Laserfiche WebLink
SYSTEM SIZE <br /> PV SYSTEM(DC):6.480kW <br /> PV SYSTEM(AC):4.64kW @ 240V <br /> WIRE SCHEDULE <br /> STARTING ADJUSTMENT MAXIMUM CLIENT DETAILS <br /> STARTING TEMPERATURE ADJUSTED VICTOR QUIROZ JIMENEZ <br /> RACEWAY CONDUCTOR <br /> AWG ALLOWABLE CURRENT CORRECTION FACTOR FOR CONDUCTOR CURRENT 6117 W MAGNOLIA AVE,EVERETT,WA 98203 EQUIPMENT WIRE APPLIED TO MORE THAN 3 APPLIED TO AHJ:CITY OF EVERETT <br /> SIZE CONDUCTORS CONDUCTORS CONDUCTORS <br /> # QTY. AMPACITY @ 90°C FACTOR AMPACITY UTILITY:SNOHOMISH PUD <br /> 310.15(B)(16) 310.15(B)(2)(a) @ 90°C METER:63 282 652 <br /> IN RACEWAY 310.15(B)(3)(a) IN RACEWAY APN:280401-004-006-00 <br /> PHONE:(206)941-7448 <br /> 1 DC MODULE TO MICROINVERTER 2 10 40 13.88 0.91 1 36.4 17.34 EMAIL:VJQUIROZ2@YAHOO.COM <br /> 2 AC ENPHASE COMBINER PANEL TO AC DISCONNECT 3 10 40 19.36 0.91 1 36.4 24.2 <br /> 3 AC AC DISCONNECT TO PRODUCTION METER 3 6 75 19.36 0.91 1 68.25 24.2 <br /> 4 AC PRODUCTION METER TO POI 3 6 75 19.36 0.91 1 68.25 24.2 SYSTEM DETAILS <br /> MODULES:16 X JA SOLAR:JAM54S31-405/MR <br /> MICROINVERTERS:16 X ENPHASE <br /> IQ8PLUS-72-M-US <br /> REVISIONS <br /> NO. REVISED BY DATE <br /> 1 Z.S. 05/20/2025 <br /> freedom <br /> O P F V f N <br /> FREEDOM FOREVER WASHINGTON,LLC <br /> 43445 BUSINESS PARK DRIVE SUITE 110, <br /> TEMECULA,CA 92590 <br /> Tel:(888)557-6431 <br /> GREG ALBRIGHT <br /> CONTRACTOR LICENSE: <br /> ELECTRICAL ADMINISTRATOR ALBRIG`807C1 <br /> CONDUCTOR AMPACITY CALCULATIONS IN ACCORDANCE WITH NEC 690.8. <br /> CONDUCTOR CALCULATIONS <br /> JOB NO: DATE: DESIGNED BY: SHEET: <br /> 558938 05/20/2025 Z.S. PV-5 <br />