Laserfiche WebLink
ABOVE-GROUND STORAGE TANKS STAINLESS STEEL HVAC PIPING SPECIFICATIONS PLUMBING PIPING SPECIFICATIONS <br /> 1. HIGH PRESSURE STEAM AND CONDENSATE (LIPS) PIPING: ASTM A53B SCH 40 1. 1 1/2" HYDRAULIC FLUID SUPPLY(HS) PIPING:ASTM A790 ALLOY 2205 SCH <br /> MARK LOCATION SERVICE SIZE, GALLONS TANK DIAMETER TANK LENGTH TANK/FITTINGS TYPE REMARKS BLACK STEEL PIPE WITH BUTT-WELDED FITTINGS AND CLASS 300 FLANGES, 80 STAINLESS STEEL PIPE WITH BUTT WELD FITTINGS TO ASME B31.3, <br /> MATERIAL EXCEPT SCH 80 WITH ASTM A105 CLASS 3000 FORGED STEEL SOCKET WELD CHAPTER IX,AND AS SPECIFIED <br /> FITTINGS FOR 2"AND SMALLER. <br /> UL-142 CUSTOM STAINLESS STEEL CONSTRUCTION 2. 2" HYDRAULIC FLUID RETURN (HR) PIPING:ASTM A312 TYPE 304L SCH 40 <br /> ST-1 A/P POS 2 HYDRAULIC 1500 60 125" TYPE 304L SS SINGLE-WALL SEE 40-026-M568 FOR RISE AND NOZZLE CONFIGURATION 2. MEDIUM PRESSURE STEAM AND CONDENSATE (MPS) PIPING:ASTM A53B SCH STAINLESS STEEL PIPE WITH BUTT WELD FITTINGS AND AS SPECIFIED <br /> HPU ROOM FLUID SADDLE TANK MGR: ECKSTROM 40 BLACK STEEL PIPE WITH BUTT-WELDED FITTINGS AND CLASS 150 FLANGES, <br /> EXCEPT SCH 80 WITH 150# MALLEABLE IRON THREADED FITTINGS FOR 2"AND 3. 4" HYDRAULIC FLUID TANK FILL PIPING:ASTM A312 TYPE 304L SCH 10 <br /> UL-142 CUSTOM STAINLESS STEEL CONSTRUCTION SMALLER STAINLESS STEEL PIPE WITH MSS SP119 BELLED-END STAINLESS STEEL <br /> SOCKET WELD FITTINGS <br /> A/P POS 2 INDUSTRIAL SINGLE-WALL SEE 40-026-M568 FOR RISE AND NOZZLE CONFIGURATION <br /> ST-2 HPU ROOM WASTE 1500 60" 125" TYPE 304E SS SADDLE TANK MGR: ECKSTROM 3. CHILLED WATER (WITH ASTM A536 GROOVED-END <br /> PIPING:ASTM A53B SCH 40 BLACK STEEL PIPE <br /> ND DUCTILE IRON PIPE FITTINGS, RIGID 4. 1 1/2" HYDRAULIC FLUID TRANSFER PIPING:ASTM A312 TYPE 304E SCH 40 <br /> COUPLINGS,AND FLANGE ADAPTERS WITH EPDM GASKETS, EXCEPT 150# STAINLESS STEEL PIPE WITH STAINLESS STEEL SOCKET WELD FITTINGS AND <br /> LANDING AQUEOUS SINGLE-WALL STAINLESS STEEL CONSTRUCTION THREADED MALLEABLE IRON FITTINGS FOR 2"AND SMALLER. COAT AS SPECIFIED <br /> ST <br /> GEAR PIT WASH 2O00 64" 144" TYPE 304E SS SEE 40-026-M582 FOR RISER AND NOZZLE GROOVED-END GASKET SURFACES WITH VICTAULIC LUBRICANT. INSULATE WITH <br /> 3 SADDLE TANK POSITION 4 WASTE CONFIGURATION 5. HYDRAULIC