Laserfiche WebLink
PERMW OMMENUFSPONSE hT9 <br /> June 20, 2025 ku <br /> JTK ENGINEERING <br /> Project: M2505-075 1020 10TH ST HVAC I PLUMBING I ENERGY <br /> Please see our response to the permit comments below. <br /> Subject: Mechanical <br /> Review Comment No. 1: Please address IMC Section 510. Please explain what is being exhausted and if it meets <br /> the IFC's definition of toxic. <br /> • Response: The exhaust fan is discharging general ventilation room air. <br /> Review Comment No. 2: Please provide the height above the adjacent roof. Please show that the appropriate <br /> clearances are provided (air intakes, mechanical equipment, right of way, etc.) <br /> • Response: The new exhaust louver is located 10 feet above existing building intake and exhaust openings. <br /> It is also 10 feet from the adjacent lower roof and 2 feet above it. The exhaust discharge location is within <br /> the property, approximately 90 feet from the property fence line to the west. Please below images for <br /> reference. <br /> ew Louver location <br /> City of Everett Permit Services <br /> EVERETT Reviewed for Permit 07/07/2025 <br /> WNSHINCaTON <br />