r <br />�, �� , ; s'.,y�' � ,,.s <br />� <br />� <br />� �,''`, � t <br />3. A roof plan showing the location of the exhaust equipment and make up air are required <br />for plan review. Exhaust outlets should be located per IMC 501.3.1 for minimum <br />separations from intakes and property lines. <br />Applicable codes include: 2012 International Building Code (IBC), the 2012 International Fire <br />Code (IFC), the 2012 International Mechanical Code (IMC), the 2009 Washington State Energy <br />Code (WSEC), and the Accessible and Usable Buildings and Facilities A117.1-2009 (ICC/ANSI) <br />adopted by the State of Washington, as amended by the City of Everett Municipal Code (EMC). <br />These comments address building issues only. Revisions or additions may be required by other <br />departments (such as Utilities, Planning or Fire). <br />All required submittals must be of sufficient detail and information to ensure that the proposed <br />structure will be constructed in compliance with all adopted codes. You can reach me directly to <br />discuss this letter at mhaley@everettwa.gov or by phone at 425-257-8813. <br />Cc: Zachary Christopher, Snohomish Health District <br />Steve Miller <br />Darold Pons <br />Charles Johnstone <br />