Sprinklers(TY7126), (specify tempera- <br /> imum-to-maximum torque of 10 to 20 ture rating), with Natural Brass finish, <br /> lb-ft (13,4 to 26,8 N•m). Higher levels Automatic sprinklers must never be P/N (specify): <br /> of torque can distort the sprinkler inlet painted, plated, coated, or other. 165°F(74°C)..................58-447-1-165 <br /> with consequent leakage or impairment wise altered after leaving the factory. 212°F(100°C).................58-447-1-214 <br /> of the sprinkler. Modified sprinklers must be replaced. <br /> Sprinklers that have been exposed to Special Order <br /> Note: Install the Model ESFR-17 Upright corrosive products of combustion, but Sprinkler Assemblies with <br /> Sprinkler in the Upright position as shown have not operated,should be replaced ISO 7-1 Thread Connection <br /> in Figure 2. if they cannot be completely cleaned Specify: Model ESFR-17 Early Sup- <br /> Step 1. With pipe thread sealant by wiping the sprinkler with a cloth or pression, Fast Response 16.8K Upright <br /> applied,hand-tighten the sprinkler into by brushing it with a soft bristle brush. Sprinklers (TY7126) with ISO 7-1 <br /> the sprinkler fitting. Do not apply pres- Care must be exercised to avoid thread connection, (specify tempera- <br /> sure to the Link Assembly, and handle damage to the sprinklers before, ture rating), with Natural Brass finish, <br /> the Model ESFR-17 Sprinkler only by during, and after installation. Sprin- P/N (specify): <br /> the Frame arms. klers damaged by dropping, striking, 165°F(74°C)..................58-448-1-165 <br /> Step 2. Wrench-tighten the Model wrench twist/slippage,or the like,must 212°F(100°C).................58-448-1-214 <br /> ESFR-17 Upright Sprinkler using only be replaced.Also,replace any sprinkler Sprinkler Wrench <br /> the W-Type 21 Sprinkler Wrench as that has a cracked bulb or that has lost Specify: W-Type 21 Sprinkler Wrench, <br /> shown in Figure 2, and by fully engag- liquid from its bulb. For more informa- P/N 56-001-0-686 <br /> ing(seating)the wrench on the sprinkler tion, see the Installation section. <br /> wrench flats as shown in Figure 1. The owner is responsible for the <br /> Step 3. After installation, inspect the inspection,testing,and maintenance of <br /> Link Assembly of each Model ESFR-17 their fire protection system and devices <br /> Sprinkler for damage. In particu- in compliance with this document, as <br /> lar, verify that the Link Assembly and well as with the applicable standards <br /> Hook are positioned as shown in Figure of the National Fire Protection Associ- <br /> 1, and that the Link Assembly is not ation, such as NFPA 25, in addition to <br /> bent, creased, or forced out of normal the standards of any authorities having <br /> position in any way. Replace damaged jurisdiction.Contact the installing con- <br /> sprinklers. tractor or product manufacturer with <br /> any questions. <br /> Automatic sprinkler systems are <br /> recommended to be inspected, <br /> tested, and maintained by a qualified <br /> Inspection Service in accordance with <br /> local requirements and/or national <br /> codes. <br /> 1467 Elmwood Avenue,Cranston,RI 029101 Telephone+1-401-781-8220 <br /> O 2022 Johnson Controls.All rights reserved.All specifications and other information shown were current as of document revision date and are subject to change without notice. Johnson <br /> 11^Ison <br /> NATIONAL FIRE PROTECTION ASSOCIATION a d NFPA are regist,,,d tratlemarks of National Fire Protection Association; Controls <br /> TEFLON is atr.d—rk of The Ch—.rs Company FC,LLC 1 1 I.1 <br />