1 2 3 4 5 6 7
<br /> V -
<br /> SYMBOLS AND ABBREVIATIONS
<br /> SPECIFICATIONS arQ�
<br /> 4.
<br /> SECTION 260100-GENERAL PROVISIONS SYSTEMS IN CONCEALED CEILING SPACES TO SWITCHBOARDS, PANELBOARDS, COMMUNICATION AND CIRCUITS RECEPTACLES CIRCUITS GENERAL NOTES /� m'
<br /> SIGNALING AND SYSTEM CONTROL PANELS. PROVIDE NEW CONDUIT SYSTEMS IN CEILING SPACES OF ° 'Y NOA l V m o a
<br /> PROVIDE COMPLETE AND FULLY OPERATIONAL ALL ELECTRICAL SYSTEMS WITHIN THE RENOVATED FLOOR BELOW REMODEL FLOORS. REMOVE AND RELOCATE ELECTRICAL EQUIPMENT IN THE WAY OF a A �M
<br /> AREA,ALONG WITH POWER CONNECTIONS TO EQUIPMENT FURNISHED BY OWNER. OTHER TRADES WORK INSTALLED UNDER THIS CONTRACT. SPACES ABOVE EXISTING CEILINGS ARE DUPLEX RECEPTACLE 120V �«N- RACEWAY CONCEALED IN CEILING OR WALL.HASH MARKS 1. COMPLY WITH THE NATIONAL ELECTRICAL CODE AS ADOPTED AND AMENDED BY THE LOCAL � -a t
<br /> HIGHLY CONGESTED. ROUTE WIRING AROUND OBSTRUCTIONS AND PROVIDE PULL BOXES PER CODE. INDICATE NUMBER OF WIRES. 12 AWG WIRE UNLESS OTHERWISE AUTHORITY HAVING JURISDICTION. y m ';a.
<br /> A.CODES: DOUBLE DUPLEX RECEPTACLE 120V NOTED.EXPOSED RACEWAY IS ALLOWED ONLY WHERE NOTED.
<br /> CONFORM TO THE NATIONAL ELECTRICAL CODE AND ALL OTHER CODES AND REGULATIONS AS I.EXISTING MATERIALS S
<br /> ADOPTED AND AMENDED BY THE STATE OF WASHINGTON AND CITY OF EVERETT INCLUDING THE ALL MATERIALS WHICH ARE A PART OF THE BUILDING SHALL REMAIN THE PROPERTY OF THE OWNER. o a e
<br /> F AMERICANS MATH DISABILITIES ACT(ADA). N/A RECEPTACLE 208V OR 24OV,SINGLE PHASE(TWIST LOCK) HOT(SHORT HASH MARK)
<br /> J.EXISTING MATERIALS TO BE REINSTALLED 3 N f3 0
<br /> B.PERMITS AND FEES EXISTING MATERIALS AND EQUIPMENT (EXCEPT INTERIOR, UNDAMAGED RACEWAYS) THAT ARE + NEUTRAL(LONG HASH MARK) o
<br /> CONTRACTOR TO OBTAIN AND PAY FOR ALL REQUIRED LICENSES,PERMITS AND INSPECTIONS. REMOVED AS A PART OF THE WORK OR STORED IN SURPLUS SHALL NOT BE REINSTALLED AS A
<br /> PART OF THE NEW SYSTEMS UNLESS SPECIFICALLY NOTED OR AUTHORIZED IN WRITING BY THE RECEPTACLE TYPES GROUND WIRE(JOGGED HASH MARK)
<br /> C.COORDINATION: OWNER. FORWARD A COPY OF THE AUTHORIZATION TO THE ENGINEER. THE REQUIREMENTS OF THE EXISTING RACEWAY(IF HASH MARKS ARE SHOWN,PULL NEW
<br /> CONTRACTOR TO COORDINATE ELECTRICAL WORK WITH OTHER TRADES. SPECIFICATIONS(I.E.,CONDITION,INSTALLATION,TESTING,ETC.)SHALL APPLY AS IF THE MATERIALS G CONDUCTORS)
<br /> WERE NEW,FURNISHED BY THE CONTRACTOR. GROUND FAULT CIRCUIT INTERRUPTER
<br /> D.WARRANTY: - RACEWAY BELOW SLAB OR UNDERGROUND