PIPING SHALL BE FASTENED TO SUPPORT STRUTS WITH <br /> 1" FIBERGLASS WITH FACTORY-APPLIED ALL-SERVICE JACKET. PROVIDE <br /> FACTORY-MOLDED PVC COVERS FOR VALVES AND FITTINGS. CUSHIONED CLAMPS, B-LINE NO. 62000 SERIES CLAMP WITH 61999 <br /> LANDING AQUEOUS STAINLESS STEEL CONSTRUCTION VIBRA-CUSHION <br /> ST SINGLE-WALL <br /> GEAR PIT WASH 3000 64" 216" TYPE 304L SS SEE 40-026-M582 FOR SIMILAR RISER AND NOZZLE 4. DRAIN (D) PIPING:ASTM A53B SCH 40 BLACK STEEL PIPE WITH 150# <br /> 4 POSITION 3 WASTE SADDLE TANK CONFIGURATION. TANK RELOCATED FROM 40-024. MALLEABLE IRON FITTINGS 6. PRESSURE TEST HYDRAULIC FLUID PIPING WITH AN APPROVED FLUID: <br /> SUPPLY PIPING:TEST AT 8500 PSIG <br /> 5. PRESSURE TEST STEAM PIPING WITH CLEAN WATER: RETURN PIPING:TEST AT 1500 PSIG <br /> HPS PIPING:TEST AT 300 PSIG TANK FILL AND TRANSFER PIPING:TEST AT 125 PSIG <br /> �` WASTE <br /> �` MPS PIPING: TEST AT 50 PSIG DURATION: 1 HOUR WITHOUT LOSS IN PRESSURE <br /> INDUSTRIAL VV ASTE PUMPS DURATION: HOLD PRESSURE TO INSPECT ALL JOINTS AND CONNECTIONS AND IN NO CASE LESS THAN 1 HOUR WITHOUT LOSS IN PRESSURE 7. COLD WATER (CW),AND HOT WATER CIRCULATION (HWC) PIPING:TYPE L <br /> COPPER PIPE WITH COPPER SOCKET JOINT FITTINGS, EXCEPT ROLL-GROOVED <br /> 6. PRESSURE TEST CHILLED WATER PIPING WITH CLEAN WATER: TYPE L COPPER OR TYPE 304 SCH 10 STAINLESS STEEL PIPE AND FITTINGS <br /> MOTOR PIPING: TEST AT 150 PSIG WITH DUCTILE IRON COUPLINGS AND FLANGE ADAPTERS WITH EPDM GASKETS <br /> CAPACITY HEAD INLET DISCHARGE <br /> MARK LOCATION SERVICE TYPE RPM REMARKS DURATION: HOLD PRESSURE TO INSPECT ALL JOINTS AND CONNECTIONS AND FOR 3"AND LARGER. COAT GROOVED-END GASKET SURFACES WITH VICTAULIC <br /> GPM FT WG SIZE SIZE HP ELEC IN NO CASE LESS THAN 1 HOUR WITHOUT LOSS IN PRESSURE LUBRICANT. INSULATE WITH 1" FIBERGLASS WITH FACTORY-APPLIED <br /> ALL-SERVICE JACKET. PROVIDE FACTORY-MOLDED PVC COVERS FOR VALVES <br /> PUMPED SELF-PRIMING AND FITTINGS. EXCEPT PIPE, FITTINGS,AND VALVES IN FINGER TRENCHES AND <br /> IWP-1A, IWP-18 A/P POS 2 INDUSTRIAL CENTRIFUGAL 100 250 3500 1 1/2" 1 1/2" 25 NEMA MG1-31 GOULDS MODEL 3796, CAST IRON BASE MOUNT PRODUCTION POSITIONS 1 AND 2 MAIN FABRICATION TUNNELS SHALL BE <br /> HPU ROOM WASTE SOLIDS HANDLING 460/60/3 FURNISH WITH CASE DRAIN (BECKWITH & KUFFEL) INSULATED WITH CALCIUM SILICATE AND 0.019"STUCCO-EMBOSSED STAINLESS <br /> STEEL JACKET. <br /> WP LANDING AQUEOUS SELF-PRIMING GOULDS MODEL 3796 2x2-10, CAST IRON BASE 8. COMPRESSED AIR (A) PIPING:ASTM A53B SCH 40 BLACK STEEL PIPE WITH <br /> 2A GEAR PIT WASH CENTRIFUGAL 80 75 1760 2 2" 7.5 460/60/3 MOUNT FURNISH WITH CASE DRAIN (BECKWITH ASTM A536 GROOVED-END DUCTILE IRON FITTINGS, RIGID COUPLINGS,AND <br /> POS 4 WASTE SOLIDS HANDLING & KUFFEL 1�' FLANGE ADAPTERS WITH EPDM GASKETS, EXCEPT 150 THREADED MALLEABLE <br /> HVAC DUCTWORK SPECIFICATIONS IRON FITTINGS FOR 2"AND SMALLER. COAT GROOVED-END GASKET SURFACES <br /> WP LANDING AQUEOUS SELF-PRIMING GOULDS MODEL 3796 2x2-10, CAST IRON BASE WITH VICTAUUC LUBRICANT. <br /> 2B GEAR PIT WASH CENTRIFUGAL 80 75 1760 2" 2° 7.5 460/60/3 MOUNT FURNISH WITH CASE DRAIN (BECKWITH <br /> POS 4 WASTE SOLIDS HANDLING & KUFFEL) 1. PROVIDE FABRICATED STEEL MEMBER SUPPORTS AS REQUIRED BY 9. DRAIN (D)AND INDUSTRIAL WASTE(IW) PIPING:ASTM A53B SCH 40 BLACK <br /> MANUFACTURER'S INSTALLATION INSTRUCTIONS AND AS INDICATED ON DRAWINGS STEEL PIPE WITH ASTM A536 GROOVED-END DUCTILE IRON NON-COATED <br /> WP LANDING AQUEOUS SELF-PRIMING NEMA MG1-31 GOULDS MODEL 3796, CAST IRON BASE AWWA WYE FITTINGS, RIGID COUPLINGS,AND EPDM GASKETS, EXCEPT 150# <br /> 3A GEAR PIT WASH CENTRIFUGAL 100 250 3500 1 1/2" 1 1/2" 25 MOUNT. FURNISH WITH CASE DRAIN. 2. IF REQUIRED FOR INSTALLATION OF DUCTS AND EQUIPMENT, PROVIDE THREADED MALLEABLE IRON FITTINGS FOR 2"AND SMALLER. COAT <br /> ROB 3 WASTE SOLIDS HANDLING 460/60/3 RELOCATED FROM THE 40-024. ADDITIONAL STRUCTURAL MEMBERS BETWEEN COLUMNS,JOISTS,AND GROOVED-END GASKET SURFACES WITH VICTAULIC LUBRICANT. <br /> STRUCTURAL FRAME TO MEET SUPPORT REACTIONS (FORCES, MOMENTS, <br /> LANDING AQUEOUS SELF-PRIMING NEMA MG1-31 DEFLECTIONS <br /> WE GOULDS MODEL 3796, CAST IRON BASE 10. PUMPED INDUSTRIAL WASTE (PIW) PIPING:ASTM A536 SCH 40 BLACK STEEL <br /> 3B GEAR PIT WASH CENTRIFUGAL 100 250 3500 1 1/2" 1 1/2" 25 MOUNT. FURNISH WITH CASE DRAIN. BUTT-WELDED CARRIER PIPE AND ASTM A53B BLACK STEEL SCH 10 <br /> POS 3 WASTE SOLIDS HANDLING 460/60/3 RELOCATED FROM THE 40-024. 