Laserfiche WebLink
8/12/2019 City of Everett Page 1 <br /> 1:02:38PM <br /> INSPECTION ACTIVITY REPORT <br /> Permit No. K1807-001 Site Address 4532 EVERGREEN WAY <br /> Applied 7/2/2018 Applicant Lot <br /> Approved 7/30/2018 Owner KANE MICHAEL&CHERYL Block <br /> Issued 2/21/2019 Contractor ALPINE FIRE&SAFETY SYSTEMS Tract <br /> Parent Permit No. Description REVISION TO HOOD SUPPRESSION SYSTEM <br /> Notes <br /> Scheduled Completed Type Inspector Result Remarks Inspector's Comments <br /> 3/27/2019 3/27/2019 SPRINKLER CHA CORRECTION (3/27/2019 11:37 AM CHA) <br /> 05-COMMERCIAL Missing nozzle on griddle hood,was never <br /> installed. <br /> Fryers and griddle need to be centered in <br /> the hoods. <br /> Overdue for hood cleaning <br /> Fryers need low proximity nozzles with new <br /> foil covers <br /> Class K extinguisher needs to be moved <br /> loft from cooking area <br /> Wood table being used as prep table near <br /> fryers must be removed. <br /> (3/27/2019 11:47 AM CHA) <br /> Link temperature not listed on plans.Need <br /> to conduct a heat test <br /> 4/16/2019 4/16/2019 SPRINKLER CHA CORRECTION (4/16/2019 6:52 AM CHA) <br /> 06-COMMERCIAL Greg @ Alpine 360-707-8406 <br /> (4/16/2019 11:56 AM SDA) <br /> Need to move appliances to get correct <br /> coverage. <br /> Remove wood prep table. <br /> 8/2/2019 8/2/2019 ADMIN USE KLC APPROVAL <br /> ONLY** <br /> 8/2/2019 8/2/2019 SPRINKLER CHA APPROVAL (7/22/2019 1:40 PM CHA) <br /> 06-COMMERCIAL Nisha 360-755-5444 <br /> 8/2/2019 8/2/2019 SPRINKLER CHA APPROVAL <br /> 05-COMMERCIAL <br /> INSP12 <br />