<br /> PROVIDE WARRANTY FOR ONE FULL YEAR AFTER COMPLETION. K.EXISTING MATERIALS NOT TO BE REINSTALLED T ABBREVIATIONS
<br /> ALL MATERIAL TO BE DEMOLISHED AND DEBRIS SHALL BE LEGALLY DISPOSED OF BY THE GD TAMPER RESISTANT
<br /> E.CONTRACT DRAWINGS: CONTRACTOR. RACEWAY UP
<br /> RACEWAYS AND OUTLET BOXES ARE SHOWN DIAGRAMMATICALLY ONLY AND THE LAYOUT DOES NOT A,AMP AMPERE LR LEGALLY REQUIRED
<br /> NECESSARILY SHOW THE TOTAL NUMBER OF RACEWAYS NOR THEIR EXACT LOCATION. THE L.EXISTING RACEWAYS PANELBOARDS RACEWAY DOWN ABV ABOVE LS LIFE SAFETY BRANCH
<br /> CONTRACTOR SHALL PROVIDE ALL RACEWAYS,BOXES,CABLES,AND OTHER MATERIALS REQUIRED FOR THE CONTRACTOR MAY REUSE THE EXISTING RACEWAYS IF NO OTHER SYSTEMS OCCUPY THE AC 3°ABOVE COUNTER BACKSPLASH MAG MAGNETIC
<br /> THE COMPLETE ELECTRICAL SYSTEMS SHOWN OR INDICATED ON THE CONTRACT DRAWINGS. RACEWAY, RACEWAYS AND ENCLOSURES ARE ELECTRICALLY AND MECHANICALLY CONTINUOUS AND RACEWAY STUB-OUT WITH BUSHING
<br /> NEW WIRING IS PROVIDED. NO WARRANTY IS MADE AND THE CONTRACTOR SHALL ASSUME THE RISK i 208V SYSTEM PANELBOARD ACH ABOVE COUNTER HEIGHT MCC MOTOR CONTROL CENTER _
<br /> F.RECORD DRAWINGS: OF USING EXISTING OUTLET BOXES AND RACEWAY SYSTEMS. CIRCUIT CONTINUATION MTD MOUNTED E
<br /> AT THE CONCLUSION OF CONTRACT WORK, PROVIDE THE OWNER WITH A COMPLETE SET OF AFF ABOVE FINISHED FLOOR a
<br /> REPRODUCIBLE DRAWINGS WITH ALL CHANGES CLEARLY AND LEGIBLY MARKED TO REFLECT THE M.EXISTING CONDITIONS AG ABOVE GRADE MW MICROWAVE
<br /> AS-BUILT CONDITIONS. THESE DRAWINGS SHALL BE LABELED "AS-BUILT' AND CERTIFIED BY THE EXAMINE THE STRUCTURE, BUILDING, AND CONDITIONS UNDER WHICH ELECTRICAL WORK IS TO BE HOMERUN TO PANEL OR LOCATION NOTED
<br /> CONTRACTOR FOR ACCURACY. INSTALLEDFOR CONDITIONS PROCEED NTH
<br /> RIMEN AL TO DE ENT ON PROPER E AND S OR TIMELY
<br /> COMPLETION
<br /> OF HAVE B Qj �j JUNCTION BOX ELECTRICAL
<br /> ELECTRICAL RISER AIC AMPERE INTERRUPTING CAPACITY N NEUTRAL V
<br /> WORK. DO
<br /> ATS AUTOMATIC TRANSFER SWITCH NIC NOT IN CONTRACT
<br /> G.MAINTENANCE MANUALS: CORRECTED. REPORT DEFICIENCIES OR DETRIMENTAL CONDITIONS OF EXISTING ELECTRICAL WORK
<br /> COMPLETE FOR EVERY SYSTEM. HARDBOARD COVERS WITH 3 RING BINDERS. WHICH MIGHT BE UNSUITABLE TO CONNECT NTH OR RECEIVE OTHER WORK. FAILURE TO SO REPORT FEEDER SIZE IDENTIFICATION ® PULL BOX AWG AMERICAN WIRE GAUGE TITS NOT TO SCALE f
<br /> SHALL CONSTITUTE ACCEPTANCE OF OTHER WORK AS BEING FIT AND PROPER FOR THE RECEPTION AV,A/V AUDIO/VISUAL OPER OPERATER/OPERABLE r
<br /> H.QUALITY ASSURANCE: OF ELECTRICAL WORK.
