Laserfiche WebLink
� <br />�� ��� <br />�� �� <br />�� <br />FRAN KLI N <br />ENGINEERING <br />MECHANICAL CONSULTING <br />November 28, 2011 <br />RE: Majestic Glove <br />2610 W Casino Rd <br />Everett, WA <br />625 Fourth �ivenue <br />Suite 202 <br />Kirkland, WA 98033 <br />� <br />Pri 425 827-332h <br />FAX 425 827-6252 <br />hvacC�franklineng.com <br />IVELOPE SUMMARY <br />New construction of Office/Warehouse building. Entire building is conditianed space. <br />Project complies with 2009 WSEC using the Component Performance approach. <br />Other Roof: R-21 rigid insulation. U= 0.046, default (Table 10-7G). <br />Wall #1 fOpaque, Exterior, At Warehouse Floor to 10'-0" AFF (except as noted below) <br />and at Oftice Floor to 10'-0" AFF and Upper Level to 10'-0" AFF): Concrete, min. <br />6" thick, furred with metal studs, 3-1 /2", 24" oc with R-15 batt insulation, <br />U = 0.101, calculated. <br />Wall #2 (Opaque, Exterior, Floor to 10'-0" at Warehouse along West wall Grids 2-8 and <br />along East wall Grids 5-9): Concrete, min. 6" thick, with NO insulation, U=0.61 <br />default (Table 10-5B(1)). <br />Wall #3 (Opaque, Exterior, 10'-0" AFF to structurel: Concrete, min. 6" thick, with R-15 <br />batt insulation stickpinned to concrete, U= 0.063, calculated. <br />Doors (Opaque, Man): Insulated metal, U= 0.60, default (Table 10-6}. <br />Doors (Opaque, Overhead): 2" thick, R-17, insulated metal, U=0.057, per manufacturer <br />(Wayne Dalton Thermospan 200-20 or approved equal). <br />Slab on Grade: No Insulation, F=0.73, default (Table 10-2). <br />