Laserfiche WebLink
Job : Boeing Cells Hydraulic Calculations <br /> PIPE INFORMATION <br /> Node 1 Elev 1 K-Factor 1 Flow added (q) Nominal ID Fittings L C Factor total (Pt) <br /> Node 2 Elev 2 K-Factor 2 Total flow (Q) Actual ID quantity x (name) = length F Pf per ft elev (Pe) NOTES <br /> T frict (Pf) <br /> (ft) (gpm/psis/z) (gpm) (in) (ft) (ft) (psi) (psi) <br /> Path No: 1 <br /> 135 -7.9 0 8 0.12 120 115.3 <br /> 136-0 -8.01 186.1 8.329 0 0.0003 0.1 <br /> 0.12 0 <br /> 136-0 -8.01 0 8 0.96 115.3 Gate A2360 <br /> 136-I -8.97 186.1 0 0 0.1044 0.4 *** <br /> 0.96 0.1 <br /> 136-I -8.97 0 8 1x(tee-Br)=43.09 2.61 120 115.8 <br /> 138 -11.58 186.1 8.329 43.09 0.0003 1.1 <br /> 45.7 0.0 <br /> 138 -11.58 0 10 6.13 120 117 <br /> W1 -11.58 186.1 10.42 0 0.0001 0 <br /> 6.13 0 <br /> W1 117 <br /> * Pressures are balanced to a high degree of accuracy. Values may vary by 0.1 psi due to display rounding. <br /> * Maximum Velocity of 26.94 ft/s occurs in the following pipe(s): (0024-617) <br /> *** Device pressure loss (gain in the case of pumps) is calculated from the device's curve. If the device curve is printed with <br /> this report, it will appear below. The length of the device as shown in the table above comes from the CAD drawing. The friction <br /> loss per unit of length is calculated based upon the length and the curve-based loss/gain value. Internal ID and C Factor values <br /> are irrelevant as the device is not represented as an addition to any pipe, but is an individual item whose loss/gain is based <br /> solely on the curve data. <br /> File:C:\Users\yates\Documents\dwg2\burns\tenant improvements\boeing\Ti 1_21_25\submittal\Boeing cell ti <br /> 2025.dwg <br /> Date 2/4/2025 Copyright©2002-2012 Tyco Fire Protection Products Page 9 <br />