Mr. Miguel Ortega <br /> TEKAS Fire & Hood Installations, LLC <br /> Plan Check Number: M2110-081, First Building Review <br /> November 8, 2021 <br /> Comments <br /> 1. The proposed project may require modifications to the building, including but not limited to the <br /> roof and ceiling framing, and the wall supporting the hood. A separate building permit <br /> application is required for building modifications. See IBC Section 105.1. <br /> 2. Continuing with the previous comment, modifications to the structural system will require <br /> structural drawings and calculations prepared by a professional engineer licensed in the state of <br /> Washington. See IBC Section 107.1, and RCW Sections 18.43.010, 18.43.020, and 18.43.070. <br /> 3. Typical Section B/M1 shows the installation of the new hood and MAU on the roof of the <br /> building. See IBC Section 107.2.1. The following comments should be addressed: <br /> a. The plans should include a roof plan showing the location of the MAU. <br /> b. The building is a converted house with a steep slope that is anticipated to be framed with <br /> roof joists. The section shows a standard flat roof with trusses, and is not valid. A section <br /> specific to the proposed work should be included. <br /> c. The weights of the hood and MAU should be specified in the drawings. Calculations <br /> evaluating the strength of the roof to support the units should be submitted for review. See <br /> IEBC Section 806.2. <br /> d. The MAU is located on a sloped roof and is required to have a service platform complying <br /> with IMC Section 306.5.1. <br /> 4. The submittal documents include generic manufacturer requirements for suspending the hood. <br /> Details specific to the project for connecting the hood to the structure above should be included <br /> in the construction drawings. See IBC Sections 107.2.1 and 1604.1. <br /> 5. The building construction appears to be wood framing. The hood is required to have a <br /> minimum 18-inch clearance to combustible materials. Alternatively, reduced clearance <br /> construction is required peer IMC Table 308.4.2. See IMC Section 507.2.6. <br /> 6. Section A/M1 shows the zero-clearance duct wrap extending not more than 18-inches below the <br /> roof framing. The duct is anticipated to be located against a wall. The wrap should extend for <br /> the full height of the duct. See IMC Section 506.3.6. <br /> 7. Up-blast fans serving Type I hoods shall be installed with a hinge, restraint, and flexible <br /> electrical cable to permit inspection and cleaning. These do not appear to be specified. The <br /> drawing should be revised. See IMC 506.5.3. <br /> 3200 Cedar Street © 425.257.8810 O everetteps@everettwa.gov <br /> Everett,WA 98201 425.257.8857 fax everettwa.gov/permits <br /> Page 2 of 3 <br />