<br /> AVAILABLE FAULT CURRENT IDENTIFICATION
<br /> CB CIRCUIT BREAKER OP01 OWNER PROVIDED OWNER INSTALLED
<br /> 1.MATERIALS AND SYSTEMS: PROVIDE ILL LISTED AND LABELED MATERIALS WHERE LISTING SERVICE N.EXISTING SYSTEMS MAINTAINED • • ARRESTOR,SURGE CCTV CLOSED CIRCUIT TELEVISION OS OCCUPANCY SENSOR,OPTIONAL I<
<br /> IS NORMALLY PROVIDED FOR A GIVEN PRODUCT. PROVIDE NEW AND SHIP TO JOBSITE IN ORIGINAL GENERAL a
<br /> MANUFACTURER'S CONTAINERS OR BUNDLES. REROUTE EXISTING CIRCUITS THAT ARE INTERRUPTED AS A RESULT OF THIS CONTRACT THAT SERVE CKT CIRCUIT STANDBY
<br /> 2.WORKMANSHIP: ARRANGE WORK TO OBTAIN COORDINATED I DEVICES TO REMAIN IN SERVICE. ua ARRESTOR,LIGHTNING WORK DEFINITION CLG CEIUNG PB PULLBOX
<br /> 3 DRAWINGS: FOR PURPOSE OF CLARITY AND LEGIBILITY, THE Im
<br /> Y, THE TON.DRAWINGS ARE ESSENTIALLY 1.POWER CIRCUITS AUTOMATIC TRANSFER SWITCH ® FLAG NOTE CM CEIUNG MOUNTED PNL PANEL,PANELBOARD
<br /> . COMM COMMUNICATIONS POS POSITION/POINT OF SALE
<br /> E DIAGRAMMATICAL ONLY. TRACE OUT AND IDENTIFY LOADS AND SYSTEMS BEING SERVED. BUS SPACE PROVIDE TEMPORARY WIRING,SCHEDULE OUTAGE AND RECONNECT LOADS TO TEMPORARY WIRING. SPACE ® REVISION IDENTIFICATION C CONDUIT R RACEWAY
<br /> 4. ROUTING: EXACT ROUTING OF WIRING AND LOCATIONS OF OUTLETS, PANELS, ETC. SHALL BE PROVIDE NEW WIRING IN NEW LOCATION. - BUS DUCT CO CONDUIT ONLY RO RACEWAY ONLY
<br /> GOVERNED BY STRUCTURAL CONDITIONS, OBSTRUCTIONS AND EXISTING CONDITIONS. ENGINEER SCHEDULE OUTAGE,DISCONNECT TEMPORARY WIRING,AND CONNECT LOADS TO NEW WIRING. ®EQUIPMENT IDENTIFICATION
<br /> RESERVES THE RIGHT AT NO INCREASE IN PRICE,TO MAKE REASONABLE CHANGES IN LOCATIONS OF CTRL CONTROL RECEPT RECEPTACLE
<br /> ELECTRICAL ITEMS EXPOSED AT CEILING AND/OR ON WALLS. 2.SIGNAL AND COMMUNICATION SYSTEMS BUSWAY END TAP BOX / EQUIPMENT IDENTIFICATION o
<br /> CU COPPER SLV SLEEVE
<br /> I.COORDINATION: TRACE OUT AND IDENTIFY DEVICE AND SYSTEMS BEING SERVED. ♦ CABLE TO BUS CONNECTION D8Q DETAIL REFERENCE D DATA SPECS SPECIFICATIONS
<br /> PROVIDE TEMPORARY WIRING TO MAINTAIN OPERATION OF SYSTEM THROUGHOUT FACILITY. Shoot/ DED DEDICATED SW SWITCH
<br /> 1. WORK OUT ALL "TIGHT" CONDITIONS INVOLVING WORK UNDER THIS CONTRACT IN ADVANCE OF SCHEDULE OUTAGE AND CONNECT TO TEMPORARY WIRING AND TEST SYSTEM. I CAPACITOR Det/ DETAIL REFERENCE W/ORIGINATING SHEET REFERENCE
<br /> INSTALLATION. PROVIDE NEW WIRING AND NEW EQUIPMENT IN PROJECT AREA. Pmeetp D osh .&.t/ DEV DEVICE SWBD SWITCHBOARD
<br /> SCHEDULE OUTAGE,DISCONNECT TEMPORARY HIRING AND CONNECT NEW HIRING AND NEW � CONTACT,NORMALLY OPEN AND NORMALLY CLOSED DN DOWN TELECOM TELECOMMUNICATIONS
<br /> 2.CONTRACTOR SHALL COORDINATE ALL OWNER-FURNISHED EQUIPMENT LOCATIONS AND CONNECTION ��/ r
<br /> REQUIREMENTS WITH OWNER'S VENDOR PRIOR TO ROUGH-IN. CONTRACTOR SHALL MAKE ALL FINAL EQUIPMENT AND TEST SYSTEM. s"a sheet/ SECTION REFERENCE EF ENTRANCE FACILITY TV TELEVISION
<br /> LINE VOLTAGE CONNECTIONS TO EQUIPMENT AS REQUIRED. CIRCUIT BREAKER -- ER EQUIPMENT ROOM ERGENCY ROOM TYP TYPICAL
<br /> 0.DEMOLITION � zl8
<br /> 3.CONFIRM ALL ELECTRICAL EQUIPMENT AND SYSTEM PROGRAMMING NOMENCLATURE REQUIREMENTS SIGNALING AND COMMUNICATION SYSTEMS, LIGHTING FIXTURES, OTHER ELECTRICAL EQUIPMENT FREE CIRCUIT BREAKER,DRAWOUT a SECTION REFERENCE W/ORIGINATING SHEET REFERENCE FA FIRE ALARM UP UNDER FLOOR <
<br /> 'NTH THE OWNER PRIOR TO SUBMITTALS AND ROUGH-IN. CONFORM TO ALL NAMING CONVENTIONS STANDING OR SURFACE MOUNTED, RACEWAY(EXPOSED) AND CONDUCTORS; WHICH ARE NO LONGER PlanSheetp DetShe t/
<br /> DEFINED THROUGHOUT THE PROJECT.
