TFP316
<br /> Page 4of4
<br /> Installation Care and Limited
<br /> TYCO Model ESFR-17 Early Suppres- Maintenance Warranty
<br /> sion, Fast Response 16.8K Upright
<br /> Sprinklers must be installed in accor- TYCO Model ESFR-17 Early Suppres- For warranty terms and conditions,visit
<br /> dance with this section. sion, Fast Response 16.8K Upright www.tyco-fire.com.
<br /> General Instructions Sprinklers must be maintained and ser-
<br /> Avoid damage to the fusible Link viced in accordance with this section. Ordering
<br /> Assembly during installation by using Before closing a fire protection system procedure
<br /> the Frame arms only to handle the main control valve for maintenance
<br /> sprinkler and by using the appropri- work on the fire protection system that
<br /> ate sprinkler wrench. Do not apply it controls,permission to shut down the Contact your local distributor for avail-
<br /> pressure to the fusible Link Assembly. affected fire protection system must be ability.When placing an order, indicate
<br /> Failure to do so can lead to an unstable obtained from the proper authorities the full product name and part number
<br /> link assembly and premature activation and notify all personnel who may be (P/N).
<br /> of the sprinkler. Damaged sprinklers affected by this action. Sprinkler Assemblies
<br /> must be replaced. Sprinklers which are found to be Specify: Model ESFR-17 Early Sup-
<br /> A leak-tight 3/4 in. NPT sprinkler joint leaking or exhibiting visible signs of pression, Fast Response 16.8K Upright
<br /> should be obtained by applying a min- corrosion must be replaced. Sprinklers(TY7126), (specify tempera-
<br /> imum-to-maximum torque of 10 to 20 ture rating), with Natural Brass finish,
<br /> lb-ft (13,4 to 26,8 N•m). Higher levels Automatic sprinklers must never be P/N (specify):
<br /> of torque can distort the sprinkler inlet painted, plated, coated, or other. 165°F(74°C)..................58-447-1-165
<br /> with consequent leakage or impairment wise altered after leaving the factory. 212°F(100°C).................58-447-1-214
<br /> of the sprinkler. Modified sprinklers must be replaced.
<br /> Sprinklers that have been exposed to Special Order
<br /> Note: Install the Model ESFR-17 Upright corrosive products of combustion, but Sprinkler Assemblies with
<br /> Sprinkler in the Upright position as shown have not operated,should be replaced ISO 7-1 Thread Connection
<br /> in Figure 2. if they cannot be completely cleaned Specify: Model ESFR-17 Early Sup-
<br /> Step 1. With pipe thread sealant by wiping the sprinkler with a cloth or pression, Fast Response 16.8K Upright
<br /> applied,hand-tighten the sprinkler into by brushing it with a soft bristle brush. Sprinklers (TY7126) with ISO 7-1
<br /> the sprinkler fitting. Do not apply pres- Care must be exercised to avoid thread connection, (specify tempera-
<br /> sure to the Link Assembly, and handle damage to the sprinklers before, ture rating), with Natural Brass finish,
<br /> the Model ESFR-17 Sprinkler only by during, and after installation. Sprin- P/N (specify):
<br /> the Frame arms. klers damaged by dropping, striking, 165°F(74°C)..................58-448-1-165
<br /> Step 2. Wrench-tighten the Model wrench twist/slippage,or the like,must 212°F(100°C).................58-448-1-214
<br /> ESFR-17 Upright Sprinkler using only be replaced.Also,replace any sprinkler Sprinkler Wrench
<br /> the W-Type 21 Sprinkler Wrench as that has a cracked bulb or that has lost Specify: W-Type 21 Sprinkler Wrench,
<br /> shown in Figure 2, and by fully engag- liquid from its bulb. For more informa- P/N 56-001-0-686
<br /> ing(seating)the wrench on the sprinkler tion, see the Installation section.
<br /> wrench flats as shown in Figure 1. The owner is responsible for the
<br /> Step 3. After installation, inspect the inspection,testing,and maintenance of
<br /> Link Assembly of each Model ESFR-17 their fire protection system and devices
<br /> Sprinkler for damage. In particu- in compliance with this document, as
<br /> lar, verify that the Link Assembly and well as with the applicable standards
<br /> Hook are positioned as shown in Figure of the National Fire Protection Associ-
<br /> 1, and that the Link Assembly is not ation, such as NFPA 25, in addition to
<br /> bent, creased, or forced out of normal the standards of any authorities having
<br /> position in any way. Replace damaged jurisdiction.Contact the installing con-
<br /> sprinklers. tractor or product manufacturer with
<br /> any questions.
<br /> Automatic sprinkler systems are
<br /> recommended to be inspected,
<br /> tested, and maintained by a qualified
<br /> Inspection Service in accordance with
<br /> local requirements and/or national
<br /> codes.
<br /> 1467 Elmwood Avenue,Cranston,RI 029101 Telephone+1-401-781-8220
<br /> O 2022 Johnson Controls.All rights reserved.All specifications and other information shown were current as of document revision date and are subject to change without notice. Johnson
<br /> 11^Ison
<br /> NATIONAL FIRE PROTECTION ASSOCIATION a d NFPA are regist,,,d tratlemarks of National Fire Protection Association; Controls
<br /> TEFLON is atr.d—rk of The Ch—.rs Company FC,LLC 1 1 I.1
<br />
|