MICROINVERTERS SPECIFICATION PV MODULE RATING A STC Rooftop conductor ampacities designed in compliance with 120% RULE 0 <br /> MICROINVERTER MAKE AP SYSTEMS MANUFACTURER ZNSHINESOLAR ZXM7-SH108-410M art. 690.8, Tables 310.15(B)(1), 310.15(C)(1), 310.15(B)(2), <br /> MICROINVERTER MODEL NO. DS3-S 310.16, Chapter 9 Table 4, 5, &9. Location specific BUS BAR RATING X 120%) - MAIN BREAKER RATING infinit solar <br /> MAX.POWER-POINT CURRENT(IMP) 13.10 AMPS p p infinity <br /> solar <br /> AC OUTPUT 640 W temperature obtained from ASHRAE 2017 data tables = MAX. PV OCPD <br /> MAX INPUT VOLTAGE 60 V MAX.POWER-POINT VOLTAGE(VMP) 31.30 VOLTS INFINITY HOME SOLUTIONS <br /> MAX AC CURRENT 2.66 A OPEN-CIRCUIT VOLTAGE(VOC) 37.50 VOLTS (200A x 120%) - 200 = 40A 6405 E MILL PLAIN <br /> VANCOUVER WA98661 <br /> MAX OUTPUT VOLTAGE 240 V SHORT-CIRCUIT CURRENT(ISC) 13.84 AMPS RECORD LOW TEMP -5'C PNONE:Y 800-81SOLAR COM8 <br /> NOM.MAX.POWER AT STC(PMAX) 410 WATT AMBIENT TEMP(HIGH TEMP 2%) 26°C THIS PANEL IS FED BY MULTIPLE SOURCES <br /> VISIBLE, LOCKABLE, LABELED DISCONNECT (UTILITY AND SOLAR) REVISIONS <br /> WITHIN 10' OF UTILITY METER MAX.SYSTEM VOLTAGE 1500V CONDUIT HEIGHT 7/8" Description Date Rev <br /> VOC TEMPERATURE COEFFICIENT -0.29%/°C ROOF TOP TEMP 48°C AC OUTPUT CURRENT 23A Initial Design 12/18/24 00 <br /> NOTE : CONDUCTOR TEMPERATURE RATE 90°C NOMINAL AC VOLTAGE 240V <br /> ATTIC RUN -YES MODULE: (13)ZNSHINESOLAR ZXM7-SH108-410M <br /> SHUTDOWN - NO INVERTER: (07)AP SYSTEMS DS3-S .-H <br /> POINT OF INTERCONNECT, LOAD SIDE Signature with Seal <br /> NOTE: (SOLAR PV SYSTEM EQUIPPED WITH EXISTING 240V/200A BUS BAR RATING, <br /> RAPID SHUTDOWN) NEEDS TO BE LOCATED MAIN SERVICE PANEL, SINGLE PHASE, <br /> WITHIN 3FT OF AC DISCONNECT. WITH A 200A MAIN BREAKER <br /> UTILITY COMPANY- PUD NO.1 SNO.CO. <br /> UTILITY METER#338949 <br /> EXISTING <br /> BI-DIRECTIONAL Project Name& <br /> (13) ZNSHINESOLAR ZXM7-SH108-410M Address <br /> (07) AP SYSTEMS DS3-S INVERTERS (N) 125A COMBINER PANEL, (N) BLADE TYPE M UTILITY METER, <br /> NON-FUSIBLE AC DISCONNECT 1-PHASE, 3W, W <br /> BRANCH 1-07 MODULES WITH 04 MICRO INVERTERS 240V,3W,1-PHASE <br /> NEMA 3R 30A-2P 120/240VAC 120V/240V z <br /> (VISIBLE, LOCKABLE, LABELED) o <br /> 200A E-{ W o <br /> w < ¢ a <br /> opop .7 (E)LOADS Q Z Z <br /> = L — J L = J L = J (N) JUNCTION BOX (N)PV BREAKER Z Q LU J <br /> ----------------- --------- ------ <br /> 600 V, NEMA 4 15A > 2E w O < <br /> UL LISTED 30A/2P W o w a- Lu <br /> BRANCH 2-06 MODULES WITH 03 MICRO INVERTERS L1 <br /> 15A L j <br /> I L1 L1 L2 �� W <br /> I = <br /> 2 L2 U <br /> L1 L1 <br /> G <br /> - Sheet Name <br /> L <br /> J --- 3-LINE <br /> EXISTING GROUNDING DIAGRAM <br /> 1 2 3 3 ELECTRODE SYSTEM <br /> Sheet Size <br /> ANSI B <br /> WIRE MAX PARALLEL C.0 PV CURB. TOTAL CONT. CURR WIRE SIZE\TYPE\AMP. WIRE #C.C.C. CONDUIT TEMP CONDUIT WIRE DERATED MAX. CONT. LENGTH VOLTAGE 11" X 17" <br /> GND <br /> TAG# DEVICES RATING MULT CURR X 125% OCP DE-RATE: FILL: AMP: AMPACITY CURRENT FT. MAX DROP(/o) <br /> Sheet Number <br /> #10\THWN \40A @90°C 15A 2 TRUNK CABLE 1.00 x 1.00 x 40A 40.00A 10.64A <br /> 04 x 2.66 x N/A = 10.64A 13.30A IN AIR #6 AWG 20 0.28 E 1 .1 <br /> 2 04 x 2.66 x N/A = 10.64A 13.30A #10\THWN \40A @90°C 15A 4 3/4" EMT 1.00 x 0.80 x 40A 32.00A 10.64A 55 1.19< <br /> #8 AWG 0.76 2 <br /> O07 x 2.66 x N/A = 18.62A 23.28A #10\THWN\ 35A @75°C 30A 2 3/4" EMT 1.00 x 1.00 x 35A 35.00A 18.62A #8 AWG 10 0.15 <br />