<br /> IN SERVICE PRESENTLY OR AS A RESULT OF THIS CONTRACT SHALL BE REMOVED. UNUSED FLUSH CIRCUIT BREAKER,DRAWOUT,MEDIUM VOLTAGE I FB FLOOR BOX UG UNDER GROUND
<br /> MOUNTED DEVICES,OUTLET AND OTHER BOXES IN FINISHED AREAS SHALL BE REMOVED FROM WALL o FBOIC FURNISHED BY OTHERS,INSTALLED LION UNLESS OTHERWISE NOTED
<br /> AND THE REMAINING HOLE PATCHED TO MATCH ADJACENT WALL SURFACES. UNUSED RACEWAYS GF CIRCUIT BREAKER,GFl / ELEVATION REFERENCE
<br /> SECTION 260126-TESTING AND SLEEVES EMBEDDED IN CONCRETE SHALL BE CUT FLUSH AT CEILING, FLOOR OR WALL AND 9--� BY CONTRACTOR V VOLT OR VOICE
<br /> FILLED WITH GROUT. ALL UNUSED RACEWAYS ABOVE CEILINGS SHALL BE REMOVED. CONTRACTOR GF FOC FACE OF COLUMN VEL VERIFY EXACT LOCATION
<br /> A.FURNISH ALL LABOR AND TEST EQUIPMENT AS REQUIRED UNDER THIS SECTION. SHALL REMOVE ALL FLOOR, WALL OR CEILING MOUNTED ELECTRICAL EQUIPMENT IN THE"DEMOLITION CIRCUIT BREAKER,GFl WITH DRAWOUT PROJECT NORTH REFERENCE
<br /> AREA" INDICATED ON THE DRAWINGS EVEN IF THE EQUIPMENT/OR DEVICE IS NOT SHOWN ON THE a D G,GND GROUND W WIRE,WATT,OR WALLPHONE
<br /> B.FACILITIES ENGINEERING REPRESENTATIVE NEEDS TO BE PRESENT FOR FINAL TESTING. PROJECT DRAWINGS. IF CONTRACTOR QUESTIONS WHETHER A PARTICULAR DEVICE IS TO BE CIRCUIT BREAKER,MAGNETIC OVERLOAD GFl,GFCI GROUND FAULT CIRCUIT INTERRUPTER WAP WIRELESS ACCESS POINT
<br /> REMOVED NOTIFY THE ENGINEER NOTING TYPE AND LOCATION OF DEVICE. IF SO DIRECTED THE w✓ PROJECT NORTH REFERENCE W/TRUE NORTH REFERENCE HH HAND HOLE WP WEATHERPROOF
<br /> C. TEST ALL PANELS AND/OR BRANCH CIRCUITS FOR GROUNDS OR SHORTS. REPAIR DEFECTIVE CONTRACTOR SHALL MAINTAIN THE EXISTING DEVICE IN SERVICE WITHOUT ANY CHANGE IN CONTRACT t:s CIRCUIT BREAKER,NETWORK PROTECTOR a D
<br /> WIRING AS REQUIRED. TEST EACH INDIVIDUAL CIRCUIT AT PANEL FOR PROPER OPERATION. PRICE.
<br /> NEW WORK HP HORSEPOWER XFMR TRANSFORMER a)
<br /> D.AT COMPLETION OF WORK,PROVIDE WRITTEN CERTIFICATION THAT ALL SYSTEMS ARE FUNCTIONING P.POWER OUTAGES �--�(J CIRCUIT BREAKER,THERMAL OVERLOAD J-BOX JUNCTION BOX 0 PHASE -
<br /> PROPERLY WITHOUT DEFECTS. 1. SCHEDULED OUTAGES. THE EXISTING FACILITY WILL CONTINUE ITS NORMAL OPERATION DURING B®S FUSE OR CURRENT LIMITER EXISTING Permit/Seal
<br /> THE CONSTRUCTION WORK; THEREFORE IT IS REQUIRED THAT THE CONTRACTOR SCHEDULE
<br /> ELECTRICAL SYSTEM(S) OUTAGES WITH THE OWNER. SUBMIT A WRITTEN REQUEST FOR A POWER ---- FUTURE
<br /> SECTION 260500-BASIC MATERIALS AND METHODS OUTAGE AT LEAST ONE WEEK IN ADVANCE IDENTIFYING THE AREAS, AND SYSTEMS THAT WILL BE FUSE(ISOLATING) .yL WA C'
<br /> D AFFECTED,TIME AND DURATION OF THE POWER OUTAGE. THE CONTRACTOR SHALL RECEIVE WRITTEN �� =xx= REMOVE EXISTING ELECTRICAL EQUIPMENT 3�w°
<br /> INCLUDES GENERAL REQUIREMENTS FOR MATERIALS AND INSTALLATION METHODS, CUTTING BUILDING AUTHORIZATION TO PROCEED WITH THE OUTAGE AND SHALL RE-NOTIFY THE OWNER VERBALLY AT �� FUSED SWITCH e z
