Laserfiche WebLink
Kidde Fire Systems <br /> NaturaTM Inert Gas System or Kidde <br /> Component Description Fire Systems <br /> Effective: April 2022 <br /> Release Unit K-38-2110 Rev AD <br /> FEATURES <br /> • For Approvals,see the"COMPATIBILITY"table. <br /> • REACH and RoHS compliant <br /> DESCRIPTION <br /> Release units connect to the gauge port of the pri- <br /> mary cylinder and are used to release the agent to <br /> the piping system. Release units can be electric oper- <br /> ated only or manual/electric. Depending on the con- <br /> trol panel needs, release units can be purchased with <br /> pressure gauges using normally open or normally <br /> closed contacts (when under pressure). <br /> Release units that include manual operation have a tam- <br /> per proof seal on the operation pin. Replacement seals <br /> are included in the Release Unit Service kit, P/N: 38- <br /> 400001-010. ' <br /> SPECIFICATIONS <br /> Nominal Working Pressure: 300 bar(4350 psi) <br /> Max Working Pressure at 50°C (122°F): <br /> 366 bar(5307 psi) <br /> Weight: 1.8 kg (3.97 Ibs) <br /> Switch: <br /> Voltage; 4.5-24 VDC <br /> Current: 5-100mA, Contact Load 2AW max <br /> Operating Voltage: 24 VDC 18W <br /> Current Draw: 0.75 Amps <br /> Gauge: ORDERING INFORMATION <br /> St. St. Casing <br /> Part Number Pressure O eration Contact <br /> Accuracy Class 1.6 in Rating p <br /> Scale: IP 65 <br /> 38-400001-001 200 Bar Manual/ Normally Open <br /> Temp Range: Electric <br /> FM Approved / UL Listed: -4° to 130°F (-20° to 54°C)* 38-400001-003 300 Bar Manual/ Normally Open <br /> *Unless superseded by local/national standards Electric <br /> "Not for use on for FM Approved and UL Listed systems,for LPCB <br /> Listed systems only <br /> 1 <br />