SION <br /> S INC. <br /> CLEAN AGENT AREA VOLUME CALCULATIONS SUPIAL H—RDSYSTEOTECTO <br /> SPECIAL HAZARDS FIRE PROTECTION <br /> FI E 20TH STREET EAST,SUITE B <br /> FIFE,WA 98420-1 793 <br /> MINIMUM ADJUSTED ESTIMATED n(253)9263300 FM(253)92"3N <br /> 001 002 004 020 021 NON PERMEABLE AGENT ELEVATION MINIMUM AGENT FREE VENT <br /> Al AI AI 2 p I p ROOM DESCRIPTION AREA DEPTH VOLUME VOLUME CONCENTRATION REQUIRES AGENT CORRECTION AGENT SUPPLIED CYLINDER AREA <br /> (SQUARE FEET) (FEET) (CUBIC FEET) (CUBIC FEET) (%BY VOLUME) (POUNDS) FACTOR REQUIRED (POUNDS) SUPPLIED (SQUARE <br /> 0 01 NICET STAMPS <br /> P (POUNDS) FEET) <br /> SHIPPING CONTAINER 160.00 7'-6" 1155 45 46.90 54.0 54.0 54.3 80 L 0.2 <br /> m N NETWORKJINTERFACE BANK A+MTS <br /> � to uva° <br /> y til 7 �e <br /> fA rn�n,nn" <br /> °C °� RS-232 <br /> rB, re,5ALARM 3 <br /> SUPERVISORY RELAY 1 Tea VOLUME CALCULATION NOTES: --� <br /> RELAY 2 T6e <br /> DISCHARGE 1. FORMULA FOR CALCULATIONS: " � ° <br /> TROUBLE RELAY 3 Te9 KI D D E AR I ES-S LX 1.1. AREA x DEPTH=VOLUME <br /> RELAY4 TB,9 1.2. MINIMUM AMOUNT OF AGENT REQUIRED X ELEVATION CORRECTION= 90°ELBOW 1/2"NPT <br /> WIRING BY OTHERS MANUFACTURER LOGO'S <br /> NTR L PAN E L ADJUSTED MINIMUM AGENT REQUIRED <br /> 2. NON-PERMEABLE VOLUME OF 45CF APPLIED. 1/2"NPT DISCHARGE PIPE TO <br /> 3. FOR ADDITIONAL INFORMATION SEE THE CLEAN AGENT FLOW CALCULATIONS REDUCE 3/4"X 1/2"NPT DISCHARGE NOZZLE fKidde <br /> BATTERY Tea INCLUDED IN THE SUBMITTAL PACKAGE. o Fire Systems <br /> Te NAC 2 30cd 4. AGENT DESIGN CONCENTRATION IS FROM NFPA 2001 AND MANUFACTURE - <br /> RECOMMENDATIONS. FLEX HOSE PN: ��UNION 1/2"NPT <br /> Tes NAC 1 <br /> 0.130A 38-400330-410 TEE 3/4"NPT <br /> ISOMETRIC PIPING NOTES: - <br /> TB,2 TBll T. T. TBs ADAPTER 3/4",BSP TO NPT <br /> N � N 5. PIPE LENGTH'S DO NOT REPRESENT CUT LENGTH'S. CYLINDER VALVE AND - <br /> 120VAC INPUT POWER nc aoweR rB,3 w m °° m m 6. ALL LENGTH'S SHALL BE FIELD VERIFIED. DISCHARGE HOSE SEE <br /> WIRING BY OTHERS x 7. ALL PIPING 1/2"TO 1 1/2"SHALL BE THREADED.MINIMUM AND MAXIMUM ACTUATION DETAIL <br /> w w O o PRESSURE RATINGS SHALL MEET FSSA PIPE DESIGN GUIDE FOR USE WITH <br /> SPECIAL HAZARD FIRE SUPPRESSION SYSTEMS. O FIRE PROTECTION ENGINEERS STAMP <br /> EOL 8. ALL PIPING 2"TO 6"SHALL BE GROOVED.MINIMUM AND MAXIMUM PRESSURE <br /> 30cd <br /> EOL RATINGS SHALL MEET FSSA PIPE DESIGN GUIDE FOR USE WITH SPECIAL <br /> 0.158A HAZARD FIRE SUPPRESSION SYSTEMS. <br /> 9. ANY DEVIATIONS IN PIPE LENGTH OR SIZE SHALL BE APPROVED BY <br /> SUPPRESSION SYSTEMS INC.PRIOR TO BEGINNING INSTALLATION. <br /> CLEAN AGENT NOTES <br /> M ILR $QL 1/2"X 6'-4" n SUUBPUANCE MIITALS DATE <br /> LO• R 1/2"XU-3" 100%SUBMITTAL 12/06/24 <br /> CLEAN AGENT 38-407500-055 <br /> CYLINDER <br /> 1/2"X V-0" PN:38-428031-100 REV DESCRIPTION DATE <br /> OWNER 12/17/24 <br /> COMMENTS <br /> 1/2-X 1'-6„ <br /> 2 <br /> REDUCE 3/4"X 1/2"NPT Q3 <br /> 10.5" <br /> SINGLE LINE WIRING CLEAN AGENT ISOMETRIC CYLINDER ARRANGEMENT <br /> z <br /> 0 <br /> 30ctl U <br /> P w <br /> ztti� �021 �020 0 0 o O Q o <br /> 0 o 0 o N <br /> wmm M¢ P¢ ^ Y 07 <br /> 00 BUILDING FIRE ALARM CONTROL PANEL LL Q Z <br /> ����� LOCATION OF CYLINDER AND PANEL 0 W O- O <br /> 0 Y � <br /> 10 LOCATION OF THE CONEX MTS/A+ w CD <br /> LLJ <br /> FRONT PLAN TOP PLAN BACK PLAN x <br /> F w z _jQ <br /> Z 0 F � <br /> w U <br /> 0- ww <br /> N - o w <br /> o > <br /> x Nw <br /> 2. z <br /> ZN O _ <br /> yo ¢ Q <br /> a N /mil <br /> Eo o �V <br /> E z x <br /> IL y F <br /> xa � <br /> 2 w 00 <br /> m <br /> Wa 0 <br /> y a <br /> O <br /> T— <br /> fl DESIGNED BY:NMB SCALE: <br /> - DRAWN BY: NMB NOT TO <br /> = SCALE <br /> -- '„ UNLESS <br /> CHECKED BY:ZST NOTED <br /> JOB NUMBER:2473 OTHERWISE <br /> SHEET TITLE: <br /> ' FIRE PROTECTION DRAWINGS <br /> j' CONEX MTS/A+FLOOR PLANS, <br /> -- WIRING DETAIL&ISOMETRIC <br /> SHEET NUMBER: <br /> ISOMETRIC PLAN TOP PLAN BACK PLAN AREA OF WORK FP-03 of 06 <br />