<br /> CONSTRUCTION,PAINTING,CLEAN-UP,AND WORKMANSHIP. LEAST ONE HOUR PRIOR TO THE OUTAGE AND ALSO NOTIFY THE OWNER WHEN THE OUTAGE IS
<br /> COMPLETED. i GROUND
<br /> A.MATERIALS: -
<br /> ALL MATERIALS SHALL BE NEW FREE FROM DEFECTS, AND SHALL HAVE BEEN TESTED AND LISTED 2. UNSCHEDULED OUTAGES IN THE EVENT THAT THE CONTRACTOR'S WORK CAUSES OR eJ_ PUSHBUTTON A901 'Fc SSh.4 t"4
<br /> BY UNDERWRITERS LABORATORIES OR OTHER APPROVED TESTING ORGANIZATION AND SHALL BE SO CONTRIBUTES TO AN UNSCHEDULED SYSTEM(S) OUTAGE (OR OTHER SYSTEM FAULT), THE L"sIONAL EP��
<br /> LABELED. CONTRACTOR IS RESPONSIBLE FOR IMMEDIATELY CORRECTING THE PROBLEM. INCLUDED (AS • SPLICE 8/1/2025
<br /> B.SUBSTITUTIONS: EXAMPLES)SHALL BE ANY PREMIUM TIME REQUIRED TO STAY ON THE JOB SITE UNTIL PROBLEM IS Q DRAWING LIST
<br /> SHALL BE REVIEWED BY THE ENGINEER. CORRECTED AND AIR FREIGHT FOR PARTS NOT LOCALLY AVAILABLE. STRESS RELIEF,MEDIUM VOLTAGE
<br /> Q.ACCESS TO PERFORM WORK EO.00 SPECIFICATIONS,SYMBOLS AND ABBREVIATIONS
<br /> C.WORKMANSHIP: CAREFULLY REMOVE,STORE OR TEMPORARILY HANG AND RE-INSTALL IN UNDAMAGED CONDITION ALL ` SWITCH,2-POLE E1.00 LEVEL 4 ELECTRICAL OVERALL PLAN
<br /> SHALL BE OF THE BEST QUALITY AND PERFORMED BY EXPERIENCED ELECTRICIANS UNDER ELECTRICAL EQUIPMENT,LIGHTING FIXTURES AND CEILING TILES WHERE ACCESS TO PERFORM WORK IS
<br /> SUPERVISION OF AN EXPERIENCED FOREMAN. REQUIRED. CLEAN PRIOR TO RE-INSTALLATION. MOO PARTIAL LEVEL 4 ELECTRICAL PLAN
<br /> A SWITCH,3-POLE E8.00 PRIMARY POWER RISER DIAGRAM NORMAL SYSTEM
<br /> D.NOISE TRANSMISSION: R.NEW DEVICES IN REMODEL AREAS �� OUTLET MOUNTING HEIGHTS
<br /> TO PREVENT NOISE TRANSMISSION(IN NEW CONSTRUCTION)BETWEEN ADJOINING ROOMS,ALL DEVICES PROVIDE FLUSH MOUNTING FOR DEVICES IN EXISTING WALLS FISH CONDUIT IN WALL. WHERE 0 E8.01 PRIMARY POWER RISER DIAGRAM EMERGENCY SYSTEM
<br /> ON OPPOSITE SIDES OF WALL TO BE SPACE A MINIMUM OF 6"APART(HORIZONTALLY PREFERRED). EXISTING BOXES ARE INDICATED TO BE REUSED, EXTEND BOX AS NECESSARY AND PROVIDE NEW THERMAL ELEMENT E8.02 D-WING POWER RISER DIAGRAM LEVEL 62 SOUTH WING
<br /> DEVICES AND PLATES. � SPECIAL OUTLET HEIGHTS ARE SHOWN ON THE ELECTRICAL DRAWINGS.IF SPECIAL OUTLET HEIGHTS
<br /> E.BRANCH CIRCUITING: %Aj E8.03 D-WING POWER RISER DIAGRAM LEVELS 81 THRU 3 SOUTH WING ARE NOT SHOWN OR REQUIRED,THEN LOCATE OUTLETS AS NOTED BELOW.OUTLET HEIGHTS ARE
<br /> NO MORE THAN SIX CURRENT CARRYING CONDUCTORS IN ANY ONE(1)HOMERUN. CONTRACTOR IS CAUTIONED THAT THE EXISTING BUILDING CONTAINS CLAY TILE AND CONCRETE ryr.,\ ry.TRANSFORMER E8.04 D-WING POWER RISER DIAGRAM LEVEL 4 SOUTH WING MEASURED FROM THE FINISHED FLOOR TO THE CENTERLINE OF THE OUTLET UNLESS OTHERWISE
<br /> WALLS. NEW DEVICES MAY REQUIRE CUTTING,PATCHING,AND PAINTING OF WALLS AND IT SHALL BE NOTED.