3. DUCTS INDICATED WITHOUT DIMENSIONS SHALL BE SIZED PER UPSTREAM DUCT CONTAINMENT PIPE WITH ASTM A536 GROOVED-END DUCTILE IRON FITTINGS, <br /> VICTAULIC STYLE 75 FLEXIBLE COUPLINGS WITH EPDM GASKETS,AND AS <br /> 4. ALL DUCTWORK IS SHOWN DIAGRAMMATICALLY AND DOES NOT SHOW ALL INDICATED. FOLLOW VICTAULIC RECOMMNEDATIONS FOR SUPPORTING <br /> OFFSETS, DROPS, RISES, OR RUNS. ALLOW FOR ROUTING OF DUCTWORK TO FLEXIBLE-COUPLED PIPING SYSTEMS. COAT GROOVED GASKET SURFACES WITH <br /> AVOID OBSTRUCTIONS. EXACT LOCATIONS ARE SUBJECT TO APPROVAL. VICTAULIC LUBRICANT. <br /> 5. ARRANGE HVAC EQUIPMENT SO THAT ACCESS CLEARANCES INDICATED BY 11. PRESSURE TEST COMPRESSED AIR PIPING WITH CLEAN DRY AIR AT 150 PSIG. <br /> DRAWINGS, REQUIRED BY CODES, OR RECOMMENDED BY MANUFACTURER ARE TEST ALL JOINTS BY BRUSHING WITH SOAPY WATER SOLUTION. <br /> PROVIDED DURATION: HOLD PRESSURE TO INSPECT ALL JOINTS AND CONNECTIONS AND <br /> �` <br /> 6. PROVIDE A VOLUME DAMPER FOR EACH SUPPLY AIR OPENING IN NO CASE LESS THAN 1 HOUR WITHOUT LOSS IN PRESSURE. <br /> BOOSTER PUMP 12. PRESSURE TEST WATER AND PIW CARRIER PIPING WITH CLEAN FRESH <br /> 7. PROVIDE CONICAL SPIN-IN FITTINGS FOR 90-DEGREE ROUND DUCT BRANCHES DOMESTIC WATER AT 150 PSIG. <br /> FROM RECTANGULAR SUPPLY DUCTWORK. DO NOT USE STRAIGHT TEE DURATION: HOLD PRESSURE TO INSPECT ALL JOINTS AND CONNECTIONS AND <br /> MARK LOCATION SERVICE TYPE CAPACITY HEAD RPM INLET DISCHARGE <br /> MOTOR REMARKS FITTINGS. IN NO CASE LESS THAN 1 HOUR WITHOUT LOSS IN PRESSURE. <br /> GP S IZ Z 8. DUCTWORK STATIC PRESSURE AND SEAL CLASS, BASED ON SMACNA AS 13. COLD WATER (CW) FLUSHING AND STERILIZATION:AFTER COMPLETION OF NEW <br /> FOLLOWS: COLD WATER PIPING INSTALLATION, FLUSH PIPING THOROUGHLY AND STERILIZE <br /> ^ i EiPdF � Gj}JHRIZoss--GRi iI5-i SI;Rlps' 04 s;"tIHIrFssss AS FOLLOWS: 24-HR STERILIZATION CONTACT TIME WITH 50 RPM CHLORINE <br /> �cmrcn ooric88 52 3569 2" _-___ WE - PARTS WIT''- - -- - - -___ _ ___ - _ CONCENTRATION.AFTER STERILIZATION PERIOD, OPEN VALVES SEVERAL TIMES <br /> c��,=P;-� -- DUCT SYSTEM STATIC PRESSURE SEAL CLASS FOLLOW BY FLUSHING WITH CLEAN WATER UNTIL RESIDUAL CHLORINE IS LESS <br /> A. SUPPLY DUCTWORK +10" A THAN 0.2 RPM. <br /> B. EXHAUST DUCTWORK +3" A 14. TRAP PRIMERS: PROVIDE TRAP PRIMERS AND PIPING FOR ALL FLOOR DRAINS <br /> C. RETURN DUCTWORK -2" A <br /> PACKAGE LIQUID BAG FILTERS C <br /> MARK