• <br />� 12. Specify roof overhang on framing plan, eave details and elevations (see #14 <br />below.) <br />Sheet AF1.1 — Dimensions added showing roof overhang to be "18" MAX." <br />Sheet A1.0 — Detail 7- Dimension added showing roof overhang to be "18" <br />MAX." <br />Added sheet A4.0 ELEVATIONS and dimensions showing roof overhang to <br />be "18" MAX." <br />✓ 13. Note on plans "110 volt smoke alarms with battery back-up and <br />interconnected." <br />Sheet A1.0 — REVISE KEYNOTE 1.12 TO READ "110V SMOKE DETECTOR <br />W/ CARBON MONOXIDE ALARM WITH BATTERY BACK-UP AND <br />INTERCONNECTED." <br />Sheet A1.0 — REVISE KEYNOTE 1.13 TO READ "110V SMOKE ALARMS <br />WITH BATTERY BACK-UP AND INTERCONNECTED." <br />,/ 14. Provide elevation drawings for all four sides. Show window sill height above <br />finished floor, roof pitch, roof overhang, siding, fireplace cantilever and <br />exterior porches & stairs. <br />ADD SHEET A4.1 — ELEVATIONS. <br />SHEET G1.0 — ADD SHEET A4.0 TO SHEET INDEX. <br />�15. Provide minimum 22" x 30" attic access located in hallway or other readily <br />accessible location. Minimum unobstructed headroom in the attic space shall <br />be 30 inches. Show on plans. <br />Sheet A1.0 — Added attic access panel in hallway. <br />Sheet A1.0 — ADD KEYNOTE 1.15: "22x30" ATTIC ACCESS. MINIMUM <br />UNOBSTRUCTED HEADROOM IN THE ATTIC SPACE SHALL BE 30"." <br />✓16. Insulation of ducts shall comply with the requirements of table 5-11 WA State <br />Energy Code. <br />Sheet AF1.0 — ADD GENERAL NOTE: "MECHANICAL — ALL DUCTWORK IN <br />UNHEATED SPACE SHALL BE INSULATED TO COMPLY WITH THE <br />REQUIREMENTS OF TABLE 5-11 OFF THE WASHINGTON STATE ENERGY <br />CODE." <br />