<br /> F.GROUNDING: THE RESPONSIBILITY OF THE CONTRACTOR TO PROVIDE ALL CUTTING, PATCHING AND PAINTING (W TRANSFORMER,CURRENT E8.06 D-WING POWER RISER DIAGRAM LEVELS 8 THRU ROOF SOUTH WING
<br /> PROVIDE SEPARATE GREEN GROUNDING CONDUCTOR IN ALL EQUIPMENT AND RECEPTACLE BRANCH REQUIRED FOR THE INSTALLATION OF THE DIVISION 26 WORK. CONTRACTOR SHALL INVESTIGATE �,�.n.i,� E8.07 D-WING POWER RISER DIAGRAM LEVEL B2 NORTH WING RECEPTACLES 18 INCHES(460 mm)VERTICALLY MOUNTED
<br /> CIRCUITS. SIZE PER NEC. EXISTING AREAS PRIOR TO BID AND SHALL INCLUDE ALL COSTS OF SUCH WORK IN THE BID. TRANSFORMER,ELECTROSTATICALLY SHIELDED,MAGNETIC CORE
<br /> SHOWN E8.08 D-WING POWER RISER DIAGRAM LEVELS 81 THRU 3 NORTH WING
<br /> G.CUTTING AND PATCHING: THIS FACILITY HAS WIRING EMBEDDED IN RACEWAYS IN CONCRETE SLABS. PROVIDE NEW CONCEALED TRANSFORMER,MAGNETIC CORE SHOWN E8.09 D-WING POWER RISER DIAGRAM LEVELS 4 THRU 7 NORTH WING
<br /> DO NOT CUT STRUCTURAL MEMBERS ALL CONSTRUCTION MATERIALS DAMAGED OR CUT INTO WIRING TO LAST OUTLET OR PULL BOX BEFORE HOMERUN TO PANEL. rvw�
<br /> DURING THE INSTALLATION OF THIS WORK MUST BE REPAIRED OR REPLACED WITH MATERIALS BY _ E8.10 D-WING POWER RISER DIAGRAM LEVELS 8 THRU 10 NORTH WING
<br /> SKILLED LABOR EXPERIENCED IN THAT PARTICULAR BUILDING TRADE. E8.11 D-WING POWER RISER DIAGRAM ROOF LEVEL NORTH WING
<br /> SECTION 260519-LOW VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES I I TRANSFORMER,SHIELDED,MAGNETIC CORE SHOWN
<br /> H.PAINTING: L ,J
<br /> TOUCH-UP TO MATCH FACTORY PAINT ANY ELECTRICAL ITEMS SCRATCHED OR MARRED IN SHIPMENT A.PROVIDE ALL WIRE AND CABLE COMPLETE.
<br /> C OR INSTALLATION. COPPER, INSULATED FOR 60OV. ALUMINUM OR COPPER CLAD ALUMINUM CONDUCTORS NOT O AMMETER
<br /> PERMITTED. TYPE THW, THWN/THHN OR XHHW. NUMBER 12 AWG MINIMUM FOR POWER AND
<br /> I.CLEAN UP: LIGHTING CIRCUITS. O CONTACTOR
<br /> CONTINUALLY REMOVE DEBRIS, CUTTINGS, CRATES, CARTONS, ETC. CAREFULLY CLEAN WIRING
<br /> DEVICES,COVER PLATES,LIGHT FIXTURES,ETC.,TO REMOVE PAINT AND PLASTER,ETC. B.SPLICES: O ENGINE-GENERATOR
<br /> SOLDERLESS TYPE ONLY. PRE-INSULATED"TWIST-ON" TYPE(LIMITED TO SIZE#10 AND SMALLER).
<br /> SECTION 260510-EXISTING SYSTEMS BOLT OR COMPRESSION SET TYPE WITH APPLICATION OF PREFORMED INSULATED COVER, HEAT
<br /> KEY INTERLOCK
<br /> A.EXISTING SYSTEMS AND SYSTEMS ADJACENT TO THE WORK SHALL BE INVESTIGATED THOROUGHLY. SHRINKABLE TUBING OR PLASTIC INSULATED TAPE ACCEPTABLE FOR ALL SIZES. O
<br /> ANY DAMAGE RESULTING FROM PERFORMANCE OF WORK UNDER THIS CONTRACT SHALL BE REPAIRED C.TERMINATIONS: O METER
<br /> TO ASSURE CONTINUING OPERATION AND INTEGRITY DURING AND AT COMPLETION OF THE PROJECT COMPRESSION SET, BOLTED OR SCREW TERMINAL CONDUCTORS /12 AND SMALLER SHALL UTILIZE
<br /> AT NO INCREASE IN CONTRACT COST. ANY EXISTING WIRING SERVING DEVICES TO REMAIN IN EYE OR FORKED TONGUE TYPE COMPRESSION SET TERMINATOR WHEN TERMINATION IS TO A BOLTED PM POWER METER
<br /> SERVICE AND WHICH IS INTERRUPTED BY WORK PERFORMED UNDER THIS CONTRACT SHALL BE SCREW SET TYPE TERMINAL BLOCK OR TERMINAL CABINET.
