Laserfiche WebLink
FLin <br /> NEUDORFER <br /> e g r a, IVENGINEERS <br /> AN Integra COMPANY <br /> Fan Unit <br /> PROJECT: Discount Tires- Everett DATE: 8/20/2025 <br /> LOCATION: Everett,WA CONTACT: Tony Vela <br /> PROJECT#: 2025-0403 AUTHOR: Tony Vela <br /> SYSTEM/UNIT: EF-02 Tested By: Tony Vela <br /> Date: 8/20/2025 <br /> Unit Data Motor Data <br /> Fan Manufacturer Broan Motor Manufacturer No Access <br /> Fan Model Number L100 Motor Frame No Access <br /> Fan Serial Number No Access Motor Power No Access HP <br /> Fan Rotation No Access Motor RPM 640 RPM <br /> Fan Discharge No Access Motor Rated Volts 120 Volts <br /> Drive Type Direct Motor Phase No Access <br /> Fan Speed N/L Motor Hertz No Access Hz <br /> Motor Full Load Amps 87W Amps <br /> Starter Data Motor Service Factor No Access <br /> Starter Manufacturer NA Nominal Efficiency No Access% <br /> Starter Model No. NA Power Factor No Access <br /> Starter Size NA <br /> Installed Thermal NA Sheave Data <br /> Rating(Amps) 87W Amps Motor Sheave MFG NA <br /> Required Thermals Motor Sheave Model NA <br /> Required Amps Motor Sheave Diam. NA in. <br /> Motor Sheave Bore NA in. <br /> Test Data Motor Sheave Type NA <br /> Total Design Flow 100 CFM Adj Mtr Sheave Pos NA <br /> Total Actual Flow 58 CFM Fan Sheave MFG NA <br /> Fan RPM Design N/L RPM Fan Sheave Model NA <br /> Fan RPM Actual No Access RPM Fan Sheave Diam. NA in. <br /> Motor RPM Actual No Access RPM Fan Sheave Bore NA in. <br /> Motor VFD Hertz NA Hz Number of Belts NA <br /> Motor Volts T1-T2 No Access Volts Belt Size NA <br /> Motor Volts T2-T3 No Access Volts Sheave Center Line NA in. <br /> Motor Volts T1-T3 No Access Volts Motor to Extend NA in. <br /> Motor Amps T1 No Access Amps Motor to Retract NA in. <br /> Motor Amps T2 No Access Amps <br /> Motor Amps T3 No Access Amps Test Pressures <br /> Fan Suction SP No Access in.we <br /> Fan Discharge SP No Access in.we <br /> Design Total SP -in.we <br /> Actual Total SP No Access in.we <br /> Design External SP 0.38 in.we <br /> Actual External SP No Access in.we <br /> Filter DP <br /> Coil DP <br /> EF-02 Exhaust Inlet Summary <br /> System/Unit Type of Inlet Size LxW/D AK Design Prelim Final Final% Remarks <br /> Readinci Type Airflow Airflow Airflow <br /> Inlet-01 Flowhood EG 1.00 100 58 58 58 <br /> Totals: - - - - 100 58 58 58 - <br /> Neudorfer Engineers Page 3 of 4 <br />