,, �Sy,�tem Design <br /> Altesnatiae 11�ethod(: I?a�c*s 0 to 75 dneZ�es in Fern�retPs <br /> Two ADP nozzles can be used in ducts with a perimeter of 0 up to 75 inches (1651 to 1905 mm). The <br /> ratio of the longest to shortest perimeter sides shall not exceed 3 to 1. <br /> One of these nozzles is pointed into the duct and the other is pointed into the plenum. <br /> The tip of the upper nozzle, of the pair of nozzles required for each duct, shall be positioned in the <br /> center of the duct opening and above the plane of the hood-duct opening between 1 in. (25 mm) and <br /> 24 in. (610 mm). The duct length is unlimited. See Figure 3-32. <br /> Note: When a damper is present at the hood duct opening, the duct nozzles are to be located above <br /> the damper and should not interfere with the operation of the damper. <br /> Note: All Range Guard systems are listed by UL and ULC for use with the e�aust fan either on or <br /> off when the system is discharged. <br /> DUCT <br /> 24 in.(610 mm) <br /> MAX. <br /> 1 in. <br /> (25.4 mm) � I <br /> MIN. + <br /> HOOD <br /> Figure 3-32. Optional Duct Nozzle Placement <br /> ,..,� � � <br /> �.�� <br /> April 2009 3-38 P/N 60-9127100-000 <br />