Laserfiche WebLink
Eintegra <br /> NEUDORFER <br /> ENGINEERS <br /> AN Integra COMPANY <br /> Fan Unit <br /> PROJECT: Discount Tires- Everett DATE: 8/26/2025 <br /> LOCATION: Everett,WA CONTACT: Tony Vela <br /> PROJECT#: 2025-0403 AUTHOR: Tony Vela <br /> SYSTEM/UNIT: EF-02 Tested By: Tony Vela <br /> Date: 8/26/2025 <br /> Unit Data Motor Data <br /> Fan Manufacturer Broan Motor RPM 640 RPM <br /> Fan Model Number L100 Motor Rated Volts 120 Volts <br /> Drive Type Direct Motor Full Load Amps 87W Amps <br /> Fan Speed N/L <br /> Test Pressures <br /> Starter Data Design External SP 0.38 in.we <br /> Rating(Amps) 87W Amps <br /> Test Data <br /> Total Design Flow 100 CFM <br /> Total Actual Flow 58 CFM <br /> EF-02 Exhaust Inlet Summary <br /> System/Unit Type of Inlet Size LxW/D AK Design Prelim Final Final% Remarks <br /> Readinq Type Airflow Airflow Airflow <br /> Inlet-01 Flowhood EG 1.00 100 58 58 58 <br /> Totals: - 100 58 58 58 - <br /> Neudorfer Engineers Page 5 of 22 <br />