<br /> REROUTED TO MAINTAIN CIRCUIT CONTINUITY. CONTRACTOR SHALL ASSUME THE RISK OF
<br /> MAINTAINING EXISTING SYSTEMS EXCEPT RELOCATION OF HIRING OF#2 AWG AND ABOVE SHALL BE D.COLOR CODE: O RELAY
<br /> CONSIDERED AN ADDITIONAL COST IF NOT SHOWN TO BE RELOCATED. IF SUCH WIRING IS FOUND 480 MARKING BRN,ORG,YELL,GRAY NEUTRAL
<br /> THE CONTRACTOR SHALL NOTIFY ENGINEER OF WIRING LOCATION,REASON IT MUST BE REMOVED AND 208 MARKING BLK,RED,BLU,WHITE NEUTRAL RELAY,GFl
<br /> COST OF RELOCATION AND RECEIVE THE OWNER'S APPROVAL BEFORE PROCEEDING WITH THE WORK. ((��
<br /> THE BUILDING WILL CONTINUE OPERATION DURING THE WORK AND IT IS ESSENTIAL THAT NO SYSTEMS E. BRANCH CIRCUITS: COPPER. SOLID FOR NO.1OAWG AND SMALLER; STRANDED FOR NO.8AWG ® SURGE PROTECTIVE DEVICE
<br /> OPERATION BE INTERRUPTED UNLESS SCHEDULED WITH THE OWNER. CONTRACTOR SHALL ASSUME AND LARGER.
<br /> RESPONSIBILITY FOR UNSCHEDULED INTERRUPTIONS AND EXPEDIENT REPAIR. O VOLTMETER
<br /> F.MULTICONDUCTOR CABLE IS NOT PERMITTED.
<br /> B.ALL CEILING AREAS IN PROJECT AREA. VERIFY THAT EXISTING RACEWAY SUPPORT SYSTEM FOR
<br /> ALL EXISTING TO REMAIN RACEWAYS ABOVE EXISTING OR NEW ACCESSIBLE CEILINGS IS INSTALLED WHM WATT HOUR METER N
<br /> G. ALL 480/277V WIRING WILL BE SEPARATED FROM THE 208/120V WIRING AT ALL TIMES.
<br /> PER CODE.ADD NEW SUPPORTS AS NECESSARY. EXCEPTIONS: MOTOR CONTROLS.
<br /> cl-
<br /> C.EXISTING SYSTEMS CONCEALED Q
<br /> 1.THE ELECTRICAL DRAWINGS SHOW PORTIONS OF THE EXISTING ELECTRICAL SYSTEMS WHICH ARE TO SECTION 260526-GROUNDING C)
<br /> REMAIN, BE REMOVED OR BE MODIFIED AS A PART OF THE CONTRACTOR'S WORK. CONCEALED r
<br /> FEATURES OF THE EXISTING SYSTEMS ARE DERIVED FROM RECORD DRAWINGS AND THE ENGINEER'S PROVIDE A GROUNDING SYSTEM FOR EQUIPMENT AND DEVICE GROUND AS REQUIRED BY CODE. m
<br /> BEST JUDGMENT OF THE CONFIGURATION,BUT NO GUARANTEE IS MADE AS TO THEIR CORRECTNESS.
<br /> A.ALL NEW AND EXISTING RECEPTACLES TO HAVE GROUNDED POLES. O
<br /> 2. THE CONTRACTOR SHALL INSPECT THE EXISTING INSTALLATION PRIOR TO BIDDING AND SHALL U
<br /> MAKE HIS OWN JUDGMENT AS TO THE WORK REQUIRED TO PROVIDE A COMPLETE INSTALLATION AND
<br /> q B DEMOLITION WITHIN THE INTENT OF THE CONTRACT DOCUMENTS. SECTION 260533-RACEWAYS AND BOXES F-
<br /> = D.EXISTING SYSTEM DRAWINGS A. PROVIDE RACEWAY SYSTEM COMPLETE AND IN CONFORMANCE WITH CODE. INSTALL RACEWAYS LU
<br /> y, THE DRAWINGS SHOW PORTIONS OF THE EXISTING SYSTEMS WHICH ARE DERIVED FROM RECORD CONCEALED IN CONSTRUCTION FOR ALL AREAS UNLESS EXPOSED RACEWAYS ARE SPECIFICALLY LULU
<br /> 00 DRAWINGS. THE DRAWINGS ARE INCOMPLETE AND NO GUARANTEE IS MADE TO THEIR CORRECTNESS. SHOWN.
