Laserfiche WebLink
CK Engineering LLC. <br /> Janet Back <br /> 1818 Bailey Ave <br /> Everett, WA <br /> August 23, 2015 <br /> Re: Lateral design upgrades review for residence located at 1818 Bailey Ave, <br /> Everett WA. <br /> Plan Check Number: CW1506-002_—' <br /> CK Engineering Job# 15-024 <br /> Dear Ms. Back: <br /> CK Engineering LLC reviewed the proposed changes for the above residence <br /> in order to determine if the lateral load resisting elements (wood panel shear walls) <br /> at the Living room, north elevation would need to be upgraded per current code <br /> requirements. <br /> It is our understanding the Living room existing window openings prior to <br /> remodeling contained two rows of windows. The bottom row was made of 34"x65" <br /> windows at each end, while two windows with total width of 12'-4" and 65" height <br /> were located at the center of the wall. The second row of windows were located <br /> directly above the center windows with approximate dimensions of 8ft wide x 4ft <br /> high. Please see photo below. <br />