LOCATION SERVICE TYPE MICRON FILTER MODULES ASSEMBLY MAX. DROP CONNECTION REMARKS REMOVAL NOTES <br /> RATING EFFICIENCY QUANTITY GPM FT WG SIZE <br /> A/P POS 2 PUMPED ASME-150# FILTRATION SYSTEMS C-424-V. FURNISH WITH DRAIN <br /> FI-1 INDUSTRIAL PACKAGE MODULAR 100 97% 4 280 100 4" VALVES, VENT VALVES, AND PRESSURE GAUGES TO <br /> HPU ROOM WASTE CARBON STEEL <br /> READ FILTER DIFFERENTIAL (HARRINGTON PLASTICS) <br /> PLUMBING FIXTURE SCHEDULE PUMP <br /> MARK DESCRIPTION WASTE VENT CW HW MO TNT. REMARKS <br /> PUMP AIR PRESSURE <br /> SK-1 HAND WASH-UP SINK 2" 2" 1/2" 1/2" FLOOR SINK SHALL BE ELKAY MODEL CHSP1716C MARK LOCATION REMARKS <br /> CAP. INLET DISCH INLET PRESSURE REMOVAL <br /> SERVICE SINK 3" 2" 3/4' 3/4" 48„* <br /> SS-1 SERVICE SINK 3" 2" 3/4" 3/4" FLOOR SINK SHALL BE JUST MODEL NSFB-230-24RL GPM HEAD FT. SIZE SIZE MIN MAX <br /> (PSIG) (PSIG) <br /> SPRAY NO SHALL BE T&S BRASS MODEL P 1st TER PUMP SHALL BE YAMADA MODEL NDP-158PT <br /> SS SERVICE SINKINK SHALL BE JUST MODEL NSFB-148 148 /2 1/2" 20 100 PROVIDE PRESURE REGULARTOR WATTS MODEL B11-04DJC <br /> 1 FAUCET SHALL BE JUST MODEL JPR-309 <br /> EW EMERGENCY EYE WASH 2" 1-1/2" 1/2" -- -- EYE/FACE WASHES SHALL BE HAWS MODEL 7360B <br /> * CL OF FAUCETS PfK� <br /> PROFESSIONAL STAMP & SIGNATURE EERS ISSUED FOR CONSTRUCTION <br /> APPLIES TO WORK WITHIN THE CLOUDED Seattle//Spokane//Baltimore DESIGN BY FSi L 03.1424 <br /> REVISION AREAS ONLY AS INDICATED <br /> SYM REVISION BY APPROVED DATE SYM REVISION BY APPROVED DATE DRAWN DATE SUBTITLE CURRENT REVISION SYMBOL DATE <br /> M. CNq ACCEPTABILITY D.ABENOJA 07.03.06 EQUIPMENT SCHEDULES AND SPECIFICATIONS-REMOVAL W8861360 G 03.14.24 <br /> ORIG 787 FA RECORD SET 555886 WH C. LARSON 06.22.07 THIS DESIGN AND/OR H K <br /> SPECIFICATION IS APPROVED J. MENIKETTI 07.03.06 SHEET <br /> A 787 SURGE LINE WH SAG 10,15.12 y APPROVED BY DEPT. DATE J. MENIKETTI 07.03.06 TITLE 737 NORTH LINE - 40-026 WING TANK CLEANOUT M 01 R <br /> BOE/NG NECKED <br /> B AQUEOUS WASH POS 3 - RECORD WBS 252 JAL FSG 12.19.18 , J.JENKINS 07.03.06 BUILDING 40-026 <br /> C 737 NORTH LINE- 40-026 WING TANK CLEANOUT W8861360 FSi KMC 03.14.24 ssYoxnL0.cac APPROVED JOB NO. 555886 COMP NO. <br /> APPROVED MECHANICAL MASTER EVERETT, WA DWI NO. 40-026-MOIR <br />