Laserfiche WebLink
1 <br /> f <br />�� <br /> Blan Check�YBS 1824 <br /> June 24, 1996 <br /> Page 2 of 2 <br /> 6. Plrase indicatc access to upper raof area. <br /> 7. One shower must be accessible per Section 1106.11.10. <br /> 8. Please indicate toilet room dimensions such as stall size, fixture heights, ekc. <br /> 9. The building must be of one hour fire resisdve construction throughout per Section <br /> 303.2.2.1. Please provide tested assemblies for roof and wall constructions. <br /> 10. Please indicate wall bracing for walls that stop at suspended cellings. <br /> 11. Slab edge insulation must be placed on the exterior and extend verkically from the <br /> tap of slab to the top of footings. Scxtion-1311.5. <br /> 12. Please provide engineering calculations for `awnings" (canopies). <br /> 13. Please provide energy calculadons or indicate prescriptive insulation values on <br /> plans. <br /> 14. Ple�;se provide lighdng power allowance calculadons for interios arid ezterior <br /> lighting including parldng lot lighting. <br /> Upon resubmitfal of the drawings, youc application will be given priority and plan <br /> nwiew will rec�mence. <br /> All required submitfals shall be of sofficient detail and conhain safficient informadon to <br /> ensure that the proposed suucture will be constructed in compliance with all aidopted <br /> codes. <br /> Sincerel <br /> - � <br /> Jef . McF <br /> Associate Engineer/Building <br /> n:yv,eua� <br />