Laserfiche WebLink
RRFB PEDESTRIAN SAFETY October 31, 2025 <br />STATE FUND # HLP-PB25(004) <br />WO 3807 <br />Page 79 of 82 <br />Category 2: Sensitive information <br />1 <br />2 Signal Controller <br />3 <br />4 NEMA control equipment shall be Siemens NEMA ATC M62 controllers. All <br />5 signal controllers will be a model listed by the software manufacturer to operate <br />6 Siemens SEPAC traffic signal controller software, most current version. All signal <br />7 controllers will also be a model listed by the software manufacturer to be fully <br />8 compatible with the Siemens TACTICS Central Traffic Management Software. <br />9 <br />10 <br />11 9-29.13(4) Traffic Signal Controller Software <br />12 Section 9-29.13(4) is supplemented with the following: <br />13 <br />14 Signal Controller Software <br />15 Siemens SEPAC control software shall be provided for each signal controller on <br />16 this project, most current LINUX version. All signal controller software will be <br />17 fully compatible with the Siemens TACTICS Central Traffic Management <br />18 Software. <br />19 <br />20 <br />21 <br />22 KEL 9-29.13(10)A NEMA AUXILIARY EQUIPMENT.RTF <br />23 9-29.13(10)A Auxiliary Equipment for NEMA Controllers <br />24 Section 9-29.13(10)A is supplemented with the following: <br />25 <br />26 Controller Auxiliary Equipment <br />27 Traffic signal control equipment to be furnished shall be provided with: <br />28 <br />29 1. Flash Indication Jumper Plugs <br />30 One for each vehicle display load switch socket (eight minimum). <br />31 Provides quick and easy change of indications, either red or yellow, <br />32 for display during flashing operations. <br />33 <br />34 2. Load Switches <br />35 All load switches shall be model 200 units equipped with <br />36 replaceable solid state relay modules. Load switches shall be <br />37 provided for all phases, not just phases used with the current <br />38 configuration. <br />39 <br />40 3. Malfunction management Unit <br />41 For NEMA controllers the MMU shall be MMU2-16LE type. The <br />42 conflict monitor shall be capable of supporting the flashing yellow <br />43 arrow signal head display configuration. The conflict monitor shall <br />44 have a RJ-45 connector on the front panel for Ethernet <br />45 connectivity. <br />46 <br />47 4. Loop Detectors <br />48 Loop Detectors shall be EDI LMD 622T or 624T. Each cabinet <br />49 shall come with the number of loop detectors shown in the plans