<br /> �a THE CONTRACTOR SHALL ASSUME THERE IS 20%MORE ELECTRICAL SYSTEMS THAN SHOWN ON THE I,,
<br /> DEMOLITION AND EXISTING SYSTEM DRAWINGS. B. PROVIDE 1" RACEWAY FOR HOMERUNS AND MAJOR CEILING CONDUIT RUNS. RACEWAY DROPS CY
<br /> b DOWN WALLS AND RACEWAY CARRYING 2 CURRENT CARRYING CONDUCTORS CAN BE 3/4".MINIMUM Lu
<br /> E.DEMOLITION WORK RACEWAY SIZE IS 3/4". Z
<br /> R ALL DEMOLITION WORK REQUIRED UNDER THIS CONTRACT IS NOT SHOWN ON THE DRAWINGS. THELu
<br /> _ CONTRACTOR SHALL REMOVE ALL ELECTRICAL EQUIPMENT IN THE AREA BEING REMODELED WHICH IS C.PROVIDE PULLWIRE IN ALL EMPTY RACEWAYS. (�
<br /> NO LONGER IN SERVICE PRESENTLY OR AS A RESULT OF THIS CONTRACT. THE DEFINITION OF
<br /> o ELECTRICAL EQUIPMENT IS ANY EQUIPMENT MENTIONED IN THE NATIONAL ELECTRICAL CODE. J z
<br /> a D. INTERIOR RACEWAYS: ELECTRICAL METALLIC TUBING (EMT) WITH STEEL COMPRESSION OR SET Q W
<br /> F.TEMPORARY ELECTRICAL EQUIPMENT SCREW FITTINGS.INDENTOR,DRIVE-ON AND PRESSURE CAST ON DIE CAST TYPE SET SCREW FITTINGS U C
<br /> i REMOVING, TEMPORARY HANGING BY CHAINS AND REINSTALLING IN CEILINGS OF LIGHT FIXTURES, 12 ARE NOT ACCEPTABLE. W
<br /> SPEAKERS, DETECTORS, EXIT SIGNS AND OTHER ELECTRICAL EQUIPMENT IS NOT SHOWN ON THE LLJ
<br /> E.RACEWAY PENETRATIONS: PENETRATIONS THROUGH FIRE RATED CONSTRUCTION SHALL BE SEALED
<br /> DRAWINGS. THE CONTRACTOR SHALL INVESTIGATE THE CEILING DEMOLITION WORK AND INCLUDE THIS USING 3M FIRE BARRIER CAULK,NELSON ELECTRIC FLAMESEAL OR T&B FLAMESAFE OR USE OTHER
<br /> WORK IN THE BID. THE SEQUENCE OF WORK SHALL BE (1) REMOVE AND STORE FIXTURES, METHOD APPROVED BY THE ARCHITECT. Q
<br /> i DETECTORS AND SPEAKERS ALONG WITH REMOVAL OF CEILING, (2) PROVIDE TEMPORARY SUPPORT J J Q
<br /> FOR WIRED FIXTURES AND DEVICES TO BE REINSTALLED IN NEW CEILING AT APPROXIMATELY THE F. PROVIDE AND SIZE OUTLET BOXES FOR DEVICES SUCH AS RECEPTACLES, SWITCHES AND LIGHT Z
<br /> S SAME LOCATION. USE CHAINS FOR LIGHTING FIXTURE SUPPORT, (3)CLEAN AND REINSTALL IN THE FIXTURES AND PULL BOXES AS REQUIRED IN THE CONDUIT SYSTEM PER THE NATIONAL ELECTRICAL O uJ
<br /> a NEW OR REPLACED CEILINGS PROVIDE NEW LAMPS WHEN SO NOTED. PROVIDE TEMPORARY CODE. CONTRACTOR SHALL COORDINATE WITH OWNER TO DETERMINE ANY SPECIALTY INSTALLATION 3 11':� Q
<br /> a RELOCATION OF EXIT SIGNS CONNECTED TO EXISTING EMERGENCY CIRCUITS AND REINSTALL IN THE REQUIREMENTS DUE TO FIRE RATINGS,CORE WALLS,ETC. Lu C/') 3
<br /> ORIGINAL LOCATION WHEN EXIT IS REACTIVATED.
<br /> lE
<br /> G. INTERIOR WIRING: PRESSED STEEL, ZINC COATED WITH PLASTER RING WHERE APPLICABLE. w
<br /> G.PREMIUM TIME MOUNT OUTLET BOXES FOR RECEPTACLES AND OTHER DEVICES AT 18",UNLESS OTHERWISE NOTED. U w
<br /> o PREMIUM TIME SHALL BE INCLUDED IN THE BASE BID FOR ELECTRICAL SYSTEM(S)OUTAGES AND FOR Z r rl w
<br /> OTHER WORK AS REQUIRED BY THE SCHEDULE, AS SHOWN ON THE DRAWINGS AND AS NOTED IN �J
<br /> OTHER DIVISIONS OF THE SPECIFICATIONS. (D Lu H
<br /> 1 o z =
<br /> H.WORK OUTSIDE OF REMODEL AREAS
<br /> ffi CAUTION - THIS WORK IS NOT SHOWN ON THE CONTRACT DOCUMENTS. PROVIDE NEW WIRING 1 0
<br /> U 11 -
<br /> i
<br /> o E A Project No.:204823055
<br /> i EODD
<br /> Scale:NONE
<br /> U A DCH NCA 2025.08.01
<br /> ya Dw Mqg. Chkd. YYYY.MM.DD
<br /> a
<br /> Title
<br /> SPECIFICATIONS,
<br /> SYMBOLS ABBREVIATIONS
<br /> o Drawing No.
